You are on page 1of 12

~b westin8nouse I.L. 41-759.

3A

INSTALLATloN . OPERATION . MAINTENANCE

- 3ENSEm©©TB©Ns
TYPE AR HIGH SPEED AUXILIARY RELAY
HIGH THRESHOLD DESIGN

CAUTION: Before putting protective relays into The moving and stationary contracts are mounted
service, remove all blocking which may have been on the molded insulation block. The molded
inserted for the purpose of securing the parts block and coil and lamination assembly are
during shipment. Make sure that all moving parts mounted to the frame. All contracts are fine
operate freely. Inspect the contacts to see that silver.
they are clean and can close properly. Operate
the relay to check the settings and electrical con- When the coil and resistor are energized, the
nections. armature is attracted to the laminations. The
card moves with the armature thereby operating
APPLICATION the moving contacts. The tension of the moving
contacts is the resetting force.
. The high threshold AR relay is a sensitive high
speed auxiliary relay with 4 N.O. contacts de- High speed operation is obtained by the lovy
signed to be secure against misoperation due to inertia of the moving parts. a sensitive electro-
inadvertent grounding of a station battery or the magnet, and the proper L/R ratio of the operating
trip lead. With the battery balanced with respect circuit.
to ground, the maximum momentary voltage that
can be applied to an auxiliary relay for either of
Operatlng lndlcator (a.I.) (When Supplled)
these grounds is half battery voltage. The opera-
ting level of the high threshold AR exceeds thesse The dc operation indicator is a small clapper
levels. type device. A magnetic armature is attracted to
the magnetic core upon energization of the switch.
CONSTRUCTION AND OPEPIATION During this operation two fingers on the armature
deflect a spring located on the front of the Switch,
AR unlt which allows the operation indicator target to
drop.
The relay consists of four stationary contact
screws, four leaf spring moving contacts, a moving
The front spring, in addition to holding the
armature and card assembly, which operates the
target, provides restraint for the armature and
moving contacts; a U shaped laminated core, a
thus controls the pickup value of the switch.
coil, a frame, a molded insulation block and a
series resistor. Refer to Fig. 1 and 2. A zener
Indlcallng Contactor Swllch Unll (lcs)
diQde is connected around the coil to eliminate
the generation of induced voltages upon interrup- (When Supplled)
tion of the coil circuit. The dc indicating contractor switch is a small
clapper type device. A magnetic armature, to
The armature and card assembly slip over a which leaf-spring mounted contacts are attached,
hinge pin which is inserted in the laminations. is attracted to the magnetic Core upon energizing

All po.s.sible contingencies which may arise during lnslallallon, operation, or maintenance, and all
de(ail.s and variations of lhis equipment do not purport to be covered by these instructions. [f J`urlher
in/ormalion i.s desired by purchaser regarding his particular installation. operation or maintenance Of
hi.s equipmenl, lhe local Westinghouse Electric Corporallon represenlatlve should be contacted.

SuPEl]SEDES I.L. 41-759.3, DATED MARCH 1976


® CHANGED SINCE PFIEVIOUS ISSUE. EFFECTIVE DECEMBEF] 1977
1 -IVIOLDED INSULATION BLOCK
2 -Nol]MALLY OPEN STATIONARY CON-
TACT SCREWS
3 -LEAF SPRING IVIOVING CONTACTS
4 -MOVING CARD ASSEMBLY
` 5 -RELAY COIL

® 6 -GAP AT THIS POINT WHEN CHECKING


RESET PRESSURE

Fig. 1. Type AFI Unit with four make c:ontacts (front view).

2
I.L. 41 -759.3A

® 1 -AI]MATURE GAP -MEASURE AT REAR END


OF GAP
2 -NORMALLY OPEN STATIONARY CON-
TACT SCREWS
3 -MOVING AF]IVIATUF]E
4 - U-SHAPED LAMINATED CORE
5 -AFIMATURE GAP ADJUSTMENT SET SCFIEW
® 6 -MEASURE CONTACT PRESSURE AT THIS
POINT

Fig. 2. Type AFI Unit with four make contacts (side view).

