1 PB1
2 -General Light 40 W 2 -Pendant Light 28 W 20
2
4 -Wall Light 28 W 3 -1.2m T5 28 W 4
4 -General Light 40 W 1 -1.2m T5 28 W 18
3
3 -Wall Light 28 W - -0.9m T5 21 W 3
4 5 - Convenience Outlet 180 VA & 3 -Weatherproof Convenience Outlet
6 1 -Range (3300W)
FEEDER SIZE
It= [ 88.02 + (25% X 8.00 ] X 85%
It= 76.51 Amperes
Use: 2- 22 mm2 THHN WIRE and
1- 8 mm2 TW Wire
in 30 mm Diameter RSC PIPE
0.704
0.78 0.6467
CIRCUIT BREAKER RATING
VOLTS V.A.
AMPS AT AF POLE
N/A N/A N/A N/A N/A N/A
-Pin Light 9W
230 596 2.59 15 50 2
-0.9m T5 21 W
-Pin Light 9W
230 488 2.12 15 50 2
-Spot Light 18 W
ce Outlet 180 VA 230 1,440 6.26 20 50 2
BREAKER SIZE
I t=
Use:
Check Design Analysis:
Therefore, Use:
31.8
2.12
TYPE WIRES CONDUIT (MM)
PLUG-IN 2 - 5.5 mm2 THHN & 1-3.5 mm2 15 MM. DIA. PVC
PLUG-IN 2 - 5.5 mm2 THHN & 1-3.5 mm2 15 MM. DIA. PVC
PLUG-IN 2 - 5.5 mm2 THHN & 1-3.5 mm2 15 MM. DIA. PVC
PLUG-IN 2 - 5.5 mm2 THHN & 1-3.5 mm2 15 MM. DIA. PVC
PLUG-IN 2 - 5.5 mm2 THHN & 1-3.5 mm2 15 MM. DIA. PVC
PLUG-IN 2 - 5.5 mm2 THHN & 1-3.5 mm2 15 MM. DIA. PVC
PLUG-IN 2 - 5.5 mm2 THHN & 1-3.5 mm2 15 MM. DIA. PVC
BREAKER SIZE
76.51 Amperes
100 AT, 2P, 230 VAC & 60 Hz.
100 AT, 2P, 230 VAC & 60 Hz.
100 AT, 2P, 230 VAC & 60 Hz.
DESIGN ANALYSIS
Total Area: 105.30 square meters
A. General Lighting:
105.30 square meters X 24.00 Volt Amperes per square meter = 2,527.20 VA
C. Heating Loads
1.00 unit(s) Range 3,300.00 VA = 3,300.00 VA
2.00 unit(s) Water Heater 1,600.00 VA = 3,200.00 VA
- unit(s) Water Heater 3,300.00 VA = - VA
D. Other Loads (Motor Loads Derived From PEC Table 4.30.14.2 Page 623) :
- unit(s) 1/2 HP Motor or Aircon Load 1,127.00 VA = - VA
- unit(s) 3/4 HP Motor or Aircon Load 1,587.00 VA = - VA
4.00 unit(s) 1.0 HP Motor or Aircon Load 1,840.00 VA = 7,360.00 VA
- unit(s) 1.5 HP Motor or Aircon Load 2,300.00 VA = - VA
- unit(s) 2.0 HP Motor or Aircon Load 2,760.00 VA = - VA
- unit(s) 3.0 HP Motor or Aircon Load 3,910.00 VA = - VA
- unit(s) 2 Tons / 2.5HP Motor or Aircon Load 3,335.00 VA = - VA
- unit(s) 3 Tons / 3.75HP Motor or Aircon Load 5,175.00 VA = - VA
- unit(s) 5 Tons / 6.25HP Motor or Aircon Load 7,820.00 VA = - VA
- unit(s) Spare 3,400.00 VA = - VA
Sub Total of Other Loads = 7,360.00 VA
Circuit Requirements
Use: Minimum of 2.00 - 15 Ampere 2 Pole Branch Circuit for Lighting Loads
Use: Minimum of 2.00 - 20 Ampere 2 Pole Branch Circuit for Convenience Outlet Loads
Use: Minimum of 7.00 - 30 Ampere 2 Pole Branch Circuit for Other Loads
KVA BASE
puZs =
SC Utility Fault KVA Utility SC Capacity 1000 MVA
100
puZs =
1000000
puZs = 0.0001 pu 50.00 KVA with
1.50% Z Impedance
Compute for per unit % Impedance (puZt)
Z
= √ R + (XL - XC)
2 2
Z
= √ 1.39 2 + ( 0.60
-
0.13 )2
Conversion
puZw = = Z (of Copper Wire) X L (Length of Conductor to Fault)
1.46 Ohms 1 Mile
puZw = = X X 25.00 Feet
Mile 5280 Feet
puZw = = 0.0069 pu
Simplified Diagram
puZ Total = puZs + puZt + puZw
puZs = 0.0001
Fault
1 Base VA 1 50,000.00 VA
Isc (sym) = X = X
puZ Total 230 V 0.0220 230 Volts
Isc (sym) = 9,868.14 Amperes RMS
Isc (sym) 9,868.14
KAIC = X 125% SF = X 125% SF
1000 1000
KAIC = 12.34 KAIC
Therefore:
Use: Minimum of 13.00 KAIC for Main Circuit Breaker but Check Line to Line Fault and Line to Neutral Fault (Below)
Minimum of 10.00 KAIC for Branch Circuit Breaker but Check Line to Line Fault and Line to Neutral Fault (Below)
SHORT CIRCUIT ANALYSIS
Checking Line to Line Fault and Line to Neutral Fault
Line to Line Fault @230 V - Fault X1
Assuming: Single Line Diagram
50.00 KVA Transformer* (Maximum Supply for Residential is only at 50KVA) Line to Line Fault @ 230V - Fault X1
*Please note that a smaller transformer than this will result to a Infinite Bus
lower KAIC rating making this assumption conservative.
