Line differential protection IED RED 670

Innovation from ABB

Advanced line differential protection extensive functionality with application


The RED 670 IED (Intelligent Electronic opportunities and expandable hardware to
Device) is designed for protection, monitor- meet your specific requirements.
ing and control of overhead lines and cables
with up to five line terminals. The phase RED 670 provides absolutely selective
segregated line differential protection of protection without time grading. All line
RED 670 enables reliable single/two/three short circuits and earth faults can be cleared
pole trip and auto-reclosing with synchro- instantaneously. Additionally, the high
check. In addition, this IED is capable of sensitivity of RED 670 allows for detection
handling transformer feeders, and genera- of small fault currents, which in turn allows
tor and transformer blocks. It provides an high resistive phase to earth faults to be
detected.
For maximum reliability of
your power system

Ready to use IEDs


The RED 670 IEDs are delivered pre-configured, type
tested and with default parameters for easy handling
of products – from ordering, engineering and com-
missioning to reliable operation. These IEDs are
equipped with complete functionality adapted for
four different configuration alternatives: single pole
breaker or multi-breaker arrangements with single or
three phase tripping. If needed, they can also be
easily adapted for your power system’s specific
requirements.

Protection for up to five line terminals


RED 670 provides phase segregated line differential
protection for two to five line terminal applications in
solidly or impedance grounded networks.

All individual phase currents in 11/2 and multi-breaker


configurations can be connected to RED 670 without
external summation. Therefore, each current will
always be correctly measured. This enables integra-
tion of a number of breaker related protection and
control functions and improves the stability of the line Extensive built-in protection for lines and cables
differential protection function. The RED 670 features integrated distance protection
to ensure fault clearance in case of communication
Power transformer in the protected zone failure. The full scheme distance protection provides
RED 670 is able to handle two or three-winding power independent phase selection, power swing detection
transformers in the protected zone. The line differ- and a wide range of scheme communication logics.
ential protection function handles all transformer The three-zone distance protection with six setting
winding vector groups and matches all transformer groups is further enhanced with load encroachment,
configurations with a simple parameter setting. This which increases the ability to detect high resistive
simplifies engineering since no auxiliary CTs or other faults on heavily loaded lines.
protection equipment is needed.
You can increase the functionality of your RED 670
Advanced stabilization methods are used for detection IEDs with optional back-up and multipurpose protec-
of transformer inrush current during energization to tion functions. Versatile overcurrent and thermal over-
ensure sensitive differential protection when a power load functions provide additional back-up protection.
transformer is included in the protected zone. Breaker failure protection allows high speed back-up
tripping of surrounding breakers and re-tripping of
When a transformer is connected to a tap on the line, the own breaker, for instance, to avoid operational
the line differential protection can be used without mistakes during testing. The distance and earth-fault
having an additional RED 670 installed at the trans- protection functions can communicate with the
former tap. remote end in any communications scheme.

For low fault currents the line differential protection Integrated protection and control
of RED 670 includes a useful definite time or inverse RED 670 features extensive functionality and expand-
time delayed characteristic. This enables selective able I/O. As a result, you can benefit from applica-
operation of other protection functions located at the tions with multiple algorithms and comprehensive bay
tapped transformer’s high or low voltage side. control functionality, such as synchrocheck, dead-line
detection and auto-reclosing in integrated and
distributed architectures.
Application examples

The integrated HMI of RED 670 • Connect RED 670 to redundant


allows secure and quick local channels to increase the depend-
control for stand-alone applications ability of the protection scheme.
RED 670 in three-terminal line application and provides back-up control for • Use GPS for time tagging of
with individual phase current exchange. substation automation systems. samples, which allows RED 670
It also enables instant access to to be used in switched networks
important data, such as settings, with unequal channel delays.
events and disturbance informa- • Use the echo-synchronization
tion. method for channels with stable
and equal delays in both
The RED 670 IEDs provide you directions without time tagging
with a future-proof concept based of samples via GPS.
on wide application flexibility,
RED 670 for line and three-winding transform- which makes these IEDs an excel-
er application with individual phase current lent choice for both new and
exchange and redundant communication.
retrofit installations.

