COMPUTATION OF LOADS

CKT. NO. OF CIRCUIT SIZES


DESCRIPTION LOCATION VA VOLT AMP
NO. OUTLET BREAKER WIRE CONDUIT
8 x 20V 1
1 LIGHTING OUTLET LANAI 280 230 1.22 15 AT 2 - 2.00 mm.TW WIRE 2 Ø CONDUIT PIPE
3 X 40V
2 X 20V 1
2 LIGHTING OUTLET WALK-IN-CLOSET 280 230 1.22 15 AT 2 - 2.00 mm.TW WIRE 2 Ø CONDUIT PIPE
6 X 40V
5 X 20V 1
3 LIGHTING OUTLET LIVING AREA 220 230 0.96 15 AT 2 - 2.00 mm.TW WIRE 2 Ø CONDUIT PIPE
3 X 40V

2 - 2.00 mm.TW WIRE 1


4 LIGHTING OUTLET FOYER 8 X 40V 320 230 1.39 15 AT 2 Ø CONDUIT PIPE

5 X 20V 1
5 LIGHTING OUTLET HALLWAY 260 230 1.13 15 AT 2 - 2.00 mm.TW WIRE Ø CONDUIT PIPE
4 X 40V 2

6 2 - 3.50 mm.TW WIRE 1


CONVENIENCE OUTLET MASTER BEDROOM 12 2160 230 9.39 20 AT 2 Ø CONDUIT PIPE

2 - 3.50 mm.TW WIRE 1


7 CONVENIENCE OUTLET BEDROOM 12 2160 230 9.39 20 AT 2 Ø CONDUIT PIPE

8 RANGE KITCHEN 1 2000 230 8.70 30 AT 2 - 5.50 mm.TW WIRE 1


2 Ø CONDUIT PIPE

9 1 2000 8.70 30 AT 2 - 5.50 mm.TW WIRE 1


REFRIGERATOR KITCHEN 230 2 Ø CONDUIT PIPE

10 2 - 5.50 mm.TW WIRE 1


SPARE 230 30 AT 2 Ø CONDUIT PIPE

2 - 5.50 mm.TW WIRE 1


11 SPARE 230 30 AT 2 Ø CONDUIT PIPE

12 70 9680 42.1

LOAD COMPUTATION: PROTECTION: 100 AMP @ 230 VOLTS, SINGLE PHASE 2 WIRE 60HZ SYSTEM