Transformer no.

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
1 1 2 4 0 1
2 1 4 2 0 1
3 0 0 6 0 1
4 2 3 0 0 1
5 0 6 4 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
1 14.39 8.06 2.332 0 0.15 24.932
2 14.39 16.12 1.166 0 0.15 31.826
3 0 0 3.498 0 0.15 8.648
4 28.78 12.09 0 0 0.15 41.02
5 0 24.18 2.332 0 0.15 26.662
Total 128.088

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 128.088 / 150 ) x 100% = 85%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 =11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.

Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 128.089KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.1 is located at pole no.3

Upper side
Pole number Kva / Pole No. of Span Kva-span
1 24.932 2 49.864
2 31.826 1 31.826
81.69

Lower side
Pole number Kva / Pole No. of Span Kva-span
4 41.02 1 41.02
5 26.662 2 53.326
94.344

%Kva= ( 81.69 / 94.344) x 100% = 87%

Therefore, Transformer no.1 should be installed at pole no. 3

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=150,000 / 230 = 652.17 A.

use: 2-167,806 CM Hard Drawn Copper Conductor per line

Ra= 0.382 Xa= 0.518

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.518 + 0.035= 0.553
Xc / Ra= 0.553 / 0.382= 1.447

By using 80% power factor, the Drop Factor is 1.7

2.) Calculation of %VR:

Upper side

Ispan-1 = 24,932 / 230= 108.4 A.

Vdc= (24 x 108.4 x 100) / 167,806= 1.55 V.

Vac= D.F. x Vdc = 1.7 x 1.55= 2.64 V.

Ispan-2 = 31,826 / 230= 138.35 A.

Vdc= (24 x 138.35 x 100) / 167,806= 1.979 V.

Vac= D.F. x Vdc = 1.7 x 1.979= 3.67 V.

Vac TOTAL = 2.64 + 3.67= 6.31 V.

%VR= (6.31 / 230) x 100%= 2.74%


Lower side

Ispan-1 = 41,020 / 230= 178.36 A.

Vdc= (24 x 178.36 x 100) / 167,806= 2.55 V.

Vac= D.F. x Vdc = 1.7 x 2.55= 4.34 V.

Ispan-2 = 26,660 / 230= 115.65 A.

Vdc= (24 x 114.65 x 100) / 167,806= 1.65 V.

Vac= D.F. x Vdc = 1.7 x 1.65= 2.8 V.

Vac TOTAL = 4.34 + 2.8= 7.1 V.

%VR= (7.1 / 230) x 100%= 3%


Transformer no.2

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
6 2 3 4 0 1
7 0 1 6 0 1
8 0 3 5 0 1
9 0 2 7 0 1
10 1 7 3 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
6 28.78 12.09 2.332 0 0.15 43.352
7 0 4.03 3.498 0 0.15 7.578
8 0 12.09 2.915 0 0.15 15.155
9 0 8.06 4.081 0 0.15 12.265
10 14.39 28.21 1.749 0 0.15 44.379
Total 122.849

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 122.489 / 150 ) x 100% = 81.89%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 =11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.

Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 122.849KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.2 is located at pole no.8

Upper side
Pole number Kva / Pole No. of Span Kva-span
6 43.352 2 86.704
7 7.678 1 7.678
94.382

Lower side
Pole number Kva / Pole No. of Span Kva-span
9 12.265 1 12.265
10 44.399 2 88.798
101.06

%Kva= ( 94.382 / 101.06) x 100% = 93.39%

Therefore, Transformer no.2 should be installed at pole no. 8

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=150,000 / 230 = 652.17 A.

use: 2-167,806 CM Hard Drawn Copper Conductor per line

Ra= 0.382 Xa= 0.518

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.518 + 0.035= 0.553
Xc / Ra= 0.553 / 0.382= 1.447

By using 80% power factor, the Drop Factor is 1.7

2.) Calculation of %VR:

Upper side

Ispan-1 = 43,352 / 230= 188.49 A.

Vdc= (24 x 188.49 x 100) / 167,806= 2.69 V.

Vac= D.F. x Vdc = 1.7 x 2.69= 4.58 V.

Ispan-2 = 7,678 / 230= 33.38 A.

Vdc= (24 x 33.38 x 100) / 167,806= 0.48 V.

Vac= D.F. x Vdc = 1.7 x 0.48= 0.81 V.

Vac TOTAL = 4.58 + 0.81= 5.39 V.

%VR= (5.39 / 230) x 100%= 2.34%


Lower side

Ispan-1 = 12,265 / 230= 53.33 A.

Vdc= (24 x 53.33 x 100) / 167,806= 0.76 V.

Vac= D.F. x Vdc = 1.7 x 0.76= 1.29 V.

Ispan-2 = 44,399 / 230= 193.03 A.

Vdc= (24 x 193.03 x 100) / 167,806= 2.7 V.

Vac= D.F. x Vdc = 1.7 x 2.7= 4.69 V.

Vac TOTAL = 1.29 + 4.69= 5.98 V.

%VR= (5.98 / 230) x 100%= 2.6%


Transformer no.3

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
11 1 3 7 0 1
12 0 2 8 0 1
13 0 4 2 1 1
14 0 3 7 0 1
15 0 7 7 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
11 14.39 12.09 4.081 0 0.15 30.711
12 0 8.06 4.664 0 0.15 12.874
13 0 16.12 1.166 25 0.15 42.436
14 0 12.09 4.081 0 0.15 16.321
15 0 28.21 4.081 0 0.15 32.441
Total 132.78

Maximum Demand Load:


Assuming:
167 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 132.78 / 167 ) x 100% = 79.51%

1.) IFL = 167 / 20 = 8.35 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 8.35 = 12.53 A.

