TRANSFORMER 1

POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)


1 1 0 0 3 1 19.033
2 0 0 2 2 1 10.16
3 0 2 2 0 1 31.946
4 0 0 2 2 1 10.16
5 0 0 1 3 1 7.736
TOTAL 1 2 7 10 5 79.035

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 7 25.914
D 10 12.78
SL 5 1
TOTAL 79.035

KVA = 1.3*kVAtotal
= 102.7455

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 3

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
4 10.16 1 10.16
5 7.736 2 15.472

TOTAL 17.896 25.632

WEST SIDE
POLE NO. Kva span kVAspan
1 19.033 2 38.066
2 10.16 1 10.16

TOTAL 29.193 48.226

USE WEST SIDE OF THE TRANSFORMER OF 29.193 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
121.6375 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 214.75628 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
87074.722

FROM THE TABLE 5, USE 133,077 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.414
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 309
CAPACITIVE REACTANCE (OHM/MILE) = 0.12
RESISTANCE (OHM/MILE) = 0.481
INDUCTIVE REACTANCE (OHM/MILE) = 0.532
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.7110921 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.482
RATIO = Xe/Ra
= 1.002079

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.37 OF 1.002079 AND 90% pf
VDe = X(VDA)
= 6.4541961

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.6892484 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 2
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
6 1 1 1 1 1 32.35
7 1 0 2 1 1 23.881
8 0 2 3 0 1 35.648
9 0 0 3 2 1 13.862
10 0 0 2 3 1 11.438
TOTAL 2 3 11 7 5 117.179

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 11 40.722
D 7 8.946
SL 5 1
TOTAL 117.179

KVA = 1.3*kVAtotal
= 152.3327

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 8

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
9 13.862 1 13.862
10 11.438 2 22.876

TOTAL 25.3 36.738

WEST SIDE
POLE NO. Kva span kVAspan
6 32.35 2 64.7
7 23.881 1 23.881

TOTAL 56.231 88.581

USE WEST SIDE OF THE TRANSFORMER OF 56.231 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
234.29583 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 204.78971 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
159937.92

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.83851 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 7.1780137

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.990839 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 3
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
11 0 1 2 1 1 21.053
12 0 0 3 2 1 13.862
13 1 0 0 4 1 20.311
14 0 1 2 2 1 22.331
15 0 2 2 0 1 31.946
TOTAL 1 4 9 9 5 109.503

LOAD UNIT KVA


A 1 14.999
B 4 48.684
C 9 33.318
D 9 11.502
SL 5 1
TOTAL 109.503

KVA = 1.3*kVAtotal
= 142.3539

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 13

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
14 22.331 1 22.331
15 31.946 2 63.892

TOTAL 54.277 86.223

WEST SIDE
POLE NO. Kva span kVAspan
11 21.053 2 42.106
12 13.862 1 13.862

TOTAL 34.915 55.968

USE EAST SIDE OF THE TRANSFORMER OF 54.277 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
226.15417 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 206.51455 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
155680.42

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.73633 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.9869371

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.9112238 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 4
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
16 1 0 0 3 1 19.033
17 0 0 3 2 1 13.862
18 0 2 2 2 1 34.502
19 1 0 2 2 1 25.159
20 0 1 1 1 1 17.351
TOTAL 2 3 8 10 5 109.907

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 8 29.616
D 10 12.78
SL 5 1
TOTAL 109.907

KVA = 1.3*kVAtotal
= 142.8791

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 18

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
17 13.862 1 13.862
18 34.502 2 69.004

TOTAL 48.364 82.866

SOUTH SIDE
POLE NO. Kva span kVAspan
19 25.159 2 50.318
20 17.351 1 17.351

TOTAL 42.51 67.669

USE NORTH SIDE OF THE TRANSFORMER OF 48.364 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
201.51667 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 222.73964 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
149619.17

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.59086 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.7149082

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.7978784 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 5
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
21 0 0 0 4 1 5.312
22 1 0 2 2 1 25.159
23 0 0 2 5 1 13.994
24 1 1 1 1 1 32.35
25 0 1 1 2 1 18.629
TOTAL 2 2 6 14 5 95.444

LOAD UNIT KVA


A 2 29.998
B 2 24.342
C 6 22.212
D 14 17.892
SL 5 1
TOTAL 95.444

KVA = 1.3*kVAtotal
= 124.0772

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 23

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
24 32.35 1 32.35
25 18.629 2 37.258

TOTAL 50.979 69.608

EAST SIDE
POLE NO. Kva span kVAspan
21 5.312 2 10.624
22 25.159 1 25.159

TOTAL 30.471 35.783

USE WEST SIDE OF THE TRANSFORMER OF 50.979 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
212.4125 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 177.50525 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
125681.11

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.0163467 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 5.6405683

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.3502368 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 6
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
26 0 1 1 3 1 19.907
27 1 0 0 4 1 20.311
28 0 1 1 3 1 19.907
29 0 1 0 4 1 17.483
30 0 0 2 2 1 10.16
TOTAL 1 3 4 16 5 87.768

LOAD UNIT KVA


A 1 14.999
B 3 36.513
C 4 14.808
D 16 20.448
SL 5 1
TOTAL 87.768

KVA = 1.3*kVAtotal
= 114.0984

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 28

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
29 17.483 1 17.483
30 10.16 2 20.32

TOTAL 27.643 37.803

EAST SIDE
POLE NO. Kva span kVAspan
26 19.907 2 39.814
27 20.311 1 20.311

TOTAL 40.218 60.125

USE EAST SIDE OF THE TRANSFORMER OF 40.218 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
167.575 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 194.34706 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
108559.03

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 2.6054167 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 4.8721292

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.0300538 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 7
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
31 0 1 2 3 1 23.609
32 1 0 1 4 1 24.013
33 0 1 2 4 1 24.887
34 0 1 2 1 1 21.053
35 1 1 1 1 1 32.35
TOTAL 2 4 8 13 5 125.912

LOAD UNIT KVA


A 2 29.998
B 4 48.684
C 8 29.616
D 13 16.614
SL 5 1
TOTAL 125.912

KVA = 1.3*kVAtotal
= 163.6856

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 33

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
34 21.053 1 21.053
35 32.35 2 64.7

TOTAL 53.403 85.753

EAST SIDE
POLE NO. Kva span kVAspan
31 23.609 2 47.218
32 24.013 1 24.013

TOTAL 47.622 71.231

USE WEST SIDE OF THE TRANSFORMER OF 53.403 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
222.5125 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 208.75026 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
154831.81

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.7159633 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.9488514

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.8953548 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 8
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
36 1 1 1 1 1 32.35
37 0 0 2 2 1 10.16
38 0 1 1 1 1 17.351
39 0 1 2 1 1 21.053
40 1 1 1 1 1 32.35
TOTAL 2 4 7 6 5 113.264

LOAD UNIT KVA


A 2 29.998
B 4 48.684
C 7 25.914
D 6 7.668
SL 5 1
TOTAL 113.264

KVA = 1.3*kVAtotal
= 147.2432

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 38

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
39 21.053 1 21.053
40 32.35 2 64.7

TOTAL 53.403 85.753

WEST SIDE
POLE NO. Kva span kVAspan
36 32.35 2 64.7
37 10.16 1 10.16

TOTAL 42.51 74.86

USE EAST SIDE OF THE TRANSFORMER OF 53.403 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
222.5125 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 208.75026 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
154831.81

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.7159633 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.9488514

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.8953548 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 9
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
41 1 0 3 1 1 27.583
42 1 1 0 2 1 29.926
43 0 0 2 2 1 10.16
44 0 2 2 0 1 31.946
45 0 0 0 4 1 5.312
TOTAL 2 3 7 9 5 104.927

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 7 25.914
D 9 11.502
SL 5 1
TOTAL 104.927

KVA = 1.3*kVAtotal
= 136.4051

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 43

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
44 31.946 1 31.946
45 5.312 2 10.624