3
of the switch. When the switch closes, the moving lndlcat]ng Contactor Swltch unlt (ICS)
contacts bridge two stationary contacts, comple- (When Supplled)
ting the trip circuit. Also during this operation
The indicating contactor switch (ICS) has
two taps that provide a pickup setting of 0.2 or
::c°atefiin8oenrsth°enfrtohnet::T£:u:;;tdceh?eactt,o`;;:griE:
2 amperes. To change taps requires connecting
operation indicator target to drop.
the lead located in front of the tap block to the
desired setting by means of a screw connection.
The front spring, in addition to holding the
target, provides restraint for the armature and
0.2 ampere tap - 6.5 ohms dc resistance
thus controls the pickup value of the switch.
2.0 ampere tap -0.15 ohms dc resistance

CHARACTEHISTICS SETTINGS

The relay operates in 4 milliseconds for an AR Unlt


®-energy input of 10 watts. The reset time is typically
16 milliseconds. No settings are required.

The relay is adjusted to have a pickup value Operatlon lndlcators (01) (When Supplled)
less than 80% of rating, but not less than 50% of The only setting required on the 01 is the se-
the typie`al battery equalizing charge voltage. i.e. lection of the 0.2 or 2.0 ampere tap setting. This
minimum pickup is greater than selection is made by connecting the lead located
in front of the tap block to the desired setting by
TABLE I means of the connecting screw.
® MINIMulvI PICKUP VALUES
Indlcatlng Contactor Swltch (lcs)
28 volts for 48 volt rating
(When Supplled)
70 volts for 125 volt rating
140 volts for 250 volt rating No setting is required on the ICS unit except
the selection of the 0.2 or 2.0 ampere tap setting.
The relay will drop out at 10% of rated voltage This selection is made by comecting the lead
or higher. The relay is only available in a 4 make located in front of the tap block to the desired
contact configuration. Typical effective contact setting by means of the connecting screw.
bounce is outlined in Table II.-Contact Bounce. INSTALLATION

The relays should be mounted on switchboard


TABLE 11
CONTACT BOUNCE panels or their equivalent in a location free from
dirt, moisture, excessive vibration, and heat.
Mount the relay vertically by means of the four
Effective Bounce Time
mounting holes on the flange for semi-flush
Contact Loading in Millise6onds
mounting or by means of the rear mounting stud
. Normally open
or studs for projection mounting. Either a mount-
Dry Circuit 2
ing stud or the mounting screws may be utilized
10 Watt (one AR relay) 1
for grounding the relay. The electrical connection
Breaker Trip Coil .2
may be made directly to the terminals by means
of screws for steel panel mounting or to the
Contact Ratlng terminal studs furnished with the relay for thick
Each relay contact is rated 3 amps continuous panel mounting. The terminal studs may be easily
® and 30 amps long enough to trip a breaker. For removed or inserted by locking two nuts on the
interrupting rating see TABLE IV - CONTACT stud and then turning the proper nut with a
INTERRUPTING CAPABILITY. wrench.

4
I.L. 41-759.3A

For detailed FT case information refer to 6. Indicating Contractor Switch (ICS)


I.L. 41-076.
(When Supplied)

ADJUSTMENTS AND MAINTENANCE Close the main relay contacts and pass sufficient
dc current through the trip circuit to close the
The proper adjustments to insure correct contacts of the ICS. This value of current
operation of this relay have been made at the should be not greater than the particular ICS
factory and should not require readjustment after tap setting being used. The operation indicator
receipt by the customer. If the adjustments have target should drop freely.
been changed or the relay taken aparrfor repairs,
the instructions below should be followed. The contact gap should be approximately
.047" between the bridging moving contact
Acceptance Check and the stationary contacts. The bridging
moving contact should touch the stationary
The following check is recommended to insure contacts simultaneously.
that the relay is in proper working order. The
relay should pickup at 80% of rating and should
not pick up below values in Table I -Minimum CALIBRATION
Pickup.
Use the following procedure for calibrating
r` 1. Contact gaps the relay if the relay has been taken apart for
repairs or the adjustments disturbed. This pro-
Normally open contacts should have a gap of cedure should not t)e used until it is apparent that
.018 to .023 inch. the relay is not in proper working order. (See
"Acceptance Check.")
® 2. Contact pressure

On relays with four normally open contacts,


Trlpplng Relay (All)
contacts should have ap`proximately 5 grams The type AR tripping relay unit has been
pressure on the card in the de-energized properly adjusted at the factory to insure correct
position, and 15 to 30 grams contact pressure operation, and under normal field conditions
in the energized position. Pressure readings should not require readjustment. If, however, the
are taken at the end of the contact spring. adjustments are disturbed in error, or it becomes
necessary to replace some part, use the following
3. Armature gap adjustment procedure. This procedure should
not be used until it is apparent that the relay is
The armature gap should be approximately not in proper working order.
.010 inches measured at the narrowest part of
the armature gap. a. Adjust the set screw at the rear of the top of
the frame to obtain a 0.010-inch gap at the
4. Contact operate time rear end of the armature air gap.