3.) The short circuit KVA in the primary:


KVASC = 167 / 0.03 = 5566.67 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 167 / (0.03 x 20) = 278.33 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 278.33 = 445.33 A.

Therfore:
The rating of the distribution transformer shall be 167 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 132.78 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 12.53 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.3 is located at pole no.13

Upper side
Pole number Kva / Pole No. of Span Kva-span
11 24.932 2 49.864
12 31.826 1 31.826
81.69

Lower side
Pole number Kva / Pole No. of Span Kva-span
14 41.02 1 41.02
15 26.662 2 53.326
94.344

%Kva= ( 81.69 / 94.344) x 100% = 87%

Therefore, Transformer no.1 should be installed at pole no. 3

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=167,000 / 230 = 726.1 A.

use: 2-211,600 CM Hard Drawn Copper Conductor per line

Ra= 0.303 Xa= 0.504

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.504 + 0.035= 0.539
Xc / Ra= 0.539 / 0.303= 1.779

By using 80% power factor, the Drop Factor is 1.91

2.) Calculation of %VR:

Upper side

Ispan-1 = 31,711 / 230= 133.5 A.

Vdc= (24 x 133.5 x 100) / 211,600= 1.51 V.

Vac= D.F. x Vdc = 1.91 x 1.51= 2.89 V.

Ispan-2 = 12,874 / 230= 55.97 A.

Vdc= (24 x 55.97 x 100) / 211,600= 0.635 V.

Vac= D.F. x Vdc = 1.91 x 0.635= 1.21 V.

Vac TOTAL = 2.89 + 1.21= 4.1 V.

%VR= (4.1 / 230) x 100%= 1.78%


Lower side

Ispan-1 = 16,321 / 230= 70.96 A.

Vdc= (24 x 70.96 x 100) / 211,600= 0.8 V.

Vac= D.F. x Vdc = 1.91 x 0.8= 1.54 V.

Ispan-2 = 32,441 / 230= 141.05 A.

Vdc= (24 x 141.05 x 100) / 211,600= 1.59 V.

Vac= D.F. x Vdc = 1.91 x 1.59= 3.04 V.

Vac TOTAL = 1.54 + 3.04= 4.58 V.

%VR= (4.58 / 230) x 100%= 1.99%


Transformer no.4

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
16 0 1 10 1 1
17 0 2 7 0 1
18 0 0 7 1 1
19 0 2 0 0 1
20 1 3 2 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
16 0 4.03 5.83 15 0.15 25.01
17 0 8.06 4.081 0 0.15 12.291
18 0 0 4.081 0 0.15 10.231
19 0 8.06 0 0 0.15 8.21
20 14.39 12.09 1.166 0 0.15 27.79
Total 83.532

Maximum Demand Load:


Assuming:
100 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 128.088 / 100 ) x 100% = 83.532%

1.) IFL = 100 / 20 = 5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 5 = 7.5 A.

3.) The short circuit KVA in the primary:


KVASC = 100 / 0.03 = 3,333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 100 / (0.003 x 20) = 166.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 166.67 = 266.67 A.

Therfore:
The rating of the distribution transformer shall be 100 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 83.532 KVA, it shall be
protected by 10 Amps Fuse Link. The rating of the fuse cutout shall be 10 Amps. The
maximum fuse setting is 7.5 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.4 is located at pole no.18

Left side
Pole number Kva / Pole No. of Span Kva-span
16 24.886 2 50.02
17 12.291 1 12.291
62.311

Right side
Pole number Kva / Pole No. of Span Kva-span
19 8.21 1 8.21
20 27.79 2 55.58
63.79

%Kva= ( 62.311 / 63.79) x 100% = 97.68%

Therefore, Transformer no.4 should be installed at pole no. 18

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 100,000 / 230 = 434.78 A.

use: 2- 250,000 CM Hard Drawn Copper Conductor per line

Ra= 0.257 Xa= 0.487

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.487 + 0.035= 0.522
Xc / Ra= 0.552 / 0.257= 2.03

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 25,000 / 230= 108.69 A.

Vdc= (24 x 108.69 x 100) / 250,000= 1.04 V.

Vac= D.F. x Vdc = 2.1 x 1.04= 2.19 V.

Ispan-2 = 12,291 / 230= 53.44 A.

Vdc= (24 x 53.44 x 100) / 250,000= 0.513 V.

Vac= D.F. x Vdc = 2.1 x 0.513= 1.1 V.

Vac TOTAL = 1.04 + 1.1= 2.12 V.

%VR= (2.12 / 230) x 100%= 0.92%


Right side

Ispan-1 = 8,210 / 230= 35.69 A.

Vdc= (24 x 35.69 x 100) / 250,000= 0.34 V.

Vac= D.F. x Vdc = 2.1 x 0.34= 0.72 V.

Ispan-2 = 27,790 / 230= 120.83 A.

Vdc= (24 x 120.83 x 100) / 250,000= 1.16 V.

Vac= D.F. x Vdc = 2.1 x 1.16= 2.44 V.

Vac TOTAL = 0.72 + 2.44= 3.16 V.