TOTAL 37.258 42.57

WEST SIDE
POLE NO. Kva span kVAspan
41 27.583 2 55.166
42 29.926 1 29.926

TOTAL 57.509 85.092

USE WEST SIDE OF THE TRANSFORMER OF 57.509 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
239.62083 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 192.35181 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
153638.33

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.68732 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.8952884

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.8730368 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 10
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
46 1 1 2 0 1 34.774
47 0 0 1 3 1 7.736
48 0 1 0 6 1 20.039
49 0 0 2 3 1 11.438
50 1 0 2 2 1 25.159
TOTAL 2 2 7 14 5 99.146

LOAD UNIT KVA


A 2 29.998
B 2 24.342
C 7 25.914
D 14 17.892
SL 5 1
TOTAL 99.146

KVA = 1.3*kVAtotal
= 128.8898

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 48

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
49 11.438 1 11.438
50 25.159 2 50.318

TOTAL 36.597 61.756

EAST SIDE
POLE NO. Kva span kVAspan
46 34.774 2 69.548
47 7.736 1 7.736

TOTAL 42.51 77.284

USE EAST SIDE OF THE TRANSFORMER OF 42.51 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
177.125 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 236.34251 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
139540.56

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.3489733 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.2625801

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.6094084 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 11
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
51 1 0 0 2 1 17.755
52 0 1 2 2 1 22.331
53 0 1 2 1 1 21.053
54 0 0 2 3 1 11.438
55 0 1 0 3 1 16.205
TOTAL 1 3 6 11 5 88.782

LOAD UNIT KVA


A 1 14.999
B 3 36.513
C 6 22.212
D 11 14.058
SL 5 1
TOTAL 88.782

KVA = 1.3*kVAtotal
= 115.4166

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 53

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
54 11.438 1 11.438
55 16.205 2 32.41

TOTAL 27.643 43.848

WEST SIDE
POLE NO. Kva span kVAspan
51 17.755 2 35.51
52 22.331 1 22.331

TOTAL 40.086 57.841

USE WEST SIDE OF THE TRANSFORMER OF 40.086 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
167.025 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 187.57995 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
104435.14

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.4809661 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.5422105

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.7259211 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 12
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
56 0 0 2 3 1 11.438
57 1 0 1 2 1 21.457
58 0 1 2 2 1 22.331
59 0 1 2 1 1 21.053
60 0 1 0 2 1 14.927
TOTAL 1 3 7 10 5 91.206

LOAD UNIT KVA


A 1 14.999
B 3 36.513
C 7 25.914
D 10 12.78
SL 5 1
TOTAL 91.206

KVA = 1.3*kVAtotal
= 118.5678

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 58

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
59 21.053 1 21.053
60 14.927 2 29.854

TOTAL 35.98 50.907

EAST SIDE
POLE NO. Kva span kVAspan
56 11.438 2 22.876
57 21.457 1 21.457

TOTAL 32.895 44.333

USE WEST SIDE OF THE TRANSFORMER OF 35.98 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
149.91667 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 183.93302 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
91915.417

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.9437863 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.757928

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.3991367 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 13
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
61 0 1 1 8 1 26.297
62 0 0 0 0 1 0.2
63 0 0 1 2 1 6.458
64 0 1 3 2 1 26.033
65 0 0 3 4 1 16.418
TOTAL 0 2 8 16 5 75.406

LOAD UNIT KVA


A 0 0
B 2 24.342
C 8 29.616
D 16 20.448
SL 5 1
TOTAL 75.406

KVA = 1.3*kVAtotal
= 98.0278

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 63

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
64 26.033 1 26.033
65 16.418 2 32.836

TOTAL 42.451 58.869

WEST SIDE
POLE NO. Kva span kVAspan
61 26.297 2 52.594
62 0.2 1 0.2

TOTAL 26.497 52.794

USE WEST SIDE OF THE TRANSFORMER OF 42.451 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
176.87917 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 180.27773 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
106291.25

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.5606057 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.6584843

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.7743685 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 14
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
66 0 0 2 3 1 11.438
67 1 0 0 3 1 19.033
68 0 0 2 2 1 10.16
69 0 1 0 3 1 16.205
70 0 0 3 3 1 15.14
TOTAL 1 1 7 14 5 71.976

LOAD UNIT KVA


A 1 14.999
B 1 12.171
C 7 25.914
D 14 17.892
SL 5 1
TOTAL 71.976

KVA = 1.3*kVAtotal
= 93.5688

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 68

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
69 16.205 1 16.205
70 15.14 2 30.28

TOTAL 31.345 46.485

EAST SIDE
POLE NO. Kva span kVAspan
66 11.438 2 22.876
67 19.033 1 19.033

TOTAL 30.471 41.909

USE WEST SIDE OF THE TRANSFORMER OF 31.345 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
130.60417 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 192.79151 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
83931.25

FROM THE TABLE 5, USE 133,077 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.414
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 309
CAPACITIVE REACTANCE (OHM/MILE) = 0.12
RESISTANCE (OHM/MILE) = 0.481
INDUCTIVE REACTANCE (OHM/MILE) = 0.532
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.5410176 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.482
RATIO = Xe/Ra
= 1.002079

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.37 OF 1.002079 AND 90% pf
VDe = X(VDA)
= 6.2211941

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5921642 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 15
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
71 1 1 2 1 1 36.052
72 0 1 2 3 1 23.609
73 0 0 0 4 1 5.312
74 0 1 2 0 1 19.775
75 0 1 3 2 1 26.033
TOTAL 1 4 9 10 5 110.781

LOAD UNIT KVA


A 1 14.999
B 4 48.684
C 9 33.318
D 10 12.78
SL 5 1
TOTAL 110.781

KVA = 1.3*kVAtotal
= 144.0153

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 73

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
74 19.775 1 19.775
75 26.033 2 52.066

TOTAL 45.808 71.841

SOUTH SIDE
POLE NO. Kva span kVAspan
71 36.052 2 72.104
72 23.609 1 23.609

TOTAL 59.661 95.713

USE SOUTH SIDE OF THE TRANSFORMER OF 59.661 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
248.5875 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 208.55651 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
172815.14

FROM THE TABLE 5, USE 400,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.725
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 607
CAPACITIVE REACTANCE (OHM/MILE) = 0.104
RESISTANCE (OHM/MILE) = 0.162
INDUCTIVE REACTANCE (OHM/MILE) = 0.458
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.1106725 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.408
RATIO = Xe/Ra
= 2.5185185

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 2.14 OF 2.5185185 AND 90% pf
VDe = X(VDA)
= 6.6568392

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.773683 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 16
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
76 0 1 1 3 1 19.907
77 1 0 2 1 1 23.881
78 0 0 0 4 1 5.312
79 0 1 1 4 1 21.185
80 1 0 2 3 1 26.437
TOTAL 2 2 6 15 5 96.722

LOAD UNIT KVA


A 2 29.998
B 2 24.342
C 6 22.212
D 15 19.17
SL 5 1
TOTAL 96.722

KVA = 1.3*kVAtotal
= 125.7386

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 78

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
79 21.185 1 21.185
80 26.437 2 52.874

TOTAL 47.622 74.059

SOUTH SIDE
POLE NO. Kva span kVAspan
76 19.907 2 39.814
77 23.881 1 23.881

TOTAL 43.788 63.695

USE NORTH SIDE OF THE TRANSFORMER OF 47.622 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
198.425 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 202.16854 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
133717.64

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.2092233 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.0012476

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5005198 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 17
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
81 0 0 0 3 1 4.034
82 1 1 0 2 1 29.926
83 1 0 2 2 1 25.159
84 0 0 2 3 1 11.438
85 0 2 2 0 1 31.946
TOTAL 2 3 6 10 5 102.503

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 6 22.212
D 10 12.78
SL 5 1
TOTAL 102.503

KVA = 1.3*kVAtotal
= 133.2539

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 83

COMPUTATION OF TOTAL CONNECTED LOAD


SOUTH SIDE
POLE NO. Kva span kVAspan
84 11.438 1 11.438
85 31.946 2 63.892

TOTAL 43.384 75.33

NORTH SIDE
POLE NO. Kva span kVAspan
81 4.034 2 8.068
82 29.926 1 29.926

TOTAL 33.96 37.994

USE SOUTH SIDE OF THE TRANSFORMER OF 43.384 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
180.76667 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 225.72607 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
136012.5

