TOTAL
TOTAL PANEL LOAD
DEMAND FACTOR
TOTAL DEMAND LOAD
TOTAL CURRENT LOAD
COMPUTATION:
Page 1 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
CB RATING: = 24.24 X 1.25
USE: 40 AT
60 AF
CABLE SIZE AMPACITY:
SEE ARTICLE 3.10 . CONDUCTORS FOR GENERAL WIRING TA
24.24 ≤ 45.1 WITH CORRE
USE: 1 SET/S -2
%V = 3.70
230
%V = 1.61 IF ≤ = 2 %
USE: 1 2 SET/S
FOR SERVICE WIRE:
USE: 1 SET/S 2
FOR GROUND WIRE:
SEE ARTICLE 2.50 . MINIMUM SIZE OF EQUIPMENT GROUND
USE: 1- 5.5 mm²
FOR CONDUIT SIZING:
SEE APPENDIX C, TABLE C.4 PEC 1, 2017 PAGE 985
USE: 40 mmø IMC
For Reference:
% VD =
Page 2 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
e (V) = Voltage Drop, (volts)
% VD = Voltage Drop, (%)
L = Single Length of Conductor, (meters)
I = Current, (amperes)
S = Single Conductor Cross Section multipl
V = System Voltage, (volts)
Page 3 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
OLTAGE DROP
6.97 0.00
NEL LOAD 6.97 kVA
ACTOR 80 %
MAND LOAD 5.58 kVA
RRENT LOAD 24.24 A
Page 4 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
= 30.30 A
PHASE: 1 WIRE: 2
MCB
60 LM
1 SET/S
14.0 mm² TW
PAGE 985
ALCULATION:
ALCULATION: 3Ø, 4W VD CALCULATION:
30.8 x L x I 17.8 x L x I
eV =
1000 x S 1000 x S
eV / V x 1000
Page 5 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
uctor, (meters)
Page 6 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Phase
### 6.97
Phase 1 NOTE:
em Voltage
VOLTAGE(V) 230 Apply 125% for Lighting (Continuous Load)
sformer (kVA) Apply 125% for Power & Motor Loads
Page 7 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 8 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 9 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
SIZE GROUND WIRE CONDUIT
AT AF mm² Type mmØ Type
15 50 2.0 TW 20 IMC
15 50 2.0 TW 20 IMC
15 50 2.0 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50 3.5 TW 20 IMC
20 50
MAIN PROTECTION:
MAIN FEEDER SIZE:
Page 10 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 11 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 12 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
CABLE AMPACITY
DUIT SE
Full Load
PF DF K L CV
Type Current Sets
IMC 1 1 35.6 100 5.01 1000 1
IMC 1 1 35.6 100 4.38 1000 1
IMC 1 1 35.6 100 1.88 1000 1
IMC 1 1 35.6 100 1.96 1000 1
IMC 1 1 35.6 100 1.30 1000 1
IMC 1 1 35.6 100 5.48 1000 1
IMC 1 1 35.6 100 4.70 1000 1
IMC 1 1 35.6 100 4.35 1000 1
IMC 1 1 35.6 100 1.25 1000 1
40 AT 60 AF MCB
1 sets - 2 x 14.0 mm² TW
5.5 mm² TW in 0.0
Page 13 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 14 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 15 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
ACITY
SERVICE WIRE PERMITTED VD VOLTAGE
System
Voltage % Voltage
Number mm² Type e(V)
Allowable Drop
2 3.5 TW 230 3% 6.9 5.09
2 3.5 TW 230 3% 6.9 4.46
2 3.5 TW 230 3% 6.9 1.91
2 3.5 TW 230 3% 6.9 1.99
2 3.5 TW 230 3% 6.9 1.33
2 3.5 TW 230 3% 6.9 5.57
2 3.5 TW 230 3% 6.9 4.78
2 3.5 TW 230 3% 6.9 4.42
2 3.5 TW 230 3% 6.9 1.27
NOTE:
VOLTAGE DROP PERMISSIBLE PERCENTAGE
3% FOR BRANCH VOLTAGE (PEC 1, 2017 PAGE 42, ARTICLE 2.10.2.2 (A) FPN NO.4
2% FOR FEEDER VOLTAGE (PEC 1, 2017 PAGE 51, ARTICLE 2.15.1.2 (A) FPN NO.2
Page 16 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 17 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 18 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
VOLTAGE DROP
REMARKS
%V
2.22% OK
1.94% OK
0.83% OK
0.87% OK
0.58% OK
2.42% OK
2.08% OK
1.92% OK
0.55% OK
ERMISSIBLE PERCENTAGE
017 PAGE 42, ARTICLE 2.10.2.2 (A) FPN NO.4
017 PAGE 51, ARTICLE 2.15.1.2 (A) FPN NO.2
Page 19 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 20 file:///conversion/tmp/activity_task_scratch/538399965.xlsx
Page 21 file:///conversion/tmp/activity_task_scratch/538399965.xlsx