%VR= (3.16 / 230) x 100%= 1.37%


Transformer no.5

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
21 0 1 3 0 1
22 0 4 1 0 1
23 0 0 0 0 1
24 0 2 0 0 1
25 1 1 3 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
21 0 4.03 1.749 0 0.15 15.903
22 0 16.12 0.583 0 0.15 16.853
23 0 0 0 0 0.15 0.15
24 0 8.06 0 0 0.15 8.21
25 14.39 4.03 1.749 0 0.15 20.319
Total 61.44

Maximum Demand Load:


Assuming:
75 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 61.44 / 75 ) x 100% = 81.92%

1.) IFL = 75 / 20 = 3.75 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 3.75 = 5.625 A.

3.) The short circuit KVA in the primary:


KVASC = 75 / 0.03 = 2,500 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 75 / (0.03 x 20) = 125 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 125 = 200 A.

Therfore:
The rating of the distribution transformer shall be 75 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 61.44 KVA, it shall be
protected by 6 Amps Fuse Link. The rating of the fuse cutout shall be 6 Amps. The maximum
fuse setting is 5.625 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.5 is located at pole no.23

Left side
Pole number Kva / Pole No. of Span Kva-span
21 15.903 2 31.806
22 16.853 1 16.853
48.659

Right side
Pole number Kva / Pole No. of Span Kva-span
24 8.21 1 8.21
25 20.319 2 40.638
48.848

%Kva= ( 48.659 / 48.848) x 100% = 99.61%

Therefore, Transformer no.5 should be installed at pole no. 23

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=75,000 / 230 = 326.1 A.

use: 1-250,000 CM Hard Drawn Copper Conductor per line

Ra= 0.257 Xa= 0.487

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.487 + 0.035= 0.0.522
Xc / Ra= 0.522 / 0.257= 2.03

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 15,903 / 230= 69.14 A.

Vdc= (24 x 69.14 x 100) / 250,000= 0.664 V.

Vac= D.F. x Vdc = 2.1 x 0.664= 1.39 V.

Ispan-2 = 16,903 / 230= 73.49 A.

Vdc= (24 x 73.49 x 100) / 250,000= 0.706 V.

Vac= D.F. x Vdc = 2.1 x 0.706= 1.48 V.

Vac TOTAL = 1.39 + 1.48= 2.87 V.

%VR= (2.87 / 230) x 100%= 1.25%


Right side

Ispan-1 = 8,210 / 230= 35.69 A.

Vdc= (24 x 35.69 x 100) / 250,000= 0.343 V.

Vac= D.F. x Vdc = 2.1 x 0.343= 0.72 V.

Ispan-2 = 20,319 / 230= 89.34 A.

Vdc= (24 x 89.34 x 100) / 250,000= 0.858 V.

Vac= D.F. x Vdc = 2.1 x 0.858= 1.8 V.

Vac TOTAL = 0.72 + 1.8= 2.52 V.

%VR= (2.52 / 230) x 100%= 1.1%


Transformer no.6

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
26 0 2 0 0 1
27 0 0 0 0 1
28 1 0 0 0 1
29 0 0 3 0 1
30 0 0 11 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
26 0 8.06 0 0 0.15 8.21
27 0 0 0 0 0.15 0.15
28 14.39 0 0 0 0.15 14.54
29 0 0 1.749 0 0.15 1.899
30 0 0 6.413 0 0.15 6.563
Total 31.362

Maximum Demand Load:


Assuming:
37.5 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 31.362 / 37.5 ) x 100% = 83.632%

1.) IFL = 37.5 / 20 = 1.875 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 1.875 = 2.81 A.

3.) The short circuit KVA in the primary:


KVASC = 37.5 / 0.03 = 1250 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 37.5 / (0.03 x 20) = 62.5 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 62.5 = 100 A.

Therfore:
The rating of the distribution transformer shall be 37.5 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 31.362 KVA, it shall be
protected by 3 Amps Fuse Link. The rating of the fuse cutout shall be 3 Amps. The maximum
fuse setting is 2.81 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.6 is located at pole no.28

Left side
Pole number Kva / Pole No. of Span Kva-span
26 8.21 2 16.42
27 0.15 1 0.15
16.57

Right side
Pole number Kva / Pole No. of Span Kva-span
29 1.899 1 1.899
30 6.563 2 13.126
15.025

%Kva= ( 15.025 / 16.57) x 100% = 90.7%

Therefore, Transformer no.6 should be installed at pole no. 28

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=37,500 / 230 = 163.04 A.

use: 1-66,371 CM Hard Drawn Copper Conductor per line

Ra= 0.59 Xa= 0.571

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.571 + 0.035= 0.606
Xc / Ra= 0.606 / 0.59= 1.03

By using 80% power factor, the Drop Factor is 1.45

2.) Calculation of %VR:

Left side

Ispan-1 = 8,210 / 230= 35.69 A.

Vdc= (24 x 35.69 x 100) / 66,371= 1.29 V.

Vac= D.F. x Vdc = 1.45 x 1.29= 1.87 V.

Ispan-2 = 150 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 66,371= 0.02 V.

Vac= D.F. x Vdc = 1.45 x 0.02= 0.03 V.

Vac TOTAL = 1.87 + 0.03= 1.9 V.

%VR= (1.9 / 230) x 100%= 0.83%


Right side

Ispan-1 = 1,899 / 230= 8.26 A.

Vdc= (24 x 8.26 x 100) / 66,371= 0.299 V.