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.2643 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.104241

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5434338 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 18
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
86 1 0 0 2 1 17.755
87 0 0 2 2 1 10.16
88 0 3 2 0 1 44.117
89 0 0 2 4 1 12.716
90 1 0 0 4 1 20.311
TOTAL 2 3 6 12 5 105.059

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 6 22.212
D 12 15.336
SL 5 1
TOTAL 105.059

KVA = 1.3*kVAtotal
= 136.5767

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 88

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
89 12.716 1 12.716
90 20.311 2 40.622

TOTAL 33.027 53.338

WEST SIDE
POLE NO. Kva span kVAspan
86 17.755 2 35.51
87 10.16 1 10.16

TOTAL 27.915 45.67

USE EAST SIDE OF THE TRANSFORMER OF 33.027 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
137.6125 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 209.94762 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
96304.722

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.1321168 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.0328906

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5137044 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 19
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
91 0 1 2 2 1 22.331
92 1 0 2 2 1 25.159
93 0 1 1 4 1 21.185
94 1 1 1 1 1 32.35
95 0 0 1 2 1 6.458
TOTAL 2 3 7 11 5 107.483

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 7 25.914
D 11 14.058
SL 5 1
TOTAL 107.483

KVA = 1.3*kVAtotal
= 139.7279

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 93

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
94 32.35 1 32.35
95 6.458 2 12.916

TOTAL 38.808 45.266

EAST SIDE
POLE NO. Kva span kVAspan
91 22.331 2 44.662
92 25.159 1 25.159

TOTAL 47.49 69.821

USE EAST SIDE OF THE TRANSFORMER OF 47.49 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
197.875 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 191.12929 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
126065.69

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.0255767 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 5.6578284

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.3574285 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 20
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
96 1 1 0 3 1 31.204
97 0 0 2 2 1 10.16
98 0 1 2 1 1 21.053
99 0 1 1 0 1 16.073
100 0 1 2 0 1 19.775
TOTAL 1 4 7 6 5 98.265

LOAD UNIT KVA


A 1 14.999
B 4 48.684
C 7 25.914
D 6 7.668
SL 5 1
TOTAL 98.265

KVA = 1.3*kVAtotal
= 127.7445

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 98

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
99 16.073 1 16.073
100 19.775 2 39.55

TOTAL 35.848 55.623

WEST SIDE
POLE NO. Kva span kVAspan
96 31.204 2 62.408
97 10.16 1 10.16

TOTAL 41.364 72.568

USE WEST SIDE OF THE TRANSFORMER OF 41.364 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
172.35 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 228.06885 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
131025.56

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.1446133 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 5.8804269

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4501779 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 21
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
101 0 1 0 3 1 16.205
102 1 0 2 1 1 23.881
103 1 0 1 4 1 24.013
104 0 2 2 0 1 31.946
105 0 0 2 2 1 10.16
TOTAL 2 3 7 10 5 106.205

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 7 25.914
D 10 12.78
SL 5 1
TOTAL 106.205

KVA = 1.3*kVAtotal
= 138.0665

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 103

COMPUTATION OF TOTAL CONNECTED LOAD


SOUTH SIDE
POLE NO. Kva span kVAspan
104 31.946 1 31.946
105 10.16 2 20.32

TOTAL 42.106 52.266

NORTH SIDE
POLE NO. Kva span kVAspan
101 16.205 2 32.41
102 23.881 1 23.881

TOTAL 40.086 56.291

USE SOUTH SIDE OF THE TRANSFORMER OF 42.106 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
175.44167 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 161.36845 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
94369.167

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.0490686 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.9116401

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4631834 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 22
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
106 0 0 1 3 1 7.736
107 1 0 2 2 1 25.159
108 0 2 1 3 1 32.078
109 1 0 2 2 1 25.159
110 0 1 3 1 1 24.755
TOTAL 2 3 9 11 5 114.887

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 9 33.318
D 11 14.058
SL 5 1
TOTAL 114.887

KVA = 1.3*kVAtotal
= 149.3531

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 108

COMPUTATION OF TOTAL CONNECTED LOAD


SOUTH SIDE
POLE NO. Kva span kVAspan
109 25.159 1 25.159
110 24.755 2 49.51

TOTAL 49.914 74.669

NORTH SIDE
POLE NO. Kva span kVAspan
106 7.736 2 15.472
107 25.159 1 25.159

TOTAL 32.895 40.631

USE SOUTH SIDE OF THE TRANSFORMER OF 49.914 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
207.975 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 194.4739 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
134819.03

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.2356567 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.050678

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5211158 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 23
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
111 0 1 1 5 1 22.463
112 0 0 3 2 1 13.862
113 0 1 0 5 1 18.761
114 0 0 2 3 1 11.438
115 1 0 1 4 1 24.013
TOTAL 1 2 7 19 5 90.537

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 7 25.914
D 19 24.282
SL 5 1
TOTAL 90.537

KVA = 1.3*kVAtotal
= 117.6981

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 113

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
114 11.438 1 11.438
115 24.013 2 48.026

TOTAL 35.451 59.464

EAST SIDE
POLE NO. Kva span kVAspan
111 22.463 2 44.926
112 13.862 1 13.862

TOTAL 36.325 58.788

USE EAST SIDE OF THE TRANSFORMER OF 36.325 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
151.35417 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 210.39064 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
106145

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.5543306 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.6493227

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.7705511 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 24
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
116 0 1 2 1 1 21.053
117 0 2 2 0 1 31.946
118 0 0 0 0 1 0.2
119 0 0 0 0 1 0.2
120 0 1 2 0 1 19.775
TOTAL 0 4 6 1 5 73.174

LOAD UNIT KVA


A 0 0
B 4 48.684
C 6 22.212
D 1 1.278
SL 5 1
TOTAL 73.174

KVA = 1.3*kVAtotal
= 95.1262

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 118

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
119 0.2 1 0.2
120 19.775 2 39.55

TOTAL 19.975 39.75

WEST SIDE
POLE NO. Kva span kVAspan
116 21.053 2 42.106
117 31.946 1 31.946

TOTAL 52.999 74.052

USE WEST SIDE OF THE TRANSFORMER OF 52.999 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
220.82917 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 181.64041 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
133705

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.20892 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.0006804

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5002835 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 25
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
121 0 0 2 3 1 11.438
122 0 1 1 4 1 21.185
123 1 0 1 2 1 21.457
124 0 0 2 1 1 8.882
125 0 0 2 2 1 10.16
TOTAL 1 1 8 12 5 73.122

LOAD UNIT KVA


A 1 14.999
B 1 12.171
C 8 29.616
D 12 15.336
SL 5 1
TOTAL 73.122

KVA = 1.3*kVAtotal
= 95.0586

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 123

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
124 8.882 1 8.882
125 10.16 2 20.32

TOTAL 19.042 29.202

EAST SIDE
POLE NO. Kva span kVAspan
121 11.438 2 22.876
122 21.185 1 21.185

TOTAL 32.623 44.061

USE EAST SIDE OF THE TRANSFORMER OF 30.623 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
127.59583 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 175.5795 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
74677.375

FROM THE TABLE 5, USE 133,077 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.414
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 309
CAPACITIVE REACTANCE (OHM/MILE) = 0.12
RESISTANCE (OHM/MILE) = 0.481
INDUCTIVE REACTANCE (OHM/MILE) = 0.532
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.0403458 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.482
RATIO = Xe/Ra
= 1.002079

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.37 OF 1.002079 AND 90% pf
VDe = X(VDA)
= 5.5352738

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.3063641 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 26
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
126 0 1 1 1 1 17.351
127 0 0 0 0 1 0.2
128 0 0 0 0 1 0.2
129 0 1 1 0 1 16.073
130 1 0 1 2 1 21.457
TOTAL 1 2 3 3 5 55.281

