Professional Documents
Culture Documents
TX1500 Series
Cus
Availab tom Scaling
Signa le! Specify
4 and 2 ls Correspond Input
0 in
U Isolated to 1500 Vrms EngineemA. Please Cog to
ring for nt
Details ®act
U 2-Wire 4 to 20 mA
Operation TX1502A-K shown actual size.
U 9 to 50V Compliance
U Turndown Ratio to 10:1
Isolation to 1500 Vrms
barriers and load resistance. For
example, at the full 20 mA output
N
U NMV Protection to 120 Vac (2100 Vp) of the transmitter, a 750 Ω load can
U -40 to 85°C (-40 to 185°F) This exceptionally high CMV rating be used with a 24 Vdc source and
Operation from the input to the case or output a 150 Ω load can be used with a
eliminates electrical ground loops 12 Vdc source. In either case, there
U Shock Resistance will still be enough voltage left to
between the signal source and the
to 55 g receiver. It also provides a high power the transmitter, namely 9 Vdc.
U NEMA 4X (IP66) Metal Case degree of protection for the receiver 10:1 Turndown Ratio
U Field Scalable against electrical hazards, such Turndown ratio is defined as zero
as accidental contact between the suppression divided by span. The
signal source and an AC power line. exceptionally high 10:1 turndown
Unmatched Electrical 9 to 50V Compliance ratio possible with the TX1500
The loop voltage driving the Series indicates that wide zero
Performance 2-Wire transmitters can be from 9 to 50V offset can be combined with narrow
Operation without loss of accuracy. The signal span for closed loop control
Power is obtained directly from the exceptionally low 9V limit allows at high gain. The signal span can
4 to 20 mA loop, with no need for the transmitters to be used with also be wide for control of batch
separate power input. This simplifies low loop supply voltages, and it operations, where a wide range of
field wiring and prevents noise maximizes the voltage drop allowed signal levels may be encountered
pickup from power lines. in the current loop for intrinsic safety over the entire batch cycle.
N-46
Electromagnetic interference (EMI)
Galvanic isolation
Signal source:
T/C, RTD, mA
mV, V
+ 4 to 20 mA current loop
Sensing
resistor V = IR
T/C -
- +
N-47
TX1501 shown smaller
than actual size.
Common Specifications
Signal Output
Connection: 2-wire Environmental
Linear Range: 4 to 20 mA
Operating Temperature: -40 to 85°C (‑40 to 185°F)
Storage Temperature: -55 to 125°C (‑67 to 257°F)
N
Maximum Output: 35 mA
Relative Humidity: 0 to 100% (sealed case)
Voltage Compliance: 9 to 50 Vdc
Watertight Proof Pressure: 35 kPa (5 psi)
Power Supply Rejection: 0.01% of span/V
Shock: 55 g, half sine, 9 to 13 ms duration
Input/Output Protection:
Vibration: 1.52 mm (0.06") double amplitude,
CMV, Input to Case or Output: 2100 Vp per HV test, 10 to 80 Hz cycled
354 Vp per IEC spacing
CMR, Input to Case or Output:120 dB, DC to 60 Hz
Mechanical
NMV Across Output Leads: 120 Vac for 1 min Case Material: Zamak zinc alloy
Reverse Polarity Across Output Leads: Gasket Material: Fluorosilicone
400 Vp
Diameter: 74 mm (2.9")
Accuracy: -40 to 85°C (-40 to 185°F)
Height, Including Barriers: 53 mm (2.1")
Hysteresis and Repeatability: ±0.1% of span
Weight: 380 g (13 oz)
6-month Stability Error: ±0.2% of zero
Electrical Connection: #6 screws with wire clamps
suppression
Terminal Protection:
Error Due to 50°C Change in
Transmitter Temperature: Standard: Screw terminal barriers plus barrier strip cover
Zero Error: ±0.2% of zero suppression CPB1 (Optional): Plastic cover for case top (protects T/C
Span Error: ±0.2% of span screw terminals from air currents)
N-48
Non-Common Specifications Thermocouple Input Milliamp Input
RTD Input Model TX1502A Model TX1505
Model TX1501 Span and Zero Suppression: Span for 4 to 20 mA Output:
Signal Source: Pt100 RTD See input table 5 to 100 mA