Vac= D.F. x Vdc = 1.45 x 0.299= 0.43 V.

Ispan-2 = 6,563 / 230= 28.53 A.

Vdc= (24 x 28.53 x 100) / 66,371= 1.03 V.

Vac= D.F. x Vdc = 1.45 x 1.03= 1.49 V.

Vac TOTAL = 0.43 + 1.49= 1.93 V.

%VR= (1.93 / 230) x 100%= 0.84%


Transformer no.7

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
31 0 1 0 1 1
32 0 0 3 0 1
33 0 2 6 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
31 0 4.03 0 7 0.15 11.18
32 0 0 1.749 0 0.15 1.899
33 0 8.06 3.493 0 0.15 11.708
Total 24.787

Maximum Demand Load:


Assuming:
30 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 24.787 / 30 ) x 100% = 82.62%

1.) IFL = 30 / 20 = 1.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 1.5 = 2.25 A.

3.) The short circuit KVA in the primary:


KVASC = 30 / 0.03 = 1000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 30 / (0.03 x 20) = 50 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 50 = 80 A.

Therfore:
The rating of the distribution transformer shall be 30 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 24.787 KVA, it shall be
protected by 3 Amps Fuse Link. The rating of the fuse cutout shall be 3 Amps. The maximum
fuse setting is 2.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.7 is located at pole no.32

Left side
Pole number Kva / Pole No. of Span Kva-span
31 11.18 1 11.18
11.18

Right side
Pole number Kva / Pole No. of Span Kva-span
33 11.708 1 11.708
11.708

%Kva= ( 11.18 / 11.708) x 100% = 90.7%

Therefore, Transformer no.7 should be installed at pole no. 32

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 30,000 / 230 = 130.43 A.

use: 1-66,371 CM Hard Drawn Copper Conductor per line

Ra= 1.52 Xa= 0.599

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.599 + 0.035= 0.634
Xc / Ra= 0.634 / 1.52= 0.417

By using 80% power factor, the Drop Factor is 1.1

2.) Calculation of %VR:

Left side

Ispan-1 = 11,180 / 230= 48.61 A.

Vdc= (24 x 48.61 x 100) / 41,741= 2.79 V.

Vac= D.F. x Vdc = 1.1 x 2.79= 3.1 V.

Vac TOTAL = 3.1= 3.1 V.

%VR= (3.1 / 230) x 100%= 1.33%


Right side

Ispan-1 = 11,708 / 230= 50.9 A.

Vdc= (24 x 50.9 x 100) / 41,741= 2.93 V.

Vac= D.F. x Vdc = 1.1 x 2.93= 3.22 V.

Vac TOTAL = 3.22= 3.22 V.

%VR= (3.22 / 230) x 100%= 1.39%


Transformer no.8

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
34 0 0 2 2 1
35 0 0 6 0 1
36 0 0 5 2 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
34 0 0 1.166 30 0.15 31.316
25 0 0 3.498 0 0.15 3.748
26 0 0 2.915 26 0.15 34.085
Total 69.129

Maximum Demand Load:


Assuming:
75 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 69.129 / 75 ) x 100% = 92.172%

1.) IFL = 75 / 20 = 3.75 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 3.75 = 5.625 A.

3.) The short circuit KVA in the primary:


KVASC = 75 / 0.03 = 2,500 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 75 / (0.03 x 20) = 125 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 125 = 200 A.

Therfore:
The rating of the distribution transformer shall be 75 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 69.129 KVA, it shall be
protected by 6 Amps Fuse Link. The rating of the fuse cutout shall be 6 Amps. The maximum
fuse setting is 5.625 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.8 is located at pole no.35

Left side
Pole number Kva / Pole No. of Span Kva-span
34 31.316 1 31.316
31.316

Right side
Pole number Kva / Pole No. of Span Kva-span
36 34.065 1 34.065
34.065

%Kva= ( 31.316 / 34.065) x 100% = 91.93%

Therefore, Transformer no.8 should be installed at pole no. 35

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 75,000 / 230 = 326.09 A.

use: 1-133,077 CM Hard Drawn Copper Conductor per line

Ra= 0.481 Xa= 0.532

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.532 + 0.035= 0.567
Xc / Ra= 0.567 / 0.481= 1.179

By using 80% power factor, the Drop Factor is 1.51

2.) Calculation of %VR:

Left side

Ispan-1 = 31,316 / 230= 136.16 A.

Vdc= (24 x 136.16 x 100) / 133,077= 2.46 V.

Vac= D.F. x Vdc = 1.51 x 2.46= 3.71 V.

Vac TOTAL = 3.71= 3.71 V.

%VR= (3.71 / 230) x 100%= 1.63%


Right side

Ispan-1 = 34,065 / 230= 148.11 A.

Vdc= (24 x 148.11 x 100) / 133,077= 2.67 V.

Vac= D.F. x Vdc = 1.51 x 2.67= 4.03 V.

Vac TOTAL = 4.03= 4.03 V.

%VR= (4.03 / 230) x 100%= 1.75%


Transformer no.9

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
37 1 3 5 0 1
38 0 2 8 0 1
39 0 1 6 0 1
40 0 1 0 0 1
41 1 4 1 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
37 14.39 12.09 2.915 0 0.15 29.519
38 0 8.06 4.664 0 0.15 12.689
39 0 4.03 3.499 0 0.15 7.674
40 0 4.03 0 0 0.15 4.175
41 14.39 16.12 0.583 0 0.15 31.238
Total 85.475

Maximum Demand Load:


Assuming:
100 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 85.475 / 100 ) x 100% = 85.475%

1.) IFL = 100 / 20 = 5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 5 =7.5 A.