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 3 11.106
D 3 3.834
SL 5 1
TOTAL 55.281

KVA = 1.3*kVAtotal
= 71.8653

Select 75 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 128

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
129 16.073 1 16.073
130 21.457 2 42.914

TOTAL 37.53 58.987

EAST SIDE
POLE NO. Kva span kVAspan
126 17.351 2 34.702
127 0.2 1 0.2

TOTAL 17.551 34.902

USE WEST SIDE OF THE TRANSFORMER OF 37.53 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
156.375 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 204.32481 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
106504.31

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.5697472 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.6718309

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.7799296 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 27
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
131 0 0 1 2 1 6.458
132 1 0 2 2 1 25.159
133 0 2 1 0 1 28.244
134 0 0 1 2 1 6.458
135 1 0 2 2 1 25.159
TOTAL 2 2 7 8 5 91.478

LOAD UNIT KVA


A 2 29.998
B 2 24.342
C 7 25.914
D 8 10.224
SL 5 1
TOTAL 91.478

KVA = 1.3*kVAtotal
= 118.9214

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 133

COMPUTATION OF TOTAL CONNECTED LOAD


WEST SIDE
POLE NO. Kva span kVAspan
134 6.458 1 6.458
135 25.159 2 50.318

TOTAL 31.617 56.776

EAST SIDE
POLE NO. Kva span kVAspan
131 6.458 2 12.916
132 25.159 1 25.159

TOTAL 31.617 38.075

USE WEST SIDE OF THE TRANSFORMER OF 31.617 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
131.7375 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 233.44656 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
102512.22

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.3984601 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.4217518

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.6757299 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 28
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
136 1 0 1 2 1 21.457
137 0 0 1 4 1 9.014
138 0 0 2 3 1 11.438
139 0 1 1 2 1 18.629
140 0 1 1 2 1 18.629
TOTAL 1 2 6 13 5 79.167

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 6 22.212
D 13 16.614
SL 5 1
TOTAL 79.167

KVA = 1.3*kVAtotal
= 102.9171

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 138

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
139 18.629 1 18.629
140 18.629 2 37.258

TOTAL 37.258 55.887

WEST SIDE
POLE NO. Kva span kVAspan
136 21.457 2 42.914
137 9.014 1 9.014

TOTAL 30.471 51.928

USE EAST SIDE OF THE TRANSFORMER OF 37.258 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
155.24167 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 195 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
100907.08

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.3295889 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.3211998

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.6338333 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 29
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
141 1 1 1 1 1 32.35
142 0 0 2 4 1 12.716
143 1 1 0 3 1 31.204
144 0 0 0 4 1 5.312
145 0 1 2 0 1 19.775
TOTAL 2 3 5 12 5 101.357

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 5 18.51
D 12 15.336
SL 5 1
TOTAL 101.357

KVA = 1.3*kVAtotal
= 131.7641

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 143

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
144 5.312 1 5.312
145 19.775 2 39.55

TOTAL 25.087 44.862

WEST SIDE
POLE NO. Kva span kVAspan
141 32.35 2 64.7
142 12.716 1 12.716

TOTAL 45.066 77.416

USE WEST SIDE OF THE TRANSFORMER OF 45.066 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
187.775 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 223.31869 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
139778.89

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.3546933 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.2732765

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.6138652 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 30
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
146 0 0 1 3 1 7.736
147 0 1 3 4 1 28.589
148 1 0 1 2 1 21.457
149 0 1 2 3 1 23.609
150 0 0 0 3 1 4.034
TOTAL 1 2 7 15 5 85.425

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 7 25.914
D 15 19.17
SL 5 1
TOTAL 85.425

KVA = 1.3*kVAtotal
= 111.0525

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 148

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
149 23.609 1 23.609
150 4.034 2 8.068

TOTAL 27.643 31.677

SOUTH SIDE
POLE NO. Kva span kVAspan
146 7.736 2 15.472
147 28.589 1 28.589

TOTAL 36.325 44.061

USE SOUTH SIDE OF THE TRANSFORMER OF 36.325 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
151.35417 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 157.68562 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
79554.583

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.4134238 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 4.9835988

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.0764995 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
151 0 0 2 1 1 8.882
152 0 1 2 5 1 26.165
153 1 0 3 2 1 28.861
154 0 1 1 1 1 17.351
155 0 0 0 0 1 0.2
TOTAL 1 2 8 9 5 81.459

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 8 29.616
D 9 11.502
SL 5 1
TOTAL 81.459

KVA = 1.3*kVAtotal
= 105.8967

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 153

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
154 17.351 1 17.351
155 0.2 2 0.4

TOTAL 17.551 17.751

SOUTH SIDE
POLE NO. Kva span kVAspan
151 8.882 2 17.764
152 26.165 1 26.165

TOTAL 35.047 43.929

USE SOUTH SIDE OF THE TRANSFORMER OF 35.047 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
146.02917 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 162.94604 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
79316.25

FROM THE TABLE 5, USE 133,077 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.414
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 309
CAPACITIVE REACTANCE (OHM/MILE) = 0.12
RESISTANCE (OHM/MILE) = 0.481
INDUCTIVE REACTANCE (OHM/MILE) = 0.532
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.2913276 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.482
RATIO = Xe/Ra
= 1.002079

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.37 OF 1.002079 AND 90% pf
VDe = X(VDA)
= 5.8791188

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4496328 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 29
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
156 0 1 1 3 1 19.907
157 0 0 1 3 1 7.736
158 0 2 3 2 1 38.204
159 1 0 0 2 1 17.755
160 0 0 3 3 1 15.14
TOTAL 1 3 8 13 5 98.742

LOAD UNIT KVA


A 1 14.999
B 3 36.513
C 8 29.616
D 13 16.614
SL 5 1
TOTAL 98.742

KVA = 1.3*kVAtotal
= 128.3646

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 158

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
159 17.755 1 17.755
160 15.14 2 30.28

TOTAL 32.895 48.035

WEST SIDE
POLE NO. Kva span kVAspan
156 19.907 2 39.814
157 7.736 1 7.736

TOTAL 27.643 47.55

USE EAST SIDE OF THE TRANSFORMER OF 32.895 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
137.0625 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 189.8328 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
86729.861

FROM THE TABLE 5, USE 133,077 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.414
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 309
CAPACITIVE REACTANCE (OHM/MILE) = 0.12
RESISTANCE (OHM/MILE) = 0.481
INDUCTIVE REACTANCE (OHM/MILE) = 0.532
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.6924337 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.482
RATIO = Xe/Ra
= 1.002079

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.37 OF 1.002079 AND 90% pf
VDe = X(VDA)
= 6.4286342

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.6785976 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 29
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
161 0 2 1 0 1 28.244
162 1 0 2 1 1 23.881
163 0 1 3 3 1 27.311
164 0 0 2 4 1 12.716
165 0 1 2 4 1 24.887
TOTAL 1 4 10 12 5 117.039

LOAD UNIT KVA


A 1 14.999
B 4 48.684
C 10 37.02
D 12 15.336
SL 5 1
TOTAL 117.039

KVA = 1.3*kVAtotal
= 152.1507

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 163

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
164 12.716 1 12.716
165 24.887 2 49.774

TOTAL 37.603 62.49

WEST SIDE
POLE NO. Kva span kVAspan
161 28.244 2 56.488
162 23.881 1 23.881

TOTAL 52.125 80.369

USE WEST SIDE OF THE TRANSFORMER OF 52.125 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
217.1875 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 200.44067 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
145110.69

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.4826567 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.512568

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.71357 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 29
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
166 0 0 0 3 1 4.034
167 0 0 0 4 1 5.312
168 1 1 1 2 1 33.628
169 0 1 3 4 1 28.589
170 0 0 2 4 1 12.716
TOTAL 1 2 6 17 5 84.279

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 6 22.212
D 17 21.726
SL 5 1
TOTAL 84.279

KVA = 1.3*kVAtotal
= 109.5627

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 168

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
169 28.589 1 28.589
170 12.716 2 25.432

