FIELD DEVICE JUNCTION BOX DCS CABINET (E-ROOM)

MAGNETIC FLOW TRANSMITTER


MAGNETIC FLOWMETER TUBE 3240-FIT-01901
.
E-ROOM: C2-3240-ER-015
.
3240-FE-01901 .
C2-3200-JB-007 C2-3300-CP-005
. PR#1 MB-1 TS/C08
PR#1 3240-FE-01901-J PR#1 3240-FIT-01901-J PR#1
19 19 2+ MB-1 1+
WT VENDOR SUPPLIED (#20AWG) WT OR 1PR #16AWG FF
C2-3200-JB-007-J PR#1 OR
PR#1 3240-PIT-01904-J
18 18 1- T+ 6- 1-
BK BK BL 5PR #16AWG FF OR BL 1PR #16AWG FF BL
17 17 TS 6S 1SH
. . .
3240-FE-01901-P 3240-FIT-01901-P
1 1 10 T- 6+ 2+
WT VENDOR SUPPLIED (#14AWG) WT BK 2C+GND #14AWG Power PR#1 BL OR
PR#1 3240-LIT-02316-J
2 2 9 1+ 7- 2-
BK BK WT OR BL 1PR #16AWG FF
GND GND GND 1S 7S 2SH
MT MT MT
MAGNETIC FLOW TRANSMITTER 1- 7+
PR#1 BL OR
3240-FIT-01903
.

OR
2+ 8-
.
2S 8S
.
PR#1 3240-FIT-01903-J 2- 8+
19 2+
1PR #16AWG FF PR#1 BL
OR 3+ 9-
18 1- OR
BL 3S 9S
17
. 3240-FIT-01903-P 3- 9+
1 10
2C+GND #14AWG Power PR#1 BL
BK 4+ 10 -
2 9 OR
WT 4S 10 S
GND GND
MT 4- 10 +
PR#1 BL
MAGNETIC FLOW TRANSMITTER 5+ 11 -
OR
MAGNETIC FLOWMETER TUBE
3240-FIT-01907
.
5S 11 S
.
3240-FE-01907 . 5- 11 +
. PR#1 BL
PR#1 3240-FE-01907-J PR#1 3240-FIT-01907-J T+ 12 -
19 19 2+
WT VENDOR SUPPLIED (#20AWG) WT OR 1PR #16AWG FF
BUS
18 18 1- TS 12 S
BK BK BL TERMINATOR
17 17 T- 12 +
. . 3240-FIT-01907-P
. 3240-FE-01907-P 1 10
1
WT VENDOR SUPPLIED (#14AWG) WT BK 2C+GND #14AWG Power
2 2 9
BK BK WT
GND GND GND
MT MT MT

I/P CONVERTER - FF
3240-FY-01901
.

.
PR#1 3240-FY-01901-J
+
OR 1PR #16AWG FF
-
BL
POWER SUPPLY - 120VAC UPS

ACOUSTIC LEVEL ELEMENT ACOUSTIC LEVEL TRANSMITTER


3240-LE-01902 3240-LIT-01902
.
C2-3200-DP-007
LE . . TS
LE
3240-LE-01902-J 1 3L
LE VENDOR SUPPLIED RD BK
2 3N 3240-FIT -01901
BK WT
3 3G
BL . MT
4 4L
WT BK
PR#1 3240-LIT-01902-J
5+ 4N 3240-FIT -01903
OR 1PR #16AWG FF WT
6- 4G
BL . MT
5L
BK
5N 3240-FIT -01907
WT
RADAR LEVEL TRANSMITTER
5G
3240-LIT-02316
.
MT
.
+
OR
PR#1
-
BL

PRESSURE IND TRANSMITTER


3240-PIT-01904
.

.
+
OR
PR#1
-
BL
NOTE:

1. FOR GENERAL NOTES AND LEGENDS, SEE DRAWING NO. 240K-C2-0000-70L-001.

DES. DESIGNED BY DRAWN BY


REV. DATE REVISION DESCRIPTION APPROVED
NOTICE: THIS DRAWING HAS NOT BEEN PUBLISHED AND IS
THE SOLE PROPERTY OF FLUOR AND IS LENT TO THE
CERRO VERDE PRODUCTION UNIT EXPANSION
CHK H. ZHUANG K. SOHAL
BORROWER FOR THEIR CONFIDENTIAL USE ONLY. AND IN

A
CONSIDERATION OF THE LOAN OF THIS DRAWING. THE
BORROWER PROMISES AND AGREES TO RETURN IT UPON
CHECKED BY CHECK DRAWING FOUNDATION FIELDBUS SEGMENT DRAWING
NOT USED G. REY
REQUEST AND AGREES THAT IT WILL NOT BE REPRODUCED, J. WONG SEGMENT NAME: C2-3200-JB-007-MB1
COPIED, LENT OR OTHERWISE DISPOSED OF DIRECTLY OR
INDIRECTLY. NOR USED FOR ANY PURPOSE OTHER THAN THAT LEAD ENGINEER APP. DATE
B NOT USED FOR WHICH IT IS FURNISHED.
K. BONNER 03SEP2014 EXPANSION DE UNIDAD DE PRODUCCION CERRO VERDE
C NOT USED
AREA MANAGER APP. DATE PLANO SEGMENTO DE LA FUNDACION DE CAMPO
N/A N/A
HZ KGB
NOMBRE DEL SEGMENTO: C2-3200-JB-007-MB1
0 03SEP2014 ISSUED FOR CONSTRUCTION ENGR MANAGER APP. DATE
GR N/A N/A N/A
R SCALE DRAWING NUMBER Sheet REV
CLIENT APP. DATE
N/A N/A NTS 240K-C2-3200-70L-201 1 of 1 0