3.) The short circuit KVA in the primary:


KVASC = 100 / 0.03 = 3,333.35 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 100 / (0.03 x 20) = 166.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 166.67 = 266.67 A.

Therfore:
The rating of the distribution transformer shall be 100 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 85.475 KVA, it shall be
protected by 10 Amps Fuse Link. The rating of the fuse cutout shall be 10 Amps. The
maximum fuse setting is 7.5 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.9 is located at pole no.39

Upper side
Pole number Kva / Pole No. of Span Kva-span
37 31.238 2 62.476
38 4.175 1 4.275
66.651

Lower side
Pole number Kva / Pole No. of Span Kva-span
40 12.869 1 12.864
41 29.519 2 59.04
71.909

%Kva= ( 66.651 / 71.909) x 100% = 92.69%

Therefore, Transformer no.9 should be installed at pole no. 39

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=100,000 / 230 = 434.78 A.

use: 1-250,000 CM Hard Drawn Copper Conductor per line

Ra= 0.257 Xa= 0.487

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.487 + 0.035= 0.522
Xc / Ra= 0.552 / 0.257= 2.03

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 12,415 / 230= 53.98 A.

Vdc= (24 x 53.98 x 100) / 250,000= 0.518 V.

Vac= D.F. x Vdc = 2.1 x 0.518= 1.1 V.

Ispan-2 = 18,385 / 230= 79.93 A.

Vdc= (24 x 79.93 x 100) / 250,000= 0.767 V.

Vac= D.F. x Vdc = 2.1 x 0.767= 1.61 V.


Ispan-3 = 6,636 / 230= 28.85 A.

Vdc= (24 x 28.85 x 100) / 250,000= 0.277 V.


Vac= D.F. x Vdc = 2.1 x 0.277= 0.58 V.

Vac TOTAL = 1.1 + 1.61 + 0.58= 3.29 V.

%VR= (3.29 / 230) x 100%= 1.43%

Right side

Ispan-1 = 8.917 / 230= 38.77 A.

Vdc= (24 x 38.77 x 100) / 250,000= 0.372 V.

Vac= D.F. x Vdc = 2.1 x 0.372= 0.78 V.

Ispan-2 = 14,747 / 230= 64.14 A.

Vdc= (24 x 64.12 x 100) / 250,000= 0.77 V.

Vac= D.F. x Vdc = 2.1 x 0.77= 1.61 V.

Ispan-3 = 15,279 / 230= 66.43 A.

Vdc= (24 x 66.43 x 100) / 250,000= 0.64 V.

Vac= D.F. x Vdc = 2.1 x 0.64= 1.34 V.

Vac TOTAL = 0.78 + 1.61 + 1.37= 3.73 V.

%VR= (3.73 / 230) x 100%= 1.62%


Transformer no.10

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
42 0 2 7 0 1
43 1 0 7 0 1
44 0 1 4 0 1
45 0 2 0 0 1
46 0 2 1 0 1
47 0 2 11 0 1
48 0 3 5 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
42 0 8.06 4.081 0 0.15 12.415
43 14.03 0 4.081 0 0.15 18.385
44 0 4.03 2.332 0 0.15 6.636
45 0 8.06 0 0 0.15 8.334
46 0 8.06 0.583 0 0.15 8.917
47 0 8.06 6.413 0 0.15 14.747
48 0 12.09 2.915 0 0.15 15.279
Total 84.713

Maximum Demand Load:


Assuming:
100 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 84.713 / 100 ) x 100% = 84.713%

1.) IFL = 100 / 20 = 5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 5 =7.5 A.

3.) The short circuit KVA in the primary:


KVASC = 100 / 0.03 = 3,333.35 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 100 / (0.03 x 20) = 166.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 166.67 = 266.67 A.

Therfore:
The rating of the distribution transformer shall be 100 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 85.475 KVA, it shall be
protected by 10 Amps Fuse Link. The rating of the fuse cutout shall be 10 Amps. The
maximum fuse setting is 7.5 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.10 is located at pole no.45

Left side
Pole number Kva / Pole No. of Span Kva-span
42 12.415 3 37.245
43 18.385 2 36.77
44 6.636 1 6.636
80.651

Right side
Pole number Kva / Pole No. of Span Kva-span
42 41.02 1 41.02
43 26.662 2 53.326
94.344

%Kva= ( 81.69 / 94.344) x 100% = 87%

Therefore, Transformer no.1 should be installed at pole no. 3

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=150,000 / 230 = 652.17 A.

use: 2-167,806 CM Hard Drawn Copper Conductor per line

Ra= 0.382 Xa= 0.518

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.518 + 0.035= 0.553
Xc / Ra= 0.553 / 0.382= 1.447
By using 80% power factor, the Drop Factor is 1.7

2.) Calculation of %VR:

Upper side

Ispan-1 = 24,932 / 230= 108.4 A.

Vdc= (24 x 108.4 x 100) / 167,806= 1.55 V.

Vac= D.F. x Vdc = 1.7 x 1.55= 2.64 V.

Ispan-2 = 31,826 / 230= 138.35 A.

Vdc= (24 x 138.35 x 100) / 167,806= 1.979 V.