TOTAL 41.305 54.021

WEST SIDE
POLE NO. Kva span kVAspan
166 4.034 2 8.068
167 5.312 1 5.312

TOTAL 9.346 13.38

USE EAST SIDE OF THE TRANSFORMER OF 41.305 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
172.10417 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 170.0213 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
97537.917

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.1850291 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.1101425

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5458927 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 29
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
171 1 0 2 2 1 25.159
172 0 0 1 2 1 6.458
173 0 1 2 0 1 19.775
174 1 0 1 1 1 20.179
175 0 0 1 7 1 12.848
TOTAL 2 1 7 12 5 84.419

LOAD UNIT KVA


A 2 29.998
B 1 12.171
C 7 25.914
D 12 15.336
SL 5 1
TOTAL 84.419

KVA = 1.3*kVAtotal
= 109.7447

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 173

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
174 20.179 1 20.179
175 12.848 2 25.696

TOTAL 33.027 45.875

WEST SIDE
POLE NO. Kva span kVAspan
171 25.159 2 50.318
172 6.458 1 6.458

TOTAL 31.617 56.776

USE WEST SIDE OF THE TRANSFORMER OF 31.617 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
131.7375 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 233.44656 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
102512.22

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.3984601 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.4217518

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.6757299 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
176 1 0 0 3 1 19.033
177 0 0 1 3 1 7.736
178 1 0 2 3 1 26.437
179 1 1 1 1 1 32.35
180 0 1 1 1 1 17.351
TOTAL 3 2 5 11 5 102.907

LOAD UNIT KVA


A 3 44.997
B 2 24.342
C 5 18.51
D 11 14.058
SL 5 1
TOTAL 102.907

KVA = 1.3*kVAtotal
= 133.7791

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 178

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
179 32.35 1 32.35
180 17.351 2 34.702

TOTAL 49.701 67.052

SOUTH SIDE
POLE NO. Kva span kVAspan
176 19.033 2 38.066
177 7.736 1 7.736

TOTAL 26.769 45.802

USE NORTH SIDE OF THE TRANSFORMER OF 49.701 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
207.0875 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 175.384 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
121066.11

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 2.9055867 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 5.4334471

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.2639363 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
181 1 1 0 0 1 27.37
182 0 1 1 2 1 18.629
183 0 1 2 2 1 22.331
184 0 0 3 2 1 13.862
185 0 0 1 2 1 6.458
TOTAL 1 3 7 8 5 88.65

LOAD UNIT KVA


A 1 14.999
B 3 36.513
C 7 25.914
D 8 10.224
SL 5 1
TOTAL 88.65

KVA = 1.3*kVAtotal
= 115.245

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 183

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
184 13.862 1 13.862
185 6.458 2 12.916

TOTAL 20.32 26.778

SOUTH SIDE
POLE NO. Kva span kVAspan
181 27.37 2 54.74
182 18.629 1 18.629

TOTAL 45.999 73.369

USE SOUTH SIDE OF THE TRANSFORMER OF 45.999 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
191.6625 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 207.35168 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
132471.81

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.1793233 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 5.9453346

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4772228 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
186 0 0 2 2 1 10.16
187 1 1 0 1 1 28.648
188 0 1 1 3 1 19.907
189 1 0 0 3 1 19.033
190 0 0 2 1 1 8.882
TOTAL 2 2 5 10 5 86.63

LOAD UNIT KVA


A 2 29.998
B 2 24.342
C 5 18.51
D 10 12.78
SL 5 1
TOTAL 86.63

KVA = 1.3*kVAtotal
= 112.619

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 188

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
189 19.033 1 19.033
190 8.882 2 17.764

TOTAL 27.915 36.797

SOUTH SIDE
POLE NO. Kva span kVAspan
186 10.16 2 20.32
187 28.648 1 28.648

TOTAL 38.808 48.968

USE SOUTH SIDE OF THE TRANSFORMER OF 38.808 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
161.7 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 164.03422 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
88414.444

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.7935711 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.5386139

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.3077558 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
191 0 0 3 0 1 11.306
192 1 1 0 2 1 29.926
193 0 1 0 4 1 17.483
194 1 0 2 2 1 25.159
195 0 0 1 3 1 7.736
TOTAL 2 2 6 11 5 91.61

LOAD UNIT KVA


A 2 29.998
B 2 24.342
C 6 22.212
D 11 14.058
SL 5 1
TOTAL 91.61

KVA = 1.3*kVAtotal
= 119.093

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 193

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
194 25.159 1 25.159
195 7.736 2 15.472

TOTAL 32.895 40.631

SOUTH SIDE
POLE NO. Kva span kVAspan
191 11.306 2 22.612
192 29.926 1 29.926

TOTAL 41.232 52.538

USE SOUTH SIDE OF THE TRANSFORMER OF 41.232 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
171.8 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 165.64659 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
94860.278

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.0701405 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.9424052

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4760021 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
196 1 0 0 3 1 19.033
197 0 1 0 2 1 14.927
198 0 0 2 1 1 8.882
199 0 1 1 2 1 18.629
200 0 0 2 2 1 10.16
TOTAL 1 2 5 10 5 71.631

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 5 18.51
D 10 12.78
SL 5 1
TOTAL 71.631

KVA = 1.3*kVAtotal
= 93.1203

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 198

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
199 18.629 1 18.629
200 10.16 2 20.32

TOTAL 28.789 38.949

SOUTH SIDE
POLE NO. Kva span kVAspan
196 19.033 2 38.066
197 14.927 1 14.927

TOTAL 33.96 52.993

USE SOUTH SIDE OF THE TRANSFORMER OF 33.96 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
141.5 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 202.85895 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
95681.806

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.1053896 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.9938688

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4974453 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
201 0 0 3 2 1 13.862
202 1 0 1 2 1 21.457
203 1 2 2 1 1 48.223
204 0 1 1 1 1 17.351
205 0 0 1 2 1 6.458
TOTAL 2 3 8 8 5 107.351

LOAD UNIT KVA


A 2 29.998
B 3 36.513
C 8 29.616
D 8 10.224
SL 5 1
TOTAL 107.351

KVA = 1.3*kVAtotal
= 139.5563

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 203

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
204 17.351 1 17.351
205 6.458 2 12.916

TOTAL 23.809 30.267

SOUTH SIDE
POLE NO. Kva span kVAspan
201 13.862 2 27.724
202 21.457 1 21.457

TOTAL 35.319 49.181

USE SOUTH SIDE OF THE TRANSFORMER OF 35.319 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
147.1625 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 181.0224 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
88799.028

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.8100723 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.5627056

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.317794 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
206 0 0 1 2 1 6.458
207 1 1 0 2 1 29.926
208 0 2 2 1 1 33.224
209 0 1 1 1 1 17.351
210 1 0 3 2 1 28.861
TOTAL 2 4 7 8 5 115.82

LOAD UNIT KVA


A 2 29.998
B 4 48.684
C 7 25.914
D 8 10.224
SL 5 1
TOTAL 115.82

KVA = 1.3*kVAtotal
= 150.566

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 208

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
209 17.351 1 17.351
210 28.861 2 57.722

TOTAL 46.212 75.073

SOUTH SIDE
POLE NO. Kva span kVAspan
206 6.458 2 12.916
207 29.926 1 29.926

TOTAL 36.384 42.842

USE NORTH SIDE OF THE TRANSFORMER OF 46.212 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
192.55 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 211.18952 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
135548.47

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.2531633 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 6.0834154

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.5347564 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
211 0 0 1 3 1 7.736
212 0 0 0 3 1 4.034
213 0 1 2 1 1 21.053
214 0 1 2 3 1 23.609
215 0 1 1 1 1 17.351
TOTAL 0 3 6 11 5 73.783

LOAD UNIT KVA


A 0 0
B 3 36.513
C 6 22.212
D 11 14.058
SL 5 1
TOTAL 73.783

KVA = 1.3*kVAtotal
= 95.9179

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 213

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
214 23.609 1 23.609
215 17.351 2 34.702

