1 15 AT - 2P GROUND FLOOR LIGHTING OUTLET 850 17 230 3.70 3 - 2.0MM THHN IN 15MM
2 15 AT - 2P GROUND FLOOR LIGHTING OUTLET 750 15 230 3.26 3 - 2.0MM THHN IN 15MM
MERALCO KILOWATT
PANEL BOX DETAILS
3 20 AT - 2P GROUND CONVENIENCE OUTLET 1620 9 230 7.04 2 - 3.5MM THHN IN 15MM METER
4 15 AT - 2P SECOND FLOOR LIGHTING OUTLET 1050 21 230 4.57 3 - 2.0MM THHN IN 15MM M
5 15 AT - 2P SECOND FLOOR LIGHTING OUTLET 1000 20 230 4.35 3 - 2.0MM THHN IN 15MM
6 30 AT - 2P SECOND CONVENIENCE OUTLET 2160 12 230 9.39 2 - 3.5MM THHN IN 15MM PANEL BOX
(GARAGE) 15A 15A
7 30 AT - 2P RANGE OUTLET 3000 1 230 13.04 2 - 5.5MM THHN IN 15MM
11 20 AT - 2P AIRCONDITION UNIT 1127 1 230 4.90 2 - 5.5MM THHN IN 15MM 20A 15A
1
12 20 AT - 2P AIRCONDITION UNIT 1127 1 230 4.90 2 - 5.5MM THHN IN 15MM
ENTRANCE CAP DIAGRAM 3 4
E1 E3 SCALE PROPORTION
15A 30A
2. SMALL APPLIANCE LOAD 3.0 SERVICE POWER SHALL BE 230 VOLTS, SINGLE PHASE, 2 WIRES WITH GROUND, 60Hz RATING. 20A 20A
21 OUTLETS X 180VA/SQ.M = 3780 V.A. 4.0 ALL MATERIALS TO BE USED SHALL BE NEW AND OF THE APPROVED TYPE FOR THE LOCATION 11 12
AND PURPOSE.
3. OTHERS
5.0 ALL WORKS IN THE SERVICE ENTRANCE SHALL BE DONE IN EITHER RIGID METAL OR
A.C. OUTLETS X 3 = 3381 V.A.
APPROVED P.V.C. CONDUIT W/ PROPER SUPPORT FITTINGS.
RANGE OUTLET = 3000 V.A.
6.0 ALL WORKS IN THE SERVICE SHALL BE EXECUTED UNDER THE DIRECT SUPERVISION OF A
12709.63 V.A. / 230V = 55.26 AMPERES LICENSED ELECTRICAL ENGINEER. THE CONTRACTOR SHALL COORDINATE AND CONSTANTLY
UPDATE ITS RELATED WORKS WITH OTHER TRADE CONTRACTOR.
TOTAL BASE LOAD : 55.26A X 0.8 D.F. = 44.208 AMPERES
PLUS 25% HIGHEST MOTOR LOAD = 1.23 AMPERES 7.0 ALL FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED IN THE PLANS.
INDIVIDUAL BRANCH CIRCUIT HOMERUNS SHALL NOT BE COMBINED IN THE SAME RACEWAY
TOTAL LOAD COMPUTATION = 45.43 AMPERES UNLESS EXPLICITLY SHOWN IN THE PLANS.