Protection communication
according to the standards
Due to development in communi-
cation technologies and synchro-
nization of measurements, line
differential protection can be used
in a wide range of applications.
Consequently, you can also protect
long lines using line differential
protection and still maintain high
Make a major leap in
RED 670 for five-terminal line application in security. RED 670 can exchange grid reliability:
master-master or master-slave configuration.
phase current and binary signal
INVEST IN AN INTELLIGENT
information between up to five
SOLUTION
line terminals.
• RED 670 provides phase segregated line
The advanced interlocking func- The RED 670 IEDs are designed to differential protection for up to five line
tionality of RED 670 allows you communicate. They feature exten-
terminals including power transformers in
to avoid dangerous or damaging sive supervision of communication
the protected zone
switchgear operations, and thus channels and provide detailed
ensure personnel safety. The con- information for fast restoration of • RED 670 provides redundancy based on
trol is based on the select before the communication system. The integrated distance protection
operate principle to assure secure built-in C37.94 interface of the • RED 670 provides improved availability
operation and to avoid human RED 670 enables easy and safe through outstanding performance and
mistakes. standardized optical connection efficient information management for any
to “off-the-shelf” communication high voltage application
equipment.
• Ready-to-use RED 670 IEDs enable
You can: significant savings and reliable operation
• Choose either master-master or • RED 670 provides you with an integrated
master-slave operating mode solution for protection, control and
depending on your system’s monitoring
functionality or your economic
requirements.
RED 670 Technology summary:
Features • Secondary system supervision
• Fully IEC 61850 compliant - Fuse failure supervision
• Control, monitoring and protection - Current circuit supervision
integrated in one IED • Frequency functions
• Extensive self-supervision - Over- and under frequency protection
including analog channels - Rate-of-change frequency protection
• Six independent parameter • Multipurpose function
setting groups - General currrent and voltage
• Large HMI for visualization protection
of single line diagrams
• Ethernet interface for fast and Logic
easy communication with PC • Tripping logic
• Signal matrix for easy configura- • Trip matrix logic
tion of binary and analog signals • Configurable logic blocks
• Advanced multi-terminal line
differential protection Monitoring
• Extensive supervision of • Disturbance recorder
communication channels - 100 disturbances

Imageneering/Printed in Finland/04/2006
- 40 Analog channels 30 physical
Pre-configured solutions and 10 derived
• Pre-configured and tested solutions - 96 Binary channels
including default settings for: • Event list for 1000 events
Fast and efficient system integration - Single breaker with selective single • Disturbance report
or three phase tripping • Event and trip value recorders
RED 670 IEDs are more than just devices. - Double breaker with selective single • Fault locator
They utilize ABB’s unique connectiv- or three phase tripping • Event counters
ity package concept, which simplifies - 11/2 circuit breaker arrangements • Supervision of AC and mA input
with selective single or three phase quantities
the system engineering and reduces the tripping • LED indications with 6 red
risks of errors in system integration. This and 9 yellow LEDs
Most important protection functions
package contains a complete description • Line differential protection
of the specific IED, consisting of data Metering
- Phase segregated line differential • U, I, P, Q, S, f, and cosϕ
signals, parameters, addresses and IED protection for up to five line • Accuracy of AC input quantities,
terminals with charging current class 1,0 or 0,5
documentation. compensation • Inputs for mA measuring
- Power transformers can be • Pulse counting support for energy
The signal data is configured auto- included in the protected zone metering
- Suitable for multiplexed, route
matically based on the information switched, as well as dedicated Control functions
provided by the connectivity package fibre, communication networks • Apparatus control for eight
to efficiently integrate the IEDs in ABB’s using C37.94 protocol or 15 apparatuses
- Time synchronization with the • Ready to use interlocking modules
MicroSCADA Pro automation system. echo-method or built-in GPS for different switchgear arrangements
- Master-master or master-slave line • Several alternatives for reservation
differential communication functionality
arrangement • Synchro check, energizing check
• High impedance differential and synchronizing
protection for tee-feeders • Auto-recloser
• Back-up distance protection
- Full-scheme distance protection Communication
for up to three zones with load • IEC 61850-8-1 including
encroachment GOOSE messaging
- Power swing detection • IEC 60870-5-103
• Current • LON
- Instantaneous phase- and residual • SPA
overcurrent protection • Remote end communication for
- Four-step phase- and residual transfer of eight binary signals
directional overcurrent protection
with definite and inverse time Setting, configuration and
characteristics disturbance handling
- Directional residual overcurrent • Protection and Control IED
protection with scheme Manager PCM600
communication logic
- Current reversal and weak end Hardware
infeed logic • 1/1 x 19”, 3/4 x 19” or 1/2 x 19” case
- Thermal overload protection selected according to the number of
- Breaker failure protection required I/O modules
- Stub protection • Power supply modules from 24 to
- Pole discordance protection 250 V DC ± 20%
• Voltage • Up to 14 I/O modules in 1/1 x 19”
- Two step phase- and residual case
overvoltage protection with definite • Binary input module with 16 inputs
1MRK 505 166-SEN © Copyright 2005 ABB. All rights reserved.

and inverse time characteristics • Binary output module with 24 outputs


- Two step undervoltage protection • Binary input/output module with
with definite and inverse time 8 inputs and 12 outputs
characteristics • mA input module with 6 transducer
- Voltage three-phase differential for channels
capacitor banks • GPS time synchronization module
- Overexcitation protection • Remote end data communication
• Power system supervision modules for C37.94 and G.703
- Loss of voltage check configured • Test switch modul
ABB Power Technologies AB based on undervoltage protection
- Dead line detection included in
Substation Automation Products fuse failure supervision and switch
Technical details are available in the
SE-721 59 Västerås, Sweden RED 670 Buyer’s Guide.
on to fault logic
Tel. +46 21 342 000
Fax +46 21 32 42 23