TOTAL 40.96 58.311

SOUTH SIDE
POLE NO. Kva span kVAspan
211 7.736 2 15.472
212 4.034 1 4.034

TOTAL 11.77 19.506

USE NORTH SIDE OF THE TRANSFORMER OF 40.96 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
170.66667 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 185.06909 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
105283.75

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.5173772 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 6.5953707

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.7480711 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 29
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
216 0 1 0 3 1 16.205
217 1 0 1 1 1 20.179
218 0 0 1 2 1 6.458
219 0 1 1 0 1 16.073
220 0 0 3 1 1 12.584
TOTAL 1 2 6 7 5 71.499

LOAD UNIT KVA


A 1 14.999
B 2 24.342
C 6 22.212
D 7 8.946
SL 5 1
TOTAL 71.499

KVA = 1.3*kVAtotal
= 92.9487

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 218

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
219 16.073 1 16.073
220 12.584 2 25.168

TOTAL 28.657 41.241

WEST SIDE
POLE NO. Kva span kVAspan
216 16.205 2 32.41
217 20.179 1 20.179

TOTAL 36.384 52.589

USE WEST SIDE OF THE TRANSFORMER OF 36.384 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
151.6 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 187.90045 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
94952.361

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 4.0740915 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.9481736

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4784057 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 29
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
221 1 0 0 3 1 19.033
222 0 0 1 3 1 7.736
223 1 0 0 2 1 17.755
224 1 1 1 1 1 32.35
225 0 1 1 1 1 17.351
TOTAL 3 2 3 10 5 94.225

LOAD UNIT KVA


A 3 44.997
B 2 24.342
C 3 11.106
D 10 12.78
SL 5 1
TOTAL 94.225

KVA = 1.3*kVAtotal
= 122.4925

Select 167 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 223

COMPUTATION OF TOTAL CONNECTED LOAD


EAST SIDE
POLE NO. Kva span kVAspan
224 32.35 1 32.35
225 17.351 2 34.702

TOTAL 49.701 67.052

WEST SIDE
POLE NO. Kva span kVAspan
221 19.033 2 38.066
222 7.736 1 7.736

TOTAL 26.769 45.802

USE EAST SIDE OF THE TRANSFORMER OF 49.701 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
207.0875 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 175.384 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
121066.11

FROM THE TABLE 5, USE 300,000 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 19
OUTSIDE DIAMETER (INCHES) = 0.628
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 540
CAPACITIVE REACTANCE (OHM/MILE) = 0.108
RESISTANCE (OHM/MILE) = 0.215
INDUCTIVE REACTANCE (OHM/MILE) = 0.476
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 2.9055867 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.426
RATIO = Xe/Ra
= 1.9813953

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.87 OF 1.9813953 AND 90% pf
VDe = X(VDA)
= 5.4334471

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.2639363 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF WEST IS BIGGER =(130*D42)/B42
IF EAST IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
226 0 0 1 2 1 6.458
227 0 0 2 1 1 8.882
228 0 1 1 2 1 18.629
229 0 0 2 1 1 8.882
230 0 0 2 1 1 8.882
TOTAL 0 1 8 7 5 51.733

LOAD UNIT KVA


A 0 0
B 1 12.171
C 8 29.616
D 7 8.946
SL 5 1
TOTAL 51.733

KVA = 1.3*kVAtotal
= 67.2529

Select 75 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 228

COMPUTATION OF TOTAL CONNECTED LOAD


SOUTH SIDE
POLE NO. Kva span kVAspan
229 8.882 1 8.882
230 8.882 2 17.764

TOTAL 17.764 26.646

NORTH SIDE
POLE NO. Kva span kVAspan
226 6.458 2 12.916
227 8.882 1 8.882

TOTAL 15.34 21.798

USE SOUTH SIDE OF THE TRANSFORMER OF 17.764 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
74.016667 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 195 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
48110.833

FROM THE TABLE 5, USE 66,371 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.292
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 235
CAPACITIVE REACTANCE (OHM/MILE) = 0.131
RESISTANCE (OHM/MILE) = 0.964
INDUCTIVE REACTANCE (OHM/MILE) = 0.574
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 5.2191168 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.524
RATIO = Xe/Ra
= 0.5435685

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.14 OF 0.5435685 AND 90% pf
VDe = X(VDA)
= 5.9497931

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.4790805 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER 31
POLE NUMER A B C D SL MAXIMUN DEMAND (KVA)
231 0 0 1 2 1 6.458
232 1 1 0 1 1 28.648
233 0 0 2 1 1 8.882
234 0 0 2 1 1 8.882
235 1 0 0 2 1 17.755
TOTAL 2 1 5 7 5 70.625

LOAD UNIT KVA


A 2 29.998
B 1 12.171
C 5 18.51
D 7 8.946
SL 5 1
TOTAL 70.625

KVA = 1.3*kVAtotal
= 91.8125

Select 100 kVA transformer, single phase, 13800/240, 60 hz,


oil immersed, pole mounted, self-cooled with 2 1/2% tap at
secondary line located at pole 233

COMPUTATION OF TOTAL CONNECTED LOAD


NORTH SIDE
POLE NO. Kva span kVAspan
234 8.882 1 8.882
235 17.755 2 35.51

TOTAL 26.637 44.392

SOUTH SIDE
POLE NO. Kva span kVAspan
231 6.458 2 12.916
232 28.648 1 28.648

TOTAL 35.106 41.564

USE NORTH SIDE OF THE TRANSFORMER OF 26.637 kVA


COMPUTATION OF LINE VOLTAGE
IL = (Kva*1000)/240
110.9875 A

COMPUTATION OF VOLTAGE DROP (ALLOW


3% DROP ON THE SECONDARY LINE)

VD = 3%*240
= 7.2 V

ASSUMING DISTANCE POLE = 130 ft SPAN


d = (L*kVAspan)/kVA
= 216.65203 ft

COMPUTATION OF SIZE CONDUCTOR IN CIRCULAR MILS


CM = (IL*d*24)/VD
80152.222

FROM THE TABLE 5, USE 167,806 CM


CHARACTERISTICS OF COPPER CONDUCTOR
NUMBER OF WIRES = 7
OUTSIDE DIAMETER (INCHES) = 0.464
APPROXIMATELY MAXIMUM CURRENT
CARRYING CAPACITY (AMPERES) = 359
CAPACITIVE REACTANCE (OHM/MILE) = 0.117
RESISTANCE (OHM/MILE) = 0.382
INDUCTIVE REACTANCE (OHM/MILE) = 0.518
COMPUTATION OF ACTUAL VOLTAGE DROP
VDa = IL*d*24/CM
= 3.4390665 V

COMPUTATION OF THE RATIO OF INDUCTANCE O RESISTANCE USING


TABLE 6
ASSUMING A SEPARATION OF 8 INCHES, FROM TABLE 6, THE
REACTANCE SPACING FACTOR IS Xd = -0.05
Xd = 0.2794*logd d = 8/12
-0.05
TOTAL REACTANCE (Xe) = Xd+Xa
= 0.468
RATIO = Xe/Ra
= 1.2251309

COMPUTATION OF AC DROP FACTOR "X" USING TABLE 7, USING AN


90% POWER FACTOR
X = 1.46 OF 1.2251309 AND 90% pf
VDe = X(VDA)
= 5.0210372

PERCENT VOLTAGE DROP


%VD = VDe/V*100
= 2.0920988 % <3%
LOAD DEMAND CELLS TO MODIFY
A 14.999 >TRANSFORMER UP TO SIZE
B 12.171 >44 (WHICH SIDE HAS BIGGER KVA)
C 3.702 > C57
D 1.278 IF 2ND SIDE IS BIGGER =(130*D42)/B42
IF 1ST SIDE IS BIGGER =(130*D35)/B35
>C63 and following parts (REFER ON TABLE 5)
>C89
TRANSFORMER NO.1
UNCLE'S LAUNDRY SHOP

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 55 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 32.60236 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 38.35572 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240,


