CCL Cooling Load Calculation
CCL Cooling Load Calculation
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 14 8.0833
1 14 8.0833
1 22 8.0833
1 22 8.0833
0 14 22
Solar radiation through glass
Lightening
Factor W BF CLF
8 3.4 36 1.1 1
Sum =
People
n qs ql CLF Qs = n x qs x CLF
mula 6 400 500 1 2400
(78 - tR) + (ta - 85)
-7
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr
Bottle Blowing 1 3 10236
Conveyer Belt 1 3 10236
Sum = 20472
ass Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 31940.85
0
Formula
Q = 3.4 x W x BF x CLF
1077.12
1077.12
Ql = n x q l Q = Qs + Ql
3000 5400
Sum = 5400
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Oral Filling Liquid 1
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 15.3332 8.0833
1 15.3332 8.0833
1 27.4998 8.0833
1 27.4998 8.0833
6 15.3332 27.4998
31
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
8 3.4 80 1.25 1 2720
Sum = 2720
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 2 400 500 1 800 1000
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr
Indian Syrup Filling M/C 1 15 51180
Conveyer 1 3 10236
Sum = 61416
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 71077.34
0
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
1800
1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Oral Filling Liquid 2
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 15.3332 8.0833
1 15.3332 8.0833
1 20.1666 8.0833
1 20.1666 8.0833
2 15.3332 20.1666
31
Solar radiation through glass
Lightening
Sum = 42650
ass Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 49069.56
0
Formula
Q = 3.4 x W x BF x CLF
538.56
538.56
Ql = n x q l Q = Qs + Ql
1000 1800
Sum = 1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Liquid Manufacturing
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 24 8.0833
1 24 8.0833
1 19 8.0833
1 19 8.0833
0 24 19
Solar radiation through glass
Direction A SHGF SC
E
W
N
S
Lightening
Number Factor W BF
6 3.4 36 1.1
People
n qs ql CLF
mula 3 400 500 1
(78 - tR) + (ta - 85)
-7
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr
Syrup Manufacturing 4 10 136480
Pump 3 1.5 15354
Sum = 151834
through glass
Formula CFM TC Wi' Wo'
CLF Q = A x SHGF x SF x CLF
0
0 To
0
0 Total cooling load =
Sum = 0
Sensible Heat gain
CFM
ening
Formula
CLF Q = 3.4 x W x BF x CLF
1 807.84
Sum = 807.84
ple
Qs = n x qs x CLF Ql = n x q l Q = Qs + Ql
1200 1500 2700
Sum = 2700
uipment and devices
Ventilation
Factor Factor Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Qs + Ql
1.1 0.68 0 0 0
Sum = 0
Total cooling load
157002.7
155502.7
2654.082
Blistering 4
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 13.5831 8.0833
1 13.5831 8.0833
1 9.2499 8.0833
1 9.2499 8.0833
3 13.5831 9.2499
50
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
2 3.4 36 1.1 1 269.28
Sum = 269.28
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 4 400 500 1 1600 2000
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
Alu Alu Old 540 1 10.2 24361.68 0.7
Sum = 24361.68
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 29467.26
0
Sensible Heat gain 27467.26
CFM 468.8045
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
3600
3600
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Blistering 3
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 19.2499 8.0833
1 19.2499 8.0833
1 9.5831 8.0833
1 9.5831 8.0833
7 19.2499 9.5831
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
3 3.4 36 1.1 1 403.92
Sum = 403.92
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 4 400 500 1 1600 2000
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
Alu Alu New 548 1 9.2 21973.28 0.7
Sum = 21973.28
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 27536.71
0
Sensible Heat gain 25536.71
CFM 435.8543
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
3600
3600
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Blistering 2
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 19.2499 8.0833
1 19.2499 8.0833
1 9.3332 8.0833
1 9.3332 8.0833
4 19.2499 9.3332
Solar radiation through glass
Lightening
Sum = 31049.2
ss Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 36648.1
0
Sensible Heat gain 34648.1
CFM 591.3655
Formula
Q = 3.4 x W x BF x CLF
403.92
403.92
Ql = n x q l Q = Qs + Ql
2000 3600
Sum = 3600
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Blistering 1
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 19.2499 8.0833
1 19.2499 8.0833
1 9.3332 8.0833
1 9.3332 8.0833
