NUEVOSOL ENERGY PVT. LTD.

PROJECT : Design.by: BCC


DOC.TITLE: Check.by BCC
DOC. NO : Rev:No 0 Appr. by

WIND LOAD CALCULATIONS AS PER EIT Standard-1018-46


Notes
·         The wind load is applied by using pressure coefficient method.
·         The variation of wind pressure  along the height of building is NOT considered.
· Simple Procedure only followed.

Location of Site as per Map A/B/C/D = D

10 Year Return Wind Velocity ( for Deflection ) v10 = 22.0 m/s

30 Year Return Wind Velocity ( For Strength ) v30 = 32.0 m/s

100 Year Return Wind Velocity ( For Post-Disaster ) v100 = 35.0 m/s

Typhoon Factor T = 1.22

Density of Air r = 1.250 kg/m3

Reference Velocity Pressure ( Deflection ) qdeflection = 302.5 N/mm2

Reference Velocity Pressure ( Strength ) qstrength = 952.6 N/mm2

Exposure Factor Ce = 0.9


( this takes care of Height + Terrain + Topography
Gust Effect Factor Cg = 1

Height of Structure ( top most point of rafter ) h = 1.5 m

Width of Structure b = 4.0 m

Length of Structure l = 20.0 m

Final Pressure before pressure Coeff ( Deflection ) Pd = 272.25 N/mm2

Final Pressure before pressure Coeff ( Strength ) Ps = 857.32 N/mm2

Roof Angle a = 15.0 degrees

Blockage j = 0.00 Tab. 7.6 - EC1-1-4

Positive Overall Force Coeff +cf = 0.70 Tab. 7.6 - EC1-1-4

Negative Overall Force Coeff -cf = -1.10 Tab. 7.6 - EC1-1-4

Orientation of Module = Potrait


-Z
Module dimensions
Load for Strength
L B kN No of Purlins kN/m
-cf -1.10 1.655 0.990 -1.545 2 -0.781 -X +X
+cf 0.70 1.655 0.990 0.983 2 0.497