You are on page 1of 1

Chemical Engineering Calculations

Pump Sizing Calculation


https://checalc.com/calc/pump.html

Project re Developed By ewr


Date 2019-10-24 Reviewed By rwe
Revision 0 Approved By rwe

Data
Flowrate liter/h 1500 Vapor Pressure barg 1.00
Density kg/m³ 1000 Pump Efficiency % 80.00
Viscosity cP 0.800

Hydraulic Data
Suction Discharge
Operating Pressure barg 1.00 5.00
Static Head m 0.500 5.00
Equipment Loss bar 0.100 2.00
Length m 5.00 2000
Pipe Selected 1", Thickness 0.375 1.5", Thickness 0.375
Pipe Inside Diameter inch 0.565 1.15
Velocity m/s 2.58 0.622
Reynold's Number 46209 22703
Pipe, ΔP bar/100 m 6.81 0.190
Pressure at Pump Suction / barg -0.0509 11.97
Discharge

Pipe Fitting Loss


Suction Discharge
Fittings # K ΔP # K ΔP
Elbows, 90LR 2 0.57 0.04 100 0.41 0.08
Elbows, 45LR 2 0.43 0.03 100 0.30 0.06
Tees, Thru 2 1.39 0.09 100 0.94 0.18
Tees, Branch 2 2.23 0.15 100 1.53 0.30
Ball Valve 2 0.43 0.03 10 0.30 0.01
Butterfly Valve 0 0.71 0.00 10 0.50 0.01
Gate Valve 0 0.28 0.00 1 0.20 0.00
Globe Valve 0 11.11 0.00 0 7.54 0.00
Check Valve 2 4.19 0.28 10 2.87 0.06
Plug Valve 2 0.71 0.05 0 0.51 0.00
Pipe Entrance / Exit 0 0.50 0.00 1 1.00 0.00
Total ΔP, bar 0.659 0.688

Result
Differential Pressure bar 12.02 Pump BKW kW 0.626
Differential Head m 122.7 NPSH Available m -10.73
Hydraulic Power kW 0.501

Downloaded on 10/24/2019, 8:55:32 AM from checalc.com Page 1 of 1