4 milliseconds at.rated voltage. b. Adjust each contact sp.ring to obtain 5 gI.ams


reset. pressure at the very end of the spring.
5. Operation Indicator (0.I.) (When Sdpplied) This pressure should be sufficient to move the
spring away from the edge of the slot of the
Close the main relay contacts and pass suf- card.
ficient dc current through the circuit to drop
the target of the 0.I. This value of current
should be not greater than the particular 0.I. 3,a:,;un§tta::::pstoaft,;:325ytocooT;2;tj::rhee:.tfnoe:::;:
tap setting being used. The operation indicator the relay and the. normally open contacts
target should drop freely. should have 15 to 30 grams contact follow.

5
d. Apply rated voltage to the relay in line with
the terminal polarity designation. Then
calibrate by adjusting the spring tension until FIENEWAL PARTS
the relay picks up in the line with Table Ill-
Pickup Values. Repair work can tie done most satisfactorily
• TABLE Ill at the factory. However, interchangeable parts
® PICKUP VALUES can be furnished to the customers who are equip-
ped for doing repair work. When- ordering parts,
31 volts for 48 volt rating always give the complete nameplate data.
80 volts for 125 volt rating
160 volts for 250 volt rating

®`TABLE ]V -CONTACT FtATING

lnterruptlng Ratlng (Amp8) Carry Ratlng (Amp8)


ContactCII'CultVoltsdc
Fles]stlve lnductlvet Contlnuous

Slngle DOuble §lngle DOublo

48 3.750 20. I.750 20. 3

125 0.500 1.7 0.350 1.2 3

250 0.250 0.5® 0.150 0.250 3

tL/R = .005 for 1<1 amp


L/R = .040 for I >1 amp

Fig. 3. Intomal Schematic ol the Typci AFI Relay - High Thros- F(g. 4. Intemal sc;hem8Iio Of the Type AFI ROI8y - Hlgh Trlr8s-

hold - with 4 make contacts ln front connected molded hold`-wltrl 4 make contacts ln roar connected molded

CEIse. case.

6
I.I. 41-759.3A

EF'a

) Aa AJ, AR
BIG'
((FT 'tl'lRLEI,H^,0"OICA'llcCO,'A¢,O|

S,''CW|(F,HALO
I-I-
l¢S A,'CSrT
/in
/

MICS'1es I
Bl'H' Cl|Tiltlcn.`l,|blIO'¢A"|¢:VI#!"Hmc!0

"ATUIE ull,zooOHiis-I.vDclsooO"S-1!5YDC•oooohms-{iavDc|lcH'HA|0leoMIDIE'ES,S,' ¢„

r-i
I`I'I.I
I.I.I.iii TES

a,
6gi:,a-- POS. '0
'E"llu3500A88
FroIT vl"/ MEG.

Fig. 5. Internal schematic ol the Type AFI Relay - HIgh Thres- Fig. 6. Internal schematic ol the Type AR R8Iay - High Thres-
hold -with 4 make contacts ln FT-11 case. hold -with 4 make contacts and 2 ICS units in FT-11
Case.

Fig. 7. Intornal sc:homatic ol the Type AR Relay - High Thres- • Fig. 8. Intemal sch6matlo ot the Type AFI Relay - HIgh Thres-

hold -double.unit with 8 make contacts ln FT-22 case. hold - double unit with inako contacts and 2 0.I. units
in FT-22 case.

7
®

pig. 9. External schematic for the Type AR Flelay.

cLEAfi^rsE roLE FOR .i9O scREw

-3+ 4# i
L-,# T,k
I

\ . .

r- aD I

. .L__=19!TEPM'N.190TEfUAROWA
-irM'NALTEf"lNAL'
Ihl£%
`.'

a
+
I

53 53,
6a`_ 64
5
£ 6
OWARE i, -4;i Ji-iF
Fig.10. Outline and drllllng plan-tor the Type AR relay in the lront connected molded case.