Z = Impedance Z of Transformer at Worst Case = 1.50%
L = Length in feet of Conductor to Fault
L= 25.00 ft* Higher length will be less conservative. 50.00 KVA with
C = Conductor Factor and Values given in the Table of IEEE Std. 241-1990 (Gray Book) 1.50% Z Impedance
C= 3,806.00 for 22 mm2 Wire
n = Number of Parallel Conductors
Vu = Line to Line Voltage 22 mm2 THHN at
50.00 KVA Transformer X 1000 25.00 feet to fault
If.l. =
230 V 100 AT
IS.C. motor contribution = 6.00 (Accepted is from 4 - 6) X Total Amperes of Motor Load (From Previous Design Calculation)
6.00 (Accepted is from 4 - 6) X 7,360.00 VA
IS.C. motor contribution =
230 V
IS.C. motor contribution = 6.00 (Accepted is from 4 - 6) X 32.00 Amperes
IS.C. motor contribution = 192 Amperes
IS.C. TOTAL (X1) = IS.C. L-L (X1) RMS + IS.C. motor contribution
IS.C. TOTAL (X1) = 10,250.20 Amperes + 192.00 Amperes
IS.C. TOTAL (X1) = 10,442.20 Amperes
IS.C. motor contribution = 6.00 (Accepted is from 4 - 6) X Total Amperes of Motor Load (From Previous Design Calculation)
6.00 (Accepted is from 4 - 6) X 7,360.00 VA
IS.C. motor contribution =
120 V
IS.C. motor contribution = 6.00 (Accepted is from 4 - 6) X 61.33 Amperes
IS.C. motor contribution = 368 Amperes
IS.C. TOTAL (X1) = IS.C. L-N (X1) RMS + IS.C. motor contribution
IS.C. TOTAL (X1) = 9,926.73 Amperes + 368.00 Amperes
IS.C. TOTAL (X1) = 10,294.73 Amperes
IS.C. TOTAL (X1) = 10,294.73 Amperes
KAIC =
1000 1000
KAIC = 10.29 KAIC
Therefore:
Use: Minimum of 13.00 KAIC for Main Circuit Breaker
Minimum of 10.00 KAIC for Branch Circuit Breaker
VOLTAGE DROP CALCULATION
From Previous Calculation:
ITotal Full Load Current = 76.51 Amperes
Size of Wire = 22 mm2 THHN
Z per mile = 1.46 Ohms / Mile
Length of Feeder Line Wire* = 30.00 meters
Length of of Feeder Line Wire in feet* = 28.00 feet
*Shorter wire will result to a lower Voltage Drop therefore assumption is conservative.
Solve for Z Ohms per foot:
1.46 Ohms 1 Mile
Z = X
Mile 5280 Feet
Z = 0.000193182 Ohms per foot
Solve for Voltage Drop VD:
VD = 2 X L (in feet) X Z (Ohms / foot) X ITotal Full Load Current
VD = 2 X 28.00 ft X 0.000193182 Ohms / foot X 76.51 Amperes
VD = 0.83 Volts
VD 0.83 V
% VD = X 100% = X 100%
230V 230 V
% VD = 0.36% is Less than the Standard Maximum Allowable of 3% to 5%
Ground Wire
FAIL 8
FAIL 8
PASS 8
PASS 14
PASS 22
PASS 30
PASS 38
PASS 50
PASS 60
PASS 80
PASS 100
PASS 125
PASS 150
PASS 200
PASS 250
PASS 325
FAIL 7,820.00 VA = - VA
FAIL 5,175.00 VA = - VA
FAIL 3,335.00 VA = - VA
FAIL 3,910.00
FAIL 2,760.00
FAIL 2,300.00
PASS 1,840.00
FAIL 1,587.00
FAIL 1,127.00
0.571429 0.630491
0.636364 0.633197
0.733333 0.63754
0.789474 0.79797
0.76 0.79771
0.833333 0.799043
0.75 0.800399
0.8 0.802993
0.8 0.86646
0.833333 0.842294
0.75
0.8
0.769231
0.8125
0.8
6.25
76.38 Wire Size Pipe Diameter TW Ampere Capacity
2 15
3.5 20
5.5 30
FAIL 8 20 40
FAIL 14 25 55
PASS 22 30 70
PASS 30 30 90
PASS 38 35 100
PASS 50 40 120
PASS 60 40 135
PASS 80 40 160
PASS 100 45 185
PASS 125 45 210
PASS 150 45 240
PASS 200 50 280
PASS 250 50 315
PASS 325 55 370
PASS 400 60 405
PASS 500 60 485