60 hz, oil immersed, pole mounted, located at pole
no. 73

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 159.8155 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 199.7694 A
Use 50 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.2
ST. JOSHUA'S CHAPEL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6 kW
DEMAND FACTOR = 55 %
GENERAL POWER LOAD TOTAL = 30 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 20.395833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 23.995098 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 86

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 99.979575 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 124.97447 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.3
TIMAWA INTEGRATED SCHOOL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4.3 kW
DEMAND FACTOR = 55 %
GENERAL POWER LOAD TOTAL = 40 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 25.159444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 29.599346 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 62

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 123.33061 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 154.16326 A
Use 30 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.4
EMMA'S BOOK STORE AND SCHOOL SUPPLIES

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 20 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 14.729444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 17.328758 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 63

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 72.203159 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 90.253949 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.5
JENNY'S BOOK STORE AND SCHOOL SUPPLIES

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 20 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 14.729444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 17.328758 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 63

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 72.203159 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 90.253949 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.6
BUBBLE'S LAUNDRY SHOP

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 55 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 32.602361 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 38.355719 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 64

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 159.8155 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 199.76937 A
Use 50 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.7
GINA'S EATERY

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 25 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.836528 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.80768 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 60

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 82.531999 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.165 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.8
SHAWTY'S BOOK STORE AND SCHOOL SUPPLIES

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 20 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 14.729444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 17.328758 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 60

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 72.203159 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 90.253949 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.9
SHANKS'S COMPUTER SHOP AND ARCADE CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 41.150556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 48.412418 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 59

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 201.71841 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 252.14801 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.10
LOW GAS STATION

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 19 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.965972 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.959967 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 26

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 83.166531 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.95816 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.11
LARA PASTRIES

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 25 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.836528 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.80768 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 236

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 82.531999 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.165 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.12
LAZARO PRIVATE SCHOOL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4.3 kW
DEMAND FACTOR = 55 %
GENERAL POWER LOAD TOTAL = 40 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 25.159444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 29.599346 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 236

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 123.33061 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 154.16326 A
Use 30 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.13
SHOT BANK

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 237

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.14
LOCAL BOOK STORE AND GIFT SHOP

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 20 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 14.729444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 17.328758 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 238

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 72.203159 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 90.253949 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.15
THUNDER MALL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 44.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 52.647712 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 239

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 219.36547 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 274.20684 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.16
UNIVERSAL TRADE CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 44.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 52.647712 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 240

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 219.36547 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 274.20684 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.17
JOHN'S AUTOMOTIVE CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 19 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.965972 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.959967 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 241

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 83.166531 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.95816 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.17
LAZA SALES CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 44.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 52.647712 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 242

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 219.36547 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 274.20684 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.19
JAZZ MALL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 44.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 52.647712 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 243

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 219.36547 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 274.20684 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.20
GINA CALL CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 45.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 53.824183 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 243

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 224.26743 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 280.33429 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.21
ROD'S GASOLINE STATION

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 19 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.965972 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.959967 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 244

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 83.166531 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.95816 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.22
TRAUMALENE BUS STATION

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 11.940833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 14.048039 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 245

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 58.533497 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 73.166871 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.23
JOY BANK

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 129

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.24
RODNEY'S COMPUTER SHOP AND ARCADE CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 41.150556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 48.412418 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 127

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 201.71841 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 252.14801 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.25
BLOSSOM'S LAUNDRY SHOP

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 55 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 32.602361 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 38.355719 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 112

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 159.8155 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 199.76937 A
Use 50 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.26
AWIT PUBLIC HIGH SCHOOL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4.3 kW
DEMAND FACTOR = 55 %
GENERAL POWER LOAD TOTAL = 40 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 25.159444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 29.599346 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 119

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 123.33061 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 154.16326 A
Use 30 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.27
GIA'S BOOK STORE AND SCHOOL SUPPLIES

CONNECTED LOADS
LIGHTING LOAD TOTAL = 1.8 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 20 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 14.729444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 17.328758 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 119

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 72.203159 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 90.253949 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.28
HONDA SHOWROOM

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 155

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.29
TOYOTA SHOWROOM

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 155

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.30
SALCEDO GIFT SHOP

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 40 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 28.794444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 33.875817 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 246

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 141.14924 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 176.43655 A
Use 38 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.31
UNIVERSAL BANK

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 247

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.32
SHOPMART SUPERMARKET

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 45.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 53.824183 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 248

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 224.26743 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 280.33429 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.33
JACK CALL CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 45.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 53.824183 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 248

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 224.26743 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 280.33429 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.34
JACK'S RESTO

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 25 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.836528 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.80768 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 249

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 82.531999 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.165 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.35
SHAI ENTERTAINMENT CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 68 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 44.750556 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 52.647712 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 250

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 219.36547 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 274.20684 A
Use 80 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.36
SIMP GASOLINE STATION

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 19 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.965972 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.959967 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 251

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 83.166531 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.95816 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.37
SIMP AUTOMOTIVE CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 19 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.965972 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.959967 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 252

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 83.166531 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.95816 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.38
SALCEDO HOSPITAL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 100 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 62.986111 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 74.101307 kVA

TRANSFORMER SPECIFICATIONS

Select 75 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 257

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 308.75545 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 385.94431 A
Use 125 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.39
FREEDOM PARK

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 9.9908333 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 11.753922 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 263

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 48.974673 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 61.218342 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.40
JOHN CAR WASH SERVICES

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 19 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.965972 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.959967 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 265

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 83.166531 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.95816 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.41
PLDC HOME INTERNET CENTER

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 266

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.42
THY ROOTS CLOTHING

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 40 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 29.794444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 35.052288 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 267

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 146.0512 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 182.564 A
Use 38 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.43
SALCEDO WATER STATION

CONNECTED LOADS
LIGHTING LOAD TOTAL = 10 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 50 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 35.493056 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 41.756536 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 269

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 173.98557 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 217.48196 A
Use 50 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.44
SALCEDO FIRE STATION

CONNECTED LOADS
LIGHTING LOAD TOTAL = 6.95 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 19 HP
DEMAND FACTOR = 65 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 16.965972 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 19.959967 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 270

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 83.166531 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 103.95816 A
Use 22 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.45
SALCEDO MUNICIPAL HALL

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 42 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 26.734167 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 31.451961 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 272

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 131.04984 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 163.8123 A
Use 38 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.46
SALCEDO POLICE STATION

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 275

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.47
SALCEDO SPORT'S COMPLEX

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4 kW
DEMAND FACTOR = 60 %
GENERAL POWER LOAD TOTAL = 60 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 36.591667 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 43.04902 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 278

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 179.37092 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 224.21364 A
Use 50 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.48
SALCEDO STATE UNIVERSITY

CONNECTED LOADS
LIGHTING LOAD TOTAL = 4.3 kW
DEMAND FACTOR = 55 %
GENERAL POWER LOAD TOTAL = 40 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 25.159444 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 29.599346 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 280

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 123.33061 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 154.16326 A
Use 30 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.49
ROD'S WET AND DRY PUBLIC MARKET

CONNECTED LOADS
LIGHTING LOAD TOTAL = 5 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 50 HP
DEMAND FACTOR = 55 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 31.993056 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 37.638889 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 283

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 156.8287 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 196.03588 A
Use 50 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.50
SALCEDO HALL OF JUSTICE

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 286

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
TRANSFORMER NO.51
MERALCO

CONNECTED LOADS
LIGHTING LOAD TOTAL = 3.7 kW
DEMAND FACTOR = 70 %
GENERAL POWER LOAD TOTAL = 10 HP
DEMAND FACTOR = 75 %
MOTOR EFFICIENCY = 72 %