8
I.L. 41-759.3A

5,i"
rc t617

i__ 5i
7`-iDLA
u.T` i\/\I +\ + /
I(/ )I(
\ +/
5i
:tt
L 1\
'5

)i\ )1\ fi±3


\i/ \i/ '
_i
E: T

Fig.11. Outline and drilling plan for the Type AR Relay ln the rear connected molded case.

illE

9
~-.±

PANEL CUTOUT a DF!lLLING


FOR SEMl-FLUSH MTG.

WHEN USED 2.328


!'!::FEE?Tt:ASN$8} ( 59.13)
CASE D|MENSIONS IN INCHE
DIMENsloNS IN M
LAF}GE INTEF`NAL
8 EXTEF3NAL _(68:!3i
TOOTH WASH ER\(41+.86733TERNALW'
t,'£.%%, DIA` 2 HOLESI
SMALL
TOOTHED 55)36± 11(g?§g)I,816(.397!)75
WASHERS
'25o `,36.(6.35)2'6?,3lrf!.g.,
'90-32
SPACER OR,FOR\NELSV)#5?),,5TERNAL '6q7jIT2'6?i5'7
(a.55) R.
SFIACERS
PANEL

5/16-'8 SCF3EW A klJ


(FOFi THICK F8?, ( t Ji I
lo(25.4)I
USE 5/16-18
I I 2 3 4 576 98
`NTEBNAL-EX
TOOTtlED WAS5HERS I '3 I'I
12 0)L
.190-32 SC REW (4PANELS6,05)
10 : ,50.
FOFi THICK
USE .190-3 2STUDS . \` ¢TERMINA

`(I
.516
11 .750 A
I__ 9.o5)D' . (13.11) NUMBER
0 HOLES OR I.03' I.0 I I.03' I.031
CUTOUT u26,19) '26. 9) (26,19) (26. 9)
TEF}MINAL AND
(16.28) PANEL Df3lLLING OF} CUTOUT FOR
MOUNTING DETAILS
pROuECTioN MTG.,(FroNT viEw)

5 7 -D+ 79 0 0

Fig.12. Outllna arld drilling plan for the Type AFI Flol8y ln the FT-11 case.

10
I.L 41.759.3A

(141, 30 )
('8,53°5i?,'€633!°kE,SscFR°ERws
I,594 6,063= `1 (2
(40.49`) F54oo,

i
t
¢ 5,2'9
(132.56 )
9.688
I
(246,08 )
A'
'L6.375 1Z=
'0. 438 4. 844
(265 13) ( 123.04 )

Iu
IIu`3

3, 88
(80.98 )
(161.93 ) PANEL LOCATION

=LLu°sCHAT±°TNG,
SEMI-FLUSH MTG. Jis i `3.I-8-) R::N±:5i:2FD(RS:L::.:N:CTloNMTC,FORSEMI-FLUSHMTG.
PBOJECTloN MTC, IIlii=

DIMENSIONS 'SHEi=>ig'ig5)!'~:--`8--'6---'4---I--`!:(5o2,'8°)
DIMENSIONS

LAFiGE INTE NAL I ,•ER,,5¥g,\lI.344


\` '9 17 15 13 1ly
a EXTEF{N
TOOTH WAS
A !;?4,I

2688
ALL (54,14 ) (68:28 ) ES
(I.E.653o )DIA` 2 HO
rERNAL 5.375
)THEO / (156.55 )
•. )5735)R7
(g?!8)I.816(.396?7git2'6?I?I)|,5

PANEL
:AsccERREswFOR tl5t34ii, r2:69,ii,ifi!'g,i;12
THIN PANELS
5/16-18 SCREW
tF:9^R.T.H,I,CLK,^p£¥E!§`tiir66i
USE 5/16-18 STUDS)

INTERNAL-EXTEF{NAL
TOOTHED WASHERS I.8|3

•190-52 SCREw (46.05 )


FOR THICK PANELS
USE: ,190-32 STUDS

TERMINAL
t_ _ _ _ _ (,§788'D,A. NUMBER
20 HOLES OR
CUTOUT
TERMINAL AND
(16.28) PANEL DFilLLING OR CUTOUT FOR
MOUNTING DETAILS
PROJECTION MTG.(FRONT VIEW)

183A158

® Fig.13. Outline and drilling plan torthe.Type AFI Relay ln the FT-22 Case.

iL

Dqtl

-'-
WESTINGHOUSE ELECTFtlc COFipoRATION
RELAY-lNSTRUMENT DIVISION CORALSPRINGS, FL.
Printed iri U.S.A.

You might also like