LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP

PROJECT: DAVAO CITY BY PASS CONSTRUCTION PROJECT/ PA


PANEL NAME: MAIN DISTRIBUTION PANEL (MDP)
LOCATI0N: ENGINEER'S OFFICE AND LIVING QUARTERS

FEEDER PANEL DESCRIPTION

1 LPP-A (LIGHTING AND POWER PANEL GROUND FLOOR)


2 LPP-B (LIGHTING AND POWER PANEL SECOND FLOOR)
3 POWER PANEL FPP
4 POWER PANEL PP-A
5 POWER PANEL ACCU
6 PP-WACU
7 SPARE
8 SPARE
9 SPARE
10 SPARE

TOTAL
TOTAL PANEL LOAD
DEMAND FACTOR
TOTAL DEMAND LOAD
TOTAL CURRENT LOAD

COMPUTATION:

FULL LOAD CURRENT:
= 62.16 kVA
1.732 X 230 V
FLC = 156.04 A

Page 1 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
CB RATING: = 156.04 X 1.25

USE: 225 AT
225 AF
CABLE SIZE AMPACITY:
SEE ARTICLE 3.10 . CONDUCTORS FOR GENERAL WIRING TA
156.04 ≤ 193.6 WITH CORRE
USE: 1 SET/S 3

VOLTAGE DROP CALCULATION:


VD = 30.6 X 156.04 X
1000 X 100 X
VD = 3.82 Volts

%V = 3.82
230
%V = 1.66 IF ≤ = 2 %
USE: 1
3 SET/S
FOR SERVICE WIRE:
USE: 1 SET/S 3
FOR GROUND WIRE:
SEE ARTICLE 2.50 . MINIMUM SIZE OF EQUIPMENT GROUND
USE: 1- mm²
FOR CONDUIT SIZING:
SEE APPENDIX C, TABLE C.4 PEC 1, 2017 PAGE 985
USE: 65 mmø IMC

For Reference:

VOLTAGE DROP CALCULATION:


1Ø, VD CALCULATION: 3Ø, 3W VD CALCULATION
35.6 x L x I 30.8 x L x I
eV = eV =
1000 x S 1000 x S

% VD =

Page 2 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
e (V) = Voltage Drop, (volts)
% VD = Voltage Drop, (%)
L = Single Length of Conductor, (meters)
I = Current, (amperes)
S = Single Conductor Cross Section multipl
V = System Voltage, (volts)

Page 3 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
TAGE DROP

N PROJECT/ PACKAGE I-2


VOLTAGE SYSTEM :
ARTERS WIRE :
ENCLOSURE :

System RATING
V
Ø Voltage kW
A kVA
(V) kW
UND FLOOR) ### 1 230 5.58
ND FLOOR) ### 1 230 7.280 7.28
### 1 230 15.64 15.64
### 1 230 5.52 5.52
### 3 230 24.36 24.36
### 1 230 19.32 19.32
### 1 230
### 1 230
### 1 230
### 1 230

77.70
NEL LOAD 77.70
ACTOR 80.00
MAND LOAD 62.16
RRENT LOAD 156.04

Page 4 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
= 195.05 A

PHASE:
### 3
MCCB

AL WIRING TABLE 3.10.2.6 PEC 1, 2017 PAGE 174


WITH CORRECTION FACTOR (0.88) @ 40°C
100 mm²

80 LM
1 SET/S

100 mm²

100 mm² (FIRE PROOF) THW

MENT GROUND TABLE 2.50.6.13, PEC 1, 2017 PAGE 124


TW

PAGE 985

ULATION:
CALCULATION: 3Ø, 4W VD CALCULATION:
30.8 x L x I 17.8 x L x I
1000 x S 1000 x S

eV / V x 1000

Page 5 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
ductor, (meters)

ss Section multiplied by the number of sets, (mm²)

Page 6 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
230 V, 3-Phase
3W + G
NEMA 1 with Ground Terminal

LOAD DISTRIBUTION, KVA CIRC


% Full Loa
AB BC CA AN
CN kVA Pole
Multiplier Current
5.58 5.58 1.25 2 24.26
10.05 7.28 1.25 2 31.65
15.64 15.64 1 2 72
5.52 5.52 1 2 25.5
24.36 24.36 24.36 24.36 1 3 61.15
19.32 19.32 1 2 85.05

35.46 34.41 40.00 ### 77.70


kVA Phase 3
% System Voltage (V) 230
kVA Transformer (kVA) 100
A

Page 7 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 8 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 9 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
CIRCUIT BREAKER SIZE GROUND WIRE
Full Load
MCCB Rating AT AF mm² Type
Current
24.26 30.33 60 100 5.5 TW
31.65 39.57 60 100 5.5 TW
72 72 150 225 14.0 TW
25.5 25.5 40 60 5.5 TW
61.15 64.60 100 100 8.0 TW
85.05 85.05 100 100 8.0 TW
50
50
50
50

MAIN P
MAIN

Page 10 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 11 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 12 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
D WIRE CONDUIT
Full Load
PF DF K L
Type mmØ Type Current
TW 40 IMC 1 1 35.6 60 24.26
TW 40 IMC 1 1 35.6 60 31.65
TW 40 IMC 1 1 35.6 70 72.25
TW 40 IMC 1 1 35.6 70 25.50
TW 50 IMC 1 1 30.8 60 61.15
TW 65 IMC 1 1 35.6 70 85.05

MAIN PROTECTION: 225 AT 225


MAIN FEEDER SIZE: 1 sets - 2 x 100 mm²
mm²

Page 13 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 14 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 15 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
CABLE AMPACITY
SERVICE WIRE PERMITTE
ull Load System
CV %
Current Sets Number mm² Type Voltage
Allowable
24.26 1000 1 2 22 TW 230 2%
31.65 1000 1 2 22 TW 230 2%
72.25 1000 1 2 38 THW 230 2%
25.50 1000 1 2 14 TW 230 2%
61.15 1000 1 3 30 THW 230 2%
85.05 1000 1 2 50 THW 230 2%

AF MCCB
THW (FIRE PROOF)
TW in 0.0

Page 16 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 17 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
Page 18 file:///conversion/tmp/activity_task_scratch/538495175.xlsx
PERMITTED VD VOLTAGE DROP
Voltage REMARKS
e(V) %V
Drop
4.6 2.36 1.02% OK
4.6 3.07 1.34% OK
4.6 4.74 2.06% NOT OK
4.6 4.54 1.97% OK
4.6 3.77 1.64% OK
4.6 4.24 1.84% OK