Span for 4 to 20 mA Output: Input Resistance (Open T/C Detector Zero Suppression: -30 to 60 mA
100 to 1050°C (180 to 1890°F) Resistance): 5 MΩ Input Resistance: 1 Ω
Zero Suppression: Bias Current, Max: 50 nA Step Response, Type: 400 ms
-200 to 750°C (‑328 to 1382°F) NMV Across Input Leads: Volt Input
Source Connection: 2- or 3-wire 120 Vac for 1 min Model TX1506
Excitation Current: 200 µA NMR Across Input Leads: Span for 4 to 20 mA Output:
40 dB, 50/60 Hz, 100 mV input 0.5 to 5 V (TX506-1); 5 to 50V
Lead Resistance, Max: 100 Ω
Thermocouple Lead Resistance: (TX506-2)
Bandwidth: DC-60 Hz Zero Suppression:
For specified performance: 100 Ω
Ohms Input Maximum: 10 kΩ -3.5 to 6.0 V (TX506‑1); -35 to 60V
Step Response, Type: 400 ms (TX506-2)
Model TX1501
Input Resistance: 1 MΩ
Signal Source: 0 to 400 Ω Millivolt Input Bias Current, Max: 1 nA
Span for 4 to 20 mA Output: Model TX1504 NMV Across Input Leads:
35 to 400 Ω Span for 4 to 20 mA Output: 120 Vac for 1 min
Zero Suppression: 0 to 365 Ω 5 to 100 mV NMR Across Input Leads:
Zero Suppression: -30 to 60 mV 40 dB, 50/60 Hz, 100 mV input
Source Connection: 2- or 3-wire
Input Resistance: 100 MΩ Step Response, Type: 400 ms
Excitation Current: 200 µA Bias Current, Max: 50 nA
Lead Resistance, Max: 100 Ω NMV Across Input Leads:
Bandwidth: DC-60 Hz 120 Vac for 1 min
NMR Across Input Leads: 40 dB,
50/60 Hz, 100 mV input
Step Response, Type: 400 ms
Dimensions: mm (inch)
+ 74.4 (2.93) 51.8 (2.04)
+S + 74.4 (2.93) is designed for 3-wire
The TX1501 transmitter 51.8 (2.04)
RTD -S
4 to 20 mA RTD operation,TEST which
PWR CASEcompensates for lead
- resistance. The TEST +S
GND
PWR terminal
CASE is not connected
-EXC GND
internally. Shorting the -S and -EXC terminals
Z
providesZ 2-wire operation 63.5 (2.50)
63.5 (2.50)
Monitor 61.0
61.0 (2.4)
(2.4)
. 4 to 20 mA 4 to 20 mA
N-49
Relay output Control
alarm
Galvanic isolation
++ 4 to 20 mA
Signal Sensing
source resistor V = IR
-
TX83A or TX82B DP25 or DP41 - +
loop-powered AC- or DC-powered
process indicator process indicator
with relay option
Isolated 2-wire Loop power provided
transmitter by control room
Control room
Galvanic isolation
Sensing
resistor + EXC
10 to 24 Vdc
excitation
- EXC supply
++
Signal AC
source
- Main board
4 to 20 mA current loop SIG LO
with sensing
resistor
SIG HI
Isolated 2-wire
transmitter
Model DP24 digital
panel meter with electrically
floating excitation supply
Powering the 4 to 20 mA Loop and Transmitter with a Low-Cost meter
A DP24, DP25 or DP41 panel meter
A model may be
DP24, usedortoDP41
DP25 powerpanel
the 4 meter
to 20 mA
mayloop, including
be used the isolated 2-wire transmitter.
to power
One or more loads may be theadded to the
4 to 20
loads
mAloop,
may
loop,including
be
includingreceiving
added to
equipment
the isolated 2-wireintransmitter.
the control room.
One ofThe excitation supply is electronically floating;
thus, the current loop may be grounded anywhere. In addition to powering the loop, the panel meter provides a local display scaled in percent
more the loop, including receiving equipment
N
or in engineering units.
in the control room. The excitation supply is electronically floating, so
that the current loop may be grouded anywhere. In addition to powering
the loop, the panel meter provides a local display scaled in percent
or in engineering units.
TX1502A-J shown
smaller than actual size.
N-50
Mounting Methods
See N-49 for mounting drawings.
N-51
Powering the 4 to 20 mA loop and the transmitter with a DP41 panel meter/controller.
Analog Relay
output output
Control room
Galvanic isolation
Analog Control
Sensing output output
resistor board board
++ +EXC
Signal Main board with
source signal conditioner AC
- and excitation supply
4 to 20 mA loop SIG HI
N-52