4 19.2499 9.3332
Solar radiation through glass
Lightening
Sum = 40841.64
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 46225.68
0
Sensible Heat gain 44225.68
CFM 754.8333
Formula
Q = 3.4 x W x BF x CLF
403.92
403.92
Ql = n x q l Q = Qs + Ql
2000 3600
Sum = 3600
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Encapsulation 1
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 10 8.0833
1 10 8.0833
1 20.2499 8.0833
1 20.2499 8.0833
3 10 20.2499
50
Solar radiation through glass
Lightening
Sum = 27978.4
ass Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 33857.86
0
Sensible Heat gain 31857.86
CFM 543.7422
Formula
Q = 3.4 x W x BF x CLF
403.92
403.92
Ql = n x q l Q = Qs + Ql
2000 3600
Sum = 3600
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Compression 4
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 9.4165 8.0833
1 9.4165 8.0833
1 20.2499 8.0833
1 20.2499 8.0833
3 9.4165 20.2499
50
50
Solar radiation through glass
Lightening
Sum = 34802.4
ass Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 38544.23
0
Sensible Heat gain 37544.23
CFM 640.7959
Formula
Q = 3.4 x W x BF x CLF
538.56
538.56
Ql = n x q l Q = Qs + Ql
1000 1800
Sum = 1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Compression 3
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 14.3332 8.0833
1 14.3332 8.0833
1 20.2499 8.0833
1 20.2499 8.0833
3 14.3332 20.2499
50
50
Solar radiation through glass
Lightening
Sum = 17913
ass Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 21944.27
0
Sensible Heat gain 20944.27
CFM 357.4718
Formula
Q = 3.4 x W x BF x CLF
538.56
538.56
Ql = n x q l Q = Qs + Ql
1000 1800
Sum = 1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Compression 2
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 14.3332 8.0833
1 14.3332 8.0833
1 20.2499 8.0833
1 20.2499 8.0833
3 14.3332 20.2499
50
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
4 3.4 36 1.1 1 538.56
Sum = 538.56
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 2 400 500 1 800 1000
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
Compression 1428 1 10.2 24361.68 0.7
Sum = 24361.68
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 28367.13
0
Sensible Heat gain 27367.13
CFM 467.0956
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
1800
1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Compression 1
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 14.3332 8.0833
1 14.3332 8.0833
1 19.833 8.0833
1 19.833 8.0833
10 14.3332 19.833
50
50
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
4 3.4 36 1.1 1 538.56
Sum = 538.56
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 2 400 500 1 800 1000
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
Compression 1401 1 7.5 17913 0.7
Sum = 17913
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 21971.45
0
Sensible Heat gain 20971.45
CFM 357.9356
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
1800
1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Granulation 3
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 34.6664 8.0833
1 34.6664 8.0833
1 19.833 8.0833
1 19.833 8.0833
10 34.6664 19.833
B A B
50 68 50
50 120 50
50
Solar radiation through glass
Lightening
Formula
Q = 3.4 x W x BF x CLF
1077.12
1077.12
Ql = n x q l Q = Qs + Ql
1000 1800
Sum = 1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Granulation 2
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 17.7497 8.0833
1 17.7497 8.0833
1 29.7497 8.0833
1 29.7497 8.0833
9 17.7497 29.7497
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF x n
4 3.4 36 1.1 1 538.56
1 3.4 250 1.25 1 1062.5
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 2 400 500 1 800 1000
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
FBD 1 70.5 168382.2 0.7
MDM 1 4.1 9792.44 0.7
High Speed Mixer & Granulator 1 9.5 22689.8 0.7
Slurry Mixer 1 8.9 21256.76 0.7
Granulator 1 2 4776.8 0.7
Max 168382.2
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 173903.2
0
Formula
Q = 3.4 x W x BF x CLF x n
Sum = 1601.06
Q = Q s + Ql
1800
1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Granulation 1
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 10.4998 8.0833
1 10.4998 8.0833
1 30.1666 8.0833
1 30.1666 8.0833
2 10.4998 30.1666
Solar radiation through glass
Lightening
Formula
Q = 3.4 x W x BF x CLF
807.84
807.84
Ql = n x q l Q = Qs + Ql
1000 1800
Sum = 1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Tray Drier