Ground Wire
FAIL 8
FAIL 8
PASS 8
PASS 14
PASS 22
PASS 30
PASS 38
PASS 50
PASS 60
PASS 80
PASS 100
PASS 125
PASS 150
PASS 200
PASS 250
PASS 325
file://reneianmayo/Fast%20Share/ELECTRICAL%20ANALYSIS/Short_Circuit_Current_Calculations.pdf
750 24137
THHN Ampere Capacity
25
30
40
50 3.87 0.672 0.1422
70 2.44 0.648 0.1379 0.630491 0.964286 0.969761
90 1.545 0.62 0.131 0.633197 0.95679 0.949964
115 0.985 0.575 0.1292 0.63754 0.927419 0.98626
130 0.786 0.561 0.1258 0.79797 0.975652 0.973684
150 0.627 0.547 0.1224 0.79771 0.975045 0.972973
170 0.501 0.533 0.1189 0.799043 0.974406 0.971405
205 0.401 0.519 0.1155 0.800399 0.973734 0.971405
225 0.322 0.505 0.112 0.802993 0.973025 0.969697
265 0.279 0.484 0.1064 0.86646 0.958416 0.95
295 0.235 0.473 0.1037 0.842294 0.977273 0.974624
355 0 0 0
400
470
515
580
FAIL 7,820.00 VA = - VA
FAIL 5,175.00 VA = - VA
FAIL 3,335.00 VA = - VA
FAIL 3,910.00
FAIL 2,760.00
FAIL 2,300.00
PASS 1,840.00
FAIL 1,587.00
FAIL 1,127.00
rt_Circuit_Current_Calculations.pdf
Interpolated from
750 24137
0.571429 0.630491
0.636364 0.633197
0.733333 0.63754
0.789474 0.79797
0.76 0.79771
0.833333 0.799043
0.75 0.800399
0.8 0.802993
0.8 0.86646
0.833333 0.842294
0.75
0.8
0.769231
0.8125
0.8
6.25
Modified Values by Engr. Ian to match Engr. Woody Factors applied From:
mm 2
AWG R XL XC R XL XC R
8 8 3.476738 0.649239 0.146433 0.898382 0.966129 1.029771 3.87
14 6 2.192052 0.626052 0.142005 0.898382 0.966129 1.029771 2.44
22 4 1.388 0.599 0.1349 0.898382 0.966129 1.029771 1.545
30 2 0.921795 0.56475 0.131945 0.935832 0.982173 1.021245 0.985
38 1 0.765 0.56 0.1274 0.973282 0.998217 1.012719 0.786
50 1/0 0.610248 0.546025 0.123957 0.973282 0.998217 1.012719 0.627
60 2/0 0.487615 0.53205 0.120412 0.973282 0.998217 1.012719 0.501
80 3/0 0.390286 0.518075 0.116969 0.973282 0.998217 1.012719 0.401
100 4/0 0.313397 0.5041 0.113424 0.973282 0.998217 1.012719 0.322
125 250 MCM 0.271546 0.483137 0.107753 0.973282 0.998217 1.012719 0.279
150 300 MCM 0.228721 0.472157 0.105019 0.973282 0.998217 1.012719 0.235
200 400 MCM 0.192651 0.489644 0.101843 0.973282 0.998217 1.012719 0.197939
250500MCM / 240sqmm 0.163753 0.507779 0.098764 0.973282 0.998217 1.012719 0.168248
325 700MCM 0.140828 0.526586 0.095777 0.973282 0.998217 1.012719 0.144693
400 800MCM 0.125337 0.546089 0.092881 0.973282 0.998217 1.012719 0.128777
500 1000 MCM 0.112803 0.566314 0.090072 0.973282 0.998217 1.012719 0.115899
http://copperweld.com/sites/copperweld.com/files/wselecccs-ed1790.pdf
XL XC
0.672 0.1422
0.648 0.1379 0.630491 0.964286 0.969761
0.62 0.131 From Engr. Woody 0.633197 0.95679 0.949964
0.575 0.1292 0.63754 0.927419 0.98626
0.561 0.1258 From Engr. Woody 0.79797 0.975652 0.973684
0.547 0.1224 0.79771 0.975045 0.972973
0.533 0.1189 0.799043 0.974406 0.971405
0.519 0.1155 0.800399 0.973734 0.971405
0.505 0.112 0.802993 0.973025 0.969697
0.484 0.1064 0.86646 0.958416 0.95
0.473 0.1037 0.842294 0.977273 0.974624
0.490519 0.100564 No Data
0.508686 0.097523 Hula nalang
0.527526 0.094574 by Proportion
0.547064 0.091714
0.567326 0.088941
VD = < 3.00%
0.36%