FIRE RESISTANT CABLES
Cables for BS 5839-1 2013 Enhanced Grade, Standard Grade, BS EN 50200 & BS 6387 CWZ I Approvals with LPCB
& BASEC I Reduced installation time I Superior electrical performance I Pliable fire resistant cables I No toxic fumes
PERFORMANCE UNDER FIRE CONDITIONS
To BS 6387 CWZ
Circuit Integrity Resist ance to fire alone CAT C 3 hours at 950°C
Resistance to fire and water CAT W 15 mins at 950°C
Resistance to fire and mechanical shock CAT Z 15 mins at 950°C
Flame Retardancy BS EN 60332-1-2
Flame Propagation IEC 332 Part 1
FIRE RESISTANCE: Complies with IEC331 and BS 6387 CWZ when tested in a steel conduit
SMOKE EMISSION: Complies with low smoke emissions to BS EN 61034
ACID GAS: Acid gas emissions to BS EN 50267 (HCL level <0.5%)
FLAME RETARDANCE: BS EN 60332- 1-2
TEMPERATURE RANGE: -25°C to 90°C
VOLTAGE RATING: 600 / 1OOOV
CONSTRUCTION: Conductor - Plain annealed copper to BS EN 60228 class 2
Fire Barner - Mica tape
Insulation - Low Smoke, Halogen Free to BS EN 50363 - EIS
COLOURS: Blue, Brown. Green/Yellow. Other colours available on request
SUPPLIED LENGTHS: 100 and 500 metre drums. Other lengths available on request
APPROVALS: LPCB approved to BS 6387 CWZ when tested in a metal conduit
Conductor No. of Strands (mm) Nominal Cable Diametre (mm) Conductor Resistance ohm/km @20"C
CABLE DESCRIPTION: BS EN 50200 Class PH30 including Annex E, BS EN 50200 Class PH60
VOLTAGE RATING: 300 / 500V
COLOURS: White and Red sheath as standard. Other colours available on request
SUPPLIED LENGTHS: 100 and 500 metre reels. Other packaging/lengths available on request
No. of Cores 2 2 2 3 3 4 4
Conductor Area (mm•) 1.5 2.5 4.0 1.5 2.5 1.5 2.5
No. of Wires 1 7 7 1 7 1 7
Nominal Diamet er of Conductor (mm) 1.37 0.67 0.85 1.37 0.67 1.37 0.67
Nominal Insulat ion Thickness (mm) 0.70 0.80 0.80 0.70 0.80 0 .70 0.80
Nominal Cable OD (mm) 8.40 10.05 11.40 9.15 11 .05 10.20 11.65
Approx Cable Weight (k g/km) 93 135 189 127 177 146 211
CABLE DESCRIPTION: High performance, very f lexible with a double fire barrier system
VOLTAGE RATING: 300 / SOOV
COLOURS:
SUPPLIED LENGTHS:
APPROVALS:
Whit e and Red sheath as standard. Other colours available on request
100 and 500 metre reels. Other lengths available on request
LPCB and BASEC approved. This cable is designed to m eet the requirements of BS 5839-1
IW
'Enhanced Grade' BS 7629, BS 6387 CWZ, BS EN 50200. Class PH 120, BS 8434- 2
KEY APPLICATIONS: ·Enhanced ' fire resistance is recommended in systems and buildings in which cables need t o
operate correctly during a fire for longer than required for single phase evacuation.
Examples: Unsprinkled high-nse buildings with phased evacuat ion arrangements; premises of
such a nature/ size that areas remote from the fire could be occupied for a prolonged period
during a fire. any location where system integrity 1s essential in severe conditions.
No. of Cores 2 2 2 3 3 4 4
Conductor tvea (mm') 1.5 2.5 4.0 1.5 2.5 1.5 2.5
No of Wires 7 7 7 7 7 7 7
Nominal Diameter of Conductor (mm) 0.53 0.67 0.85 0.53 0.67 0.53 0.67
Nominal Insulation Thickness (mm) 0.80 0.80 0.80 0.80 0.80 0.80 0.80
Nominal Cable OD (mm) 9 .40 10.70 11.00 10.20 12.50 13.20 13.90
Approx Cable Weight (kg/km) 122 175 220 182 188 192 271
GUARDIAN™ GUARDIAN
The lightweight, easy to install, 'connect and protect' cable system
M ECHANICALLY PROTECTED CABLES
,"• '\ FUMEGUARD'N FUMEGUARD LOW SMOKE HALOGEN FREE MEDIUM & LOW VOLTAGE CABLES
LOW SMOKE HALOGEN FREE CABLES
$old1et Field Stadium 111 Clucago, the Savoy Hotel London. tile Duba, Metro and t11e Galway Cli~,c ,n lteland - Just some of tre 01c1ects rnat have chosen /OH Cables .
All our cables are manufactured with materials which are compliant
with RoHS and WEEE directives.