Vac= D.F. x Vdc = 1.7 x 1.979= 3.67 V.

Vac TOTAL = 2.64 + 3.67= 6.31 V.

%VR= (6.31 / 230) x 100%= 2.74%


Lower side

Ispan-1 = 41,020 / 230= 178.36 A.

Vdc= (24 x 178.36 x 100) / 167,806= 2.55 V.

Vac= D.F. x Vdc = 1.7 x 2.55= 4.34 V.

Ispan-2 = 26,660 / 230= 115.65 A.

Vdc= (24 x 114.65 x 100) / 167,806= 1.65 V.

Vac= D.F. x Vdc = 1.7 x 1.65= 2.8 V.

Vac TOTAL = 4.34 + 2.8= 7.1 V.

%VR= (7.1 / 230) x 100%= 3%


Transformer no.11

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
49 0 3 1 0 1
50 0 1 0 0 1
51 0 0 0 0 1
52 0 0 0 0 1
53 0 3 5 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
49 0 12.09 0.583 0 0.15 12.823
50 0 4.03 0 0 0.15 4.18
51 0 0 0 0 0.15 0.15
52 0 0 0 0 0.15 0.15
53 0 24.18 2.915 0 0.15 15.155
Total 34.453

Maximum Demand Load:


Assuming:
37.5 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 34.453 / 37.5 ) x 100% = 86.53%

1.) IFL = 37.5 / 20 = 1.875 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 1.875 =2.8 A.

3.) The short circuit KVA in the primary:


KVASC = 37.5 / 0.03 = 1250 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 37.5 / (0.03 x 20) = 62.5 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 62.5 = 100 A.

Therfore:
The rating of the distribution transformer shall be 37.5 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 32.453 KVA, it shall be
protected by 3 Amps Fuse Link. The rating of the fuse cutout shall be 3 Amps. The maximum
fuse setting is 2.81 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.11 is located at pole no.51

Left side
Pole number Kva / Pole No. of Span Kva-span
49 12.823 2 25.646
59 4.18 1 4.18
29.826

Right side
Pole number Kva / Pole No. of Span Kva-span
52 0.15 1 0.15
53 15.155 2 30.31
30.46

%Kva= ( 29.826 / 30.46) x 100% = 97.92%

Therefore, Transformer no.1 should be installed at pole no. 3

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I=37,500 / 230 = 652.17 A.

use: 1- 66,371 CM Hard Drawn Copper Conductor per line

Ra= 0.59 Xa= 0.571

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.571 + 0.035= 0.606
Xc / Ra= 0.606 / 0.59= 1.027

By using 80% power factor, the Drop Factor is 1.45

2.) Calculation of %VR:

Left side

Ispan-1 = 12,823 / 230= 55.75 A.

Vdc= (24 x 55.75 x 100) / 66,371= 2.015 V.

Vac= D.F. x Vdc = 1.45 x 2.015= 2.923 V.

Ispan-2 = 4,180 / 230= 18.17 A.

Vdc= (24 x 18.17 x 100) / 66,371= 0.657 V.

Vac= D.F. x Vdc = 1.45 x 0.657= 0.953 V.

Vac TOTAL = 2.923 + 0.953= 3.88 V.

%VR= (3.88 / 230) x 100%= 1.685%


Right side

Ispan-1 = 150 / 230= 0.652 A.

Vdc= (24 x 0.652 x 100) / 66,371= 0.022 V.

Vac= D.F. x Vdc = 1.45 x 0.022= 0.032 V.

Ispan-2 = 15,155 / 230= 65.891 A.

Vdc= (24 x 65.891 x 100) / 66,371= 2.382 V.

Vac= D.F. x Vdc = 1.45 x 2.382= 3.46 V.

Vac TOTAL = 0.032 + 3.46= 3.487 V.

%VR= ( 3.487 / 230) x 100%= 1.516%


Transformer no.12

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
55 0 0 6 0 1
56 0 0 7 0 1
57 0 0 6 0 1
58 0 0 10 0 1
59 0 0 5 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
55 0 0 3.498 0 0.15 3.648
56 0 0 4.081 0 0.15 4.231
57 0 0 3.498 0 0.15 3.648
58 0 0 5.83 0 0.15 5.98
59 0 0 2.915 0 0.15 3.065
Total 20.572

Maximum Demand Load:


Assuming:
25 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 20.572 / 25) x 100% = 82.288%

1.) IFL = 25 / 20 = 1.25 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 1.25 =1.875 A.

3.) The short circuit KVA in the primary:


KVASC = 25 / 0.03 = 833.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 25 / (0.03 x 20) = 41.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 41.67 = 66.67 A.

Therfore:
The rating of the distribution transformer shall be 25 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 20.572 KVA, it shall be
protected by 3 Amps Fuse Link. The rating of the fuse cutout shall be 3 Amps. The maximum
fuse setting is 1.875 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.12 is located at pole no.57

Left side
Pole number Kva / Pole No. of Span Kva-span
55 3.648 2 7.296
56 4.231 1 4.231
11.527

Right side
Pole number Kva / Pole No. of Span Kva-span
58 5.98 1 5.98
59 3.065 2 6.13
12.11

%Kva= ( 11.527 / 12.11) x 100% = 95.19%

Therefore, Transformer no.12 should be installed at pole no.57

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 25,000 / 230 = 108.696 A.

use: 1- 66,371 CM Hard Drawn Copper Conductor per line

Ra= 1.89 Xa= 0.622

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.622 + 0.035= 0.657
Xc / Ra= 0.657 / 1.89= 0.348

By using 80% power factor, the Drop Factor is 1.04

2.) Calculation of %VR:

Left side

Ispan-1 = 3,698 / 230= 15.86 A.

