Professional Documents
Culture Documents
SYSTEM PROTECTION
COORDINATION
Haïssam Nasrat P.Eng.
Introduction
8/28/2011 Primax Technologies Inc. 2
Very simple:
Introduction
8/28/2011 Primax Technologies Inc. 3
In this presentation, We’ll focus on
Fault (short circuit) coordination
assuming that overload protection is much
easier to define and manage.
Challenge
Better understand the whole DC backup
system fault behaviour in order to get to a
conclusion for safe and reliable solution.
Introduction
8/28/2011 Primax Technologies Inc. 4
In typical DC backup systems multiple sources
of energy are:
connected in parallel
simultaneously contributing into the fault
Each has different time constant and
amplitude
Fault effect reflected on AC mains must be
taken in consideration.
Rational
8/28/2011 Primax Technologies Inc. 5
Once breaking current of each source is
defined, one has to refer to the country
standard to specify the required
components
IEC std ratings and requirements may
vary from CSA, UL, IEEE, NFPA...
Rule
8/28/2011 Primax Technologies Inc. 6
Fuses, circuit breakers, switches, bus bars,
cables and other equipment need to
operate safely and reliably during fault:
Bottom line
8/28/2011 Primax Technologies Inc. 7
For the purpose of this discussion we define
the following:
Fault: refers to a very low impedance path
created when both polarity conductors are
shorted.
Failure: refers to over-current: Ex. Failing
load, leakage in battery or DC source has lost
regulation
As always, Ohm’s law applies: I = V /∑ Z
Z: individual component impedance including interconnecting
cable resistance.
Basics
8/28/2011 Primax Technologies Inc. 8
During fault evolution:
System voltage decays gradually.
The decay rate is related to impedance
rate-of-change
of all parallel sources over the period of
time before that protection devices open.
Effects
8/28/2011 Primax Technologies Inc. 10
To define minimum protection fault current
ratings, we need to evaluate the
contribution in the fault of each of the DC
components
Energy sources
8/28/2011 Primax Technologies Inc. 11
Let’s looks first to typical DC backup
system layouts:
Typical layouts
8/28/2011 Primax Technologies Inc. 12
Typical layout
8/28/2011 Primax Technologies Inc. 13
Redundant layout
8/28/2011 Primax Technologies Inc. 14
Redundant complex layout
8/28/2011 Primax Technologies Inc. 15
Typical nuclear layout
8/28/2011 Primax Technologies Inc. 16
Typical battery charger layout
8/28/2011 Primax Technologies Inc. 17
Battery Charger output under fault
8/28/2011 Primax Technologies Inc. 18
Contribution of different DC
components
8/28/2011 Primax Technologies Inc. 19
Depending on the battery technology, plate
thickness and number, specific gravity (in
the case of Lead acid batteries) available
fault current may vary.
Check with battery manufacturers for the
exact fault current.
Time constant: consider ≈ 10ms
Battery
8/28/2011 Primax Technologies Inc. 20
Typical 350AH battery fault current at its
terminals:
VLA 0.33” thick Flat calcium plate battery with
1.215 SG: 3200A
Tubular VLA 0.35” thick plate battery with 1.215
SG: 3400A
AGM VRLA : 4361A
Gel VRLA: 3750A
Ni-Cd Medium performance: 3200A
Battery example
8/28/2011 Primax Technologies Inc. 21
Capacitors are a source of large instantaneous
currents
Consider time constant ≈ 10 ms
Ex. 8 x 10,000uF-200VDC- ESR:20mΩ
with line impedance of 0.1Ω
Filter Capacitors
8/28/2011 Primax Technologies Inc. 22
8 x 10,000uF-
200VDC
ESR:20mΩ
with line
impedance of
0.1Ω
at t=0 1360 A
t=RC(s) 0,008 I at 1 RC 500 A
t=2 RC(s) 0,016 I at 2RC 184 A
AC mains impedance
Power transformer impedance
Inductive filter design
Other series components
Charger/rectifier
8/28/2011 Primax Technologies Inc. 24
Main concern is DC motors:
They operate switchgear, turbine lube pumps
During deceleration, motors act as a generators
contributing in the short circuit.
Inductive loads
8/28/2011 Primax Technologies Inc. 25
It’s not bad to have high fault availability from the
source to efficiently perform selective clearance.
Note
8/28/2011 Primax Technologies Inc. 26
Fuse or circuit breaker?
Protection
8/28/2011 Primax Technologies Inc. 27
Fuses Circuit Breakers
DC Interrupting KA ++ -
Flexibility (optional features) + +++++
Adjustable - +++
Resettable - ++++
Reliability (maintenance) ++ -
Arc flash protection + ++++
delay trip must be at minimum
Total Fault at X:
2x3500A
+
2x7250A
7250ASC 7250ASC =
21500A
+ inductive
HJD250 HKD400 HKD400
22kADC breakers
X
To
Inverter
Case
8/28/2011 Primax Technologies Inc. 36
Soft start
If fault occurs during the soft start period of the rectifiers, available currents can
be limited to lower value and chargers might shut down.
Connection cables
Interconnecting cable impedance reduces the fault current. This depends on their
material, cross section and length. In general, battery interconnecting cable
voltage drop is accounted in the short circuit capabilities of the batteries.
Ex. 4/0-259 strands copper cable has a DC resistance of 0.15 Ω /km.
Conclusion
8/28/2011 Primax Technologies Inc. 39
However,
in special or large applications,
Rules of thumb might lead to
overestimated values affecting the size
and cost of the installation.
Conclusion
8/28/2011 Primax Technologies Inc. 40
Take all precautions to properly define your
equipment protection and selectivity:
ASK FOR
Breaking capacity of protection device
Fault capabilities of all connected energy
sources
Conclusion
8/28/2011 Primax Technologies Inc. 41
QUESTIONS?