COMPUTED TOTAL KILOWATTS AND APPLYING DEMAND FACTOR FORM TABLE 8

kW = ((HP*0.746*df)/eff) + (LL*df)
kW = 10.360833 kW

RATING IN KILOVOLT-AMPERES (kVA) AT 85% POWER FACTOR


kVA = kW/pf
kVA = 12.189216 kVA

TRANSFORMER SPECIFICATIONS

Select 50 kVA transformer, single phase, 13800/240, 60


hz, oil immersed, pole mounted, located at pole no. 288

COMPUTING FOR FULL LOAD CURRENT


IFL = (kVA*1000)/Vs
IFL = 50.788399 A

AMPACITY OF COPPER CONDUCTOR TO BE USED AT 125% DEMAND FACTOR


AMPACITY = IFL * 125%
AMPACITY = 63.485498 A
Use 14 mm THW copper conductor at 75⁰C for the secondary distribution line
2
RESIDENTIAL CUSTOMER
LOAD SCHEDULE OF FEEDER NO. 1
TRANSFORMER NO. PHASE A PHASE B PHASE C 3-PHASE
1 167
2 167
3 167
4 167
5 167
6 167
7 167
8 167
9 167
10 167
11 167
12 167
13 100
14 100
15 167
16 167
17 167
18 167
TOTAL 935 935 1002

PRIMARY WIRE COMPUTATION FOR FEEDER NO. 1


FEEDER NO.: 1 LOAD: 2872 kVA
POLES NO. : 1 to 90 TOTAL LENGTH 11,700 ft.
(130 ft. per span)

Voltage Drop, assume 3% voltage drop


Voltage Drop = 3% x Operatig Primary Voltage
VD = 0.03 x 34,500
VD = 1035 V

FEEDER LOAD CURRENT


IL = kVA load/(√3*kV)
IL = 48.06 A

SIZE OF PRIMARY WIRE


CM = (24*I*L*(√3/2))/VD
CM = 11292.55
Use 16510 CM, 50⁰C operating temperature, 60 Hz, 1 ft spacing,
hard-drawn copper wire with the following characteristics:

16510 CM:
Resistance (ohm per conductor per mile) = 3.79
Inductive Reactance = 0.665
Shunt Capacitive Reactance = 0.153
Ratio of Reactance to Resistance
X/R = (Xinductive + Xshunt capacitive )/R
X/R = 0.2158311

Actual Voltage Drop


VD = (24*I*L*(√3/2))/CM
VD = 707.92194

AC Voltage Drop Factor at 0.98 for 0.85 power factor


Actual voltage drop = 0.98 x 707.9219
Actual voltage drop = 693.7635
Actual % voltage drop = 2.010909 %

Remarks: Acceptable
RESIDENTIAL CUSTOMER
LOAD SCHEDULE OF FEEDER NO. 2
TRANSFORMER NO. PHASE A PHASE B PHASE C 3-PHASE
19 167
20 167
21 167
22 167
23 167
24 100
25 100
26 75
27 167
28 167
29 167
30 167
31 100
32 100
33 167
34 167
35 167
36 167
TOTAL 868 843 935

PRIMARY WIRE COMPUTATION FOR FEEDER NO. 2


FEEDER NO.: 2 LOAD: 2646 kVA
POLES NO. : 91 to 180 TOTAL LENGTH 11,700 ft.
(130 ft. per span)

Voltage Drop, assume 3% voltage drop


Voltage Drop = 3% x Operatig Primary Voltage
VD = 0.03 x 34,500
VD = 1035 V

FEEDER LOAD CURRENT


IL = kVA load/(√3*kV)
IL = 44.28 A

SIZE OF PRIMARY WIRE


CM = (24*I*L*(√3/2))/VD
CM = 10403.93
Use 16510 CM, 50⁰C operating temperature, 60 Hz, 1 ft spacing,
hard-drawn copper wire with the following characteristics:

16510 CM:
Resistance (ohm per conductor per mile) = 3.79
Inductive Reactance = 0.665
Shunt Capacitive Reactance = 0.153
Ratio of Reactance to Resistance
X/R = (Xinductive + Xshunt capacitive )/R
X/R = 0.2158311

Actual Voltage Drop


VD = (24*I*L*(√3/2))/CM
VD = 652.21499

AC Voltage Drop Factor at 0.98 for 0.85 power factor


Actual voltage drop = 0.98 x 652.21499
Actual voltage drop = 639.17069
Actual % voltage drop = 1.8526687 %

Remarks: Acceptable
RESIDENTIAL CUSTOMER
LOAD SCHEDULE OF FEEDER NO. 3
TRANSFORMER NO. PHASE A PHASE B PHASE C 3-PHASE
37 167
38 167
39 167
40 167
41 167
42 100
43 100
44 75
45 167
46 167
47 167
TOTAL 601 576 434

PRIMARY WIRE COMPUTATION FOR FEEDER NO. 3


FEEDER NO.: 3 LOAD: 1611 kVA
POLES NO. : 181 to 235 TOTAL LENGTH 7,150 ft.
(130 ft. per span)

Voltage Drop, assume 3% voltage drop


Voltage Drop = 3% x Operatig Primary Voltage
VD = 0.03 x 34,500
VD = 1035 V

FEEDER LOAD CURRENT


IL = kVA load/(√3*kV)
IL = 26.96 A

SIZE OF PRIMARY WIRE


CM = (24*I*L*(√3/2))/VD
CM = 3871.00
Use 16510 CM, 50⁰C operating temperature, 60 Hz, 1 ft spacing,
hard-drawn copper wire with the following characteristics:

16510 CM:
Resistance (ohm per conductor per mile) = 3.79
Inductive Reactance = 0.665
Shunt Capacitive Reactance = 0.153
Ratio of Reactance to Resistance
X/R = (Xinductive + Xshunt capacitive )/R
X/R = 0.2158311

Actual Voltage Drop


VD = (24*I*L*(√3/2))/CM
VD = 242.67032

AC Voltage Drop Factor at 0.98 for 0.85 power factor


Actual voltage drop = 0.98 x 242.67032
Actual voltage drop = 237.81691
Actual % voltage drop = 0.6893244 %

Remarks: Acceptable
COMMERCIAL CUSTOMER
LOAD SCHEDULE OF FEEDER NO. 4
TRANSFORMER NO. PHASE A PHASE B PHASE C 3-PHASE
C1 50
C2 50
C3 50
C4 50
C5 50
C6 50
C7 50
C8 50
C9 50
C10 50
C11 50
C12 50
C13 50
C14 50
C15 75
C16 75
C17 50
C18 75
C19 75
C20 75
C21 50
C22 50
C23 50
C24 50
C25 50
C26 50
C27 50
C28 50
C29 50
C30 50
C31 50
C32 75
C33 75
C34 50
C35 75
C36 50
C37 50
C38 75
C39 50
C40 50
C41 50
C42 50
C43 50
C44 50
C45 50
C46 50
C47 50
C48 50
C49 50
C50 50
C51 50
TOTAL 900 950 925

PRIMARY WIRE COMPUTATION FOR FEEDER NO. 4


FEEDER NO.: 4 LOAD: 2775 kVA
POLES NO. : 26-288 TOTAL LENGTH 34,190 ft.
(130 ft. per span)

Voltage Drop, assume 3% voltage drop


Voltage Drop = 3% x Operatig Primary Voltage
VD = 0.03 x 34,500
VD = 1035 V

FEEDER LOAD CURRENT


IL = kVA load/(√3*kV)
IL = 46.44 A

SIZE OF PRIMARY WIRE


CM = (24*I*L*(√3/2))/VD
CM = 31884.81

Use 41,741 CM, 50⁰C operating temperature, 60 Hz, 1 ft spacing,


hard-drawn copper wire with the following characteristics:

41,741 CM:
Resistance (ohm per conductor per mile) = 1.52
Inductive Reactance = 0.599
Shunt Capacitive Reactance = 0.135
Ratio of Reactance to Resistance
X/R = (Xinductive + Xshunt capacitive )/R
X/R = 0.4828947

Actual Voltage Drop


VD = (24*I*L*(√3/2))/CM
VD = 790.60834

AC Voltage Drop Factor at 1.13 for 0.85 power factor


Actual voltage drop = 1.13 x 790.60834
Actual voltage drop = 893.38742
Actual % voltage drop = 2.5895288 %

Remarks: Acceptable