Vdc= (24 x 15.86 x 100) / 33,102= 1.149 V.

Vac= D.F. x Vdc = 1.04 x 1.149= 1.196 V.

Ispan-2 = 4,231 / 230= 18.396 A.

Vdc= (24 x 18.396 x 100) / 33,102= 1.334 V.

Vac= D.F. x Vdc = 1.04 x 1.334= 1.387 V.

Vac TOTAL = 1.196 + 1.387= 2.58 V.

%VR= (2.58 / 230) x 100%= 1.123%


Right side

Ispan-1 = 5,980 / 230= 26 A.

Vdc= (24 x 26 x 100) / 33,102= 1.886 V.

Vac= D.F. x Vdc = 1.04 x 1.886= 1.96 V.

Ispan-2 = 3,065 / 230= 13.326 A.

Vdc= (24 x 13.326 x 100) / 33,102= 0.966 V.

Vac= D.F. x Vdc = 1.04 x 0.966= 1 V.

Vac TOTAL = 1.96 + 1= 2.96 V.

%VR= ( 2.96 / 230) x 100%= 1.287%


Transformer no.13

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
60 0 0 5 0 1
61 0 0 0 0 1
62 0 0 3 0 1
63 0 0 1 0 1
64 0 0 4 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
60 0 0 2.915 0 0.15 3.005
61 0 0 0 0 0.15 0.15
62 0 0 1.749 0 0.15 1.899
63 0 0 0.583 0 0.15 0.733
64 0 0 2.332 0 0.15 2.482
Total 8.329

Maximum Demand Load:


Assuming:
10 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 8.329 / 10) x 100% = 83.29%

1.) IFL = 10 / 20 = 0.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 0.5 = 0.75 A.

3.) The short circuit KVA in the primary:


KVASC = 10 / 0.03 = 333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 10 / (0.03 x 20) = 16.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 16.67 = 26.67 A.

Therfore:
The rating of the distribution transformer shall be 10 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 8.329 KVA, it shall be
protected by 1 Amps Fuse Link. The rating of the fuse cutout shall be 1 Amps. The maximum
fuse setting is 0.75 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.13 is located at pole no.62

Lower side
Pole number Kva / Pole No. of Span Kva-span
64 2.482 2 4.964
63 0.733 1 0.733
5.697

Upper side
Pole number Kva / Pole No. of Span Kva-span
61 0.15 1 0.15
60 3.065 2 6.13
6.28

%Kva= ( 5.697 / 6.28) x 100% = 90.72%

Therefore, Transformer no.13 should be installed at pole no.62

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 10,000 / 230 = 43.48 A.

use: 1- 26,251 CM Hard Drawn Copper Conductor per line

Ra= 2.84 Xa= 0.637

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.637 + 0.035= 0.672
Xc / Ra= 0.672 / 2.39= 0.281

By using 80% power factor, the Drop Factor is 0.99

2.) Calculation of %VR:

Lower side

Ispan-1 = 3,065 / 230= 13.326 A.

Vdc= (24 x 13.326 x 100) / 26,251= 1.22 V.

Vac= D.F. x Vdc = 0.99 x 1.22= 1.21 V.

Ispan-2 = 150 / 230= 10.65 A.

Vdc= (24 x 0.65 x 100) / 26,251= 0.059 V.

Vac= D.F. x Vdc = 0.99 x 0.059= 0.06 V.

Vac TOTAL = 1.21 + 0.06= 1.268 V.

%VR= (1.268 / 230) x 100%= 0.55%


Upper side

Ispan-1 = 733 / 230= 3.187 A.

Vdc= (24 x 3.187 x 100) / 26,251= 0.291 V.

Vac= D.F. x Vdc = 0.99 x 0.291= 0.29 V.

Ispan-2 = 2,482 / 230= 10.79 A.

Vdc= (24 x 10.79 x 100) / 26,251= 0.979 V.

Vac= D.F. x Vdc = 0.99 x 0.979= 0.789 V.

Vac TOTAL = 0.29 + 0.789= 1.09 V.

%VR= ( 1.09 / 230) x 100%= 0.05%


Transformer no.14

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
76 0 4 0 0 1
77 0 5 0 0 1
78 0 11 0 0 1
79 0 4 6 0 1
80 0 4 4 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
76 0 16.12 0 0 0.15 16.27
77 0 20.15 0 0 0.15 20.3
78 0 44.33 0 0 0.15 44.48
79 0 16.12 3.498 0 0.15 19.768
80 0 16.12 2.332 0 0.15 18.602
Total 119.42

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 119.42 / 150) x 100% = 79.6%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.

Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 119.42 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.14 is located at pole no.78

Left side
Pole number Kva / Pole No. of Span Kva-span
76 16.27 2 32.54
77 20.3 1 20.3
52.84

Right side
Pole number Kva / Pole No. of Span Kva-span
79 19.762 1 19.768
80 18.602 2 37.204
56.972

%Kva= ( 52.84 / 56.972) x 100% = 92.75%

Therefore, Transformer no.14 should be installed at pole no.78

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 1- 500,000 CM Hard Drawn Copper Conductor per line

Ra= 0.130 Xa= 0.443

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.443 + 0.035= 0.478
Xc / Ra= 0.478 / 0.130= 3.68

By using 80% power factor, the Drop Factor is 3.23

2.) Calculation of %VR:

Left side

Ispan-1 = 16,270 / 230= 70.74 A.