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 10.4998 8.0833
1 10.4998 8.0833
1 9.2499 8.0833
1 9.2499 8.0833
3 10.4998 9.2499
Solar radiation through glass
Lightening
Sum = 12897.36
ss Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 17164.07
0
Formula
Q = 3.4 x W x BF x CLF
134.64
134.64
Ql = n x q l Q = Qs + Ql
1000 1800
Sum = 1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Encapsulation 2
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 10.4998 8.0833
1 10.4998 8.0833
1 19 8.0833
1 19 8.0833
0 10.4998 19
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
3 3.4 36 1.1 1 403.92
Sum = 403.92
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 4 400 500 1 1600 2000
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
Capsule M/C 1417 1 6.1 17691.22 0.85
Capsule M/C 1432 1 9.5 27551.9 0.85
Sum = 45243.12
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 53567.16
0
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
3600
3600
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Direct Compression
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 10.4998 8.0833
1 10.4998 8.0833
1 9.6664 8.0833
1 9.6664 8.0833
8 10.4998 9.6664
Solar radiation through glass
Lightening
Sum = 20813.2
ass Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 25376.66
0
Formula
Q = 3.4 x W x BF x CLF
403.92
403.92
Ql = n x q l Q = Qs + Ql
1000 1800
Sum = 1800
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Coaating Area 2
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 10.4998 8.0833
1 10.4998 8.0833
1 6.5831 8.0833
1 6.5831 8.0833
7 10.4998 6.5831
Solar radiation through glass
Lightening
Sum = 18220.08
ass Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 21152.48
0
Formula
Q = 3.4 x W x BF x CLF
269.28
269.28
Ql = n x q l Q = Qs + Ql
500 900
Sum = 900
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Coating Area 3
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 10.4998 8.0833
1 10.4998 8.0833
1 6.7497 8.0833
1 6.7497 8.0833
9 10.7497 6.7497
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
2 3.4 36 1.1 1 269.28
Sum = 269.28
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 1 400 500 1 400 500
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
Coating Pan 333 1 6.1 12487.92 0.6
Sum = 12487.92
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 15460.93
0
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
900
900
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Auto Tablet Coating
Formula
to DR ta = to - DR/2
E 0 0 0
W 0 0 0
N 0 0 0
S 0 0 0
Formula
LM CLTD tR ta CLTDc = LM + CLTD + (78 - tR) + (ta - 85)
E 0 0 0 0 -7
W 0 0 0 0 -7
N 0 0 0 0 -7
S 0 0 0 0 -7
B A B
in
1 18.4998 8.0833
1 18.4998 8.0833
1 13.4998 8.0833
1 13.4998 8.0833
6 18.4998 13.4998
ouble Window
Solar radiation through glass
Formula
Direction A SHGF SC CLF Q = A x SHGF x SF x CLF
E 0
W 0
N 0
S 0
Sum = 0
Lightening
Formula
Number Factor W BF CLF Q = 3.4 x W x BF x CLF
8 3.4 36 1.1 1 1077.12
Sum = 1077.12
People
n qs ql CLF Qs = n x qs x CLF Ql = n x q l
mula 2 375 625 1 750 1250
(78 - tR) + (ta - 85)
-7 Sum =
-7 Equipment and devices
-7
-7 Equipment n kw Btu/hr Factor
Thia coat M373 1 44.5 121467.2 0.8
Sum = 121467.2
10.12227 Tons
Ventilation
Formula CFM TC Wi' Wo' Factor Factor
Q = A x SHGF x SF x CLF 1.1 0.68
0
0 Total cooling load
0
0 Total cooling load = 128091.8
0 10.67432
Formula
Q = 3.4 x W x BF x CLF
Q = Q s + Ql
2000
2000
Ventilation
Qs = 1.1 x CFM x TC Ql = 0.68 x CFM x (Wo' - Wi') Qt = Q s + Q l
0 0 0
Sum = 0
Total cooling load
Calculated
Cooling load (Ton) CFM Planned CFM
Btu/hr Tons
Auto Tablet Coating 126842 11 2165 1500
Coating Area 3 15461 1 264 330
Coating Area 2 21152 2 361 530
Direct Compression 25377 2 433 600
Encapsulation 2 53567 4 914 950
Tray Drier 17164 1 293 300
Granulation 1 123806 10 2113 1278
Granulation 2 173903 14 2968 1388
Granulation 3 166399 14 2840 1332
Compression 1 21971 2 375 736
Compression 2 28367 2 484 780
Compression 3 21944 2 375 780
Compression 4 38544 3 658 514
Encapsulation 1 33858 3 578 950
Blistering 1 46226 4 789 340
Blistering 2 36648 3 626 370
Blistering 3 27537 2 470 485
Blistering 4 29467 2 503 485
Liquid Manufacturing 157003 13 2680 5600
Oral Liquid Filling Area 2 49070 4 838 1715
Oral Liquid Filling Area 1 71077 6 1213 2350
Bottle Blowing 31941 3 545
Difference AHU
-665 2 346.3849
66 2
169 2 2550 cfm
167
36
7
-835
-1580
-1508
361 33
296 33
405 33
-144 33
372
-449
-256
15
-18
2920
877
1137
-545