ESPECTRO DE SISMO SEGÚN NORMA E.

030 - 2018

Categoria Edificio B U 1.30


Zona Sísmica 4 Z 0.45
Tipo de Suelo S2 Tp (s) 0.60
Tl(s) 2.00
S 1.05
Coeficicente de red. Albañileria Armada o Confinada
R 3.0
Ip: Irregularidad en planta 0.85
Ia: Irregularidad en altura 0.85
R a usar = 2.17
ESPECTRO DE SISMO NORMA E.030 - 2018
factor a escalar 9.81 1.80

1.60

ZUCS/R * g
C T (s) C/R ZUCS/R * g
1.40
2.50 0.00 1.1534 6.9502
1.20
2.50 0.02 1.1534 6.9502
1.00
Sa
2.50 0.04 1.1534 6.9502
2.50 0.06 1.1534 6.9502 0.80

2.50 0.08 1.1534 6.9502 0.60

2.50 0.10 1.1534 6.9502 0.40

2.50 0.12 1.1534 6.9502 0.20


2.50 0.14 1.1534 6.9502
0.00
2.50 0.16 1.1534 6.9502 0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00

2.50 0.18 1.1534 6.9502 PERIODO T


2.50 0.20 1.1534 6.9502
2.50 0.25 1.1534 6.9502
2.50 0.30 1.1534 6.9502
2.50 0.35 1.1534 6.9502
2.50 0.40 1.1534 6.9502
2.50 0.45 1.1534 6.9502
2.50 0.50 1.1534 6.9502
2.50 0.55 1.1534 6.9502
2.50 0.60 1.1534 6.9502
2.31 0.65 1.0647 6.4155
2.14 0.70 0.9886 5.9573
2.00 0.75 0.9227 5.5601
1.88 0.80 0.8651 5.2126
1.76 0.85 0.8142 4.9060
1.67 0.90 0.7689 4.6334
1.58 0.95 0.7285 4.3896
1.50 1.00 0.6920 4.1701
1.36 1.10 0.6291 3.7910
1.25 1.20 0.5767 3.4751
1.15 1.30 0.5323 3.2078
1.07 1.40 0.4943 2.9786
1.00 1.50 0.4614 2.7801
0.94 1.60 0.4325 2.6063
0.88 1.70 0.4071 2.4530
0.83 1.80 0.3845 2.3167
0.79 1.90 0.3642 2.1948
0.75 2.00 0.3460 2.0850
0.62 2.20 0.2860 1.7232
0.52 2.40 0.2403 1.4480
0.44 2.60 0.2047 1.2338
0.38 2.80 0.1765 1.0638
0.33 3.00 0.1538 0.9267
0.19 4.00 0.0865 0.5213
0.12 5.00 0.0554 0.3336
0.08 6.00 0.0384 0.2317
0.06 7.00 0.0282 0.1702
0.05 8.00 0.0216 0.1303
0.04 9.00 0.0171 0.1030
0.03 10.00 0.0138 0.0834

CORTANTE BASAL
C T (s) C/R ZUCS/R
0.95 1.59 0.4361 0.2679

C/R ES MAYOR QUE LA CORTANTE BASAL DE TAL MOTIVO CUMPLE

Circular
Period Frequency
Case Mode Frequency Eigenvalue
sec cyc/sec rad/sec rad²/sec²
Modal 1 1.587 0.63 3.9581 15.6669
Modal 2 0.421 2.378 14.9407 223.2257
Modal 3 0.393 2.548 16.0066 256.2104
Modal 4 0.232 4.304 27.0424 731.294
Modal 5 0.225 4.444 27.9221 779.6439
Modal 6 0.12 8.301 52.1586 2720.5225
Modal 7 0.082 12.244 76.9286 5918.0025
Modal 8 0.071 14.183 89.1147 7941.4245
Modal 9 0.053 18.853 118.4588 14032.4959

Sismo Severo
0 5.02149375 Mass X Mass Y
Story Diaphragm
0.02 5.02149375 ton ton
0.04 5.02149375 AZOTEA AZOTEA 38.9049885 38.9049885
0.06 5.02149375 PISO 2 PISO 2 56.724363 56.724363
0.08 5.02149375 PISO 1 PISO 1 59.4857799 59.4857799
0.1 5.02149375 PESO TOTAL 155.115131 155.115131
0.12 5.02149375
0.14 5.02149375
0.16 5.02149375
0.18 5.02149375
0.2 5.02149375
0.25 5.02149375
0.3 5.02149375
0.35 5.02149375
0.4 5.02149375
0.45 5.02149375
0.5 5.02149375
0.55 5.02149375
0.6 5.02149375
0.65 4.635225
0.7 4.3041375
0.75 4.017195
0.8 3.76612031
0.85 3.54458382
0.9 3.3476625
0.95 3.17146974
1 3.01289625
1.1 2.73899659
1.2 2.51074688
1.3 2.3176125
1.4 2.15206875
1.5 2.0085975
1.6 1.88306016
1.7 1.77229191
1.8 1.67383125
1.9 1.58573487
2 1.50644813
2.2 1.24499845
2.4 1.04614453
2.6 0.89138942
2.8 0.76859598
3 0.6695325
4 0.37661203
5 0.2410317
6 0.16738313
7 0.12297536
8 0.09415301
9 0.0743925
10 0.06025793

FUERZA SISMICA

Peso estructura 155.12 ton

Z 0.45 U
S 1.05 C
Rx 3.00 Ry
Coef. XX 0.80 Coef. YY
C / Rx = 0.83 C / Ry =

V estatico XX 79.40 ton V estatico YY

V estatico max. XX 63.52 ton V estatico max. YY


18

MA E.030 - 2018

Sa

.00 6.00 7.00 8.00 9.00 10.00

DO T
1.30
2.50
3.00
0.80
0.83

79.40 ton

63.52 ton