Vdc= (24 x 70.74 x 100) / 500,000= 0.399 V.

Vac= D.F. x Vdc = 3.23 x 0.399= 1.09 V.

Ispan-2 = 20,300 / 230= 88.26 A.

Vdc= (24 x 88.26 x 100) / 500,000= 0.424 V.

Vac= D.F. x Vdc = 3.23 x 0.424= 1.37 V.

Vac TOTAL = 1.09 + 1.37= 2.458 V.

%VR= (2.458 / 230) x 100%= 1.068%


Upper side

Ispan-1 = 19,768 / 230= 85.95 A.

Vdc= (24 x 85.95 x 100) / 500,000= 0.413 V.

Vac= D.F. x Vdc = 3.23 x 0.413= 1.33 V.

Ispan-2 = 18,602 / 230= 80.88 A.

Vdc= (24 x 80.88 x 100) / 500,000= 0.388 V.

Vac= D.F. x Vdc = 3.23 x 0.388= 1.254 V.

Vac TOTAL = 1.33 + 1.254= 2.58 V.

%VR= ( 2.58 / 230) x 100%= 1.12%


Transformer no.15

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
84 0 4 2 0 1
85 0 5 1 0 1
86 0 6 1 0 1
87 0 0 0 0 1
88 0 4 0 0 1
89 0 6 0 0 1
90 0 5 1 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
84 0 16.12 1.166 0 0.15 17.436
85 0 20.15 0.583 0 0.15 20.883
86 0 24.18 0.583 0 0.15 44.913
87 0 0 0 0 0.15 0.15
88 0 16.12 0 0 0.15 16.27
89 0 24.18 0 0 0.15 24.33
90 0 25.15 0.583 0 0.15 20.883
Total 124.282

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 124.282 / 150) x 100% = 82.85%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.
Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 124.282 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.15 is located at pole no.87

Left side
Pole number Kva / Pole No. of Span Kva-span
84 17.436 3 52.308
85 20.883 2 41.766
86 24.913 1 24.913
118.987

Right side
Pole number Kva / Pole No. of Span Kva-span
88 16.27 1 16.27
89 24.33 2 48.66
90 220.883 3 62.649
127.579

%Kva= ( 118.987 / 127.579) x 100% = 93.26%

Therefore, Transformer no.15 should be installed at pole no.87

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 1- 500,000 CM Hard Drawn Copper Conductor per line

Ra= 0.130 Xa= 0.443

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.443 + 0.035= 0.478
Xc / Ra= 0.478 / 0.130= 3.68

By using 80% power factor, the Drop Factor is 3.23


2.) Calculation of %VR:

Left side

Ispan-1 = 17,439 / 230= 75.82 A.

Vdc= (24 x 75.82 x 100) / 500,000= 0.36 V.

Vac= D.F. x Vdc = 3.23 x 0.36= 1.16 V.

Ispan-2 = 20.883 / 230= 90.79 A.

Vdc= (24 x 90.79 x 100) / 500,000= 0.436 V.

Vac= D.F. x Vdc = 3.23 x 0.436= 1.41 V.

Ispan-3 = 24,193 / 230= 105.17 A.

Vdc= (24 x 105.17 x 100) / 500,000= 0.505 V.

Vac= D.F. x Vdc = 3.23 x 0.505= 1.63 V.

Vac TOTAL = 1.16 + 1.41 + 1.63= 4.2 V.

%VR= (4.2 / 230) x 100%= 1.83%

Upper side

Ispan-1 = 16,270 / 230= 70.19 A.

Vdc= (24 x 70.19 x 100) / 500,000= 0.339 V.

Vac= D.F. x Vdc = 3.23 x 0.339= 1.09 V.

Ispan-2 = 24,320 / 230= 105.78 A.

Vdc= (24 x 105.78 x 100) / 500,000= 0.508 V.

Vac= D.F. x Vdc = 3.23 x 0.508= 1.64 V.

Ispan-3 = 20,883 / 230= 90.97 A.

Vdc= (24 x 90.97 x 100) / 500,000= 0.436 V.

Vac= D.F. x Vdc = 3.23 x 0.436= 1.41 V.

Vac TOTAL = 1.09 + 1.64 + 1.41= 4.14 V.

%VR= ( 4.14 / 230) x 100%= 1.8%


Transformer no.16

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
94 0 6 0 0 1
95 0 5 0 0 1
96 0 0 0 0 1
97 0 3 0 0 1
98 0 6 1 0 1
99 0 6 3 0 1
100 0 2 9 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
94 0 24.18 0 0 0.15 24.33
95 0 20.15 0 0 0.15 20.3
96 0 0 0 0 0.15 0.15
97 0 12.09 0 0 0.15 12.4
98 0 24.18 0.583 0 0.15 24.913
99 0 24.18 1.749 0 0.15 26.079
100 0 8.06 5.247 0 0.15 13.457
Total 121.469

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 121.469 / 150) x 100% = 80.979%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.
Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 121.469 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.16 is located at pole no.97

Left side
Pole number Kva / Pole No. of Span Kva-span
94 24.33 3 72.99
95 20.3 2 40.6
96 0.15 1 0.15
113.74

Right side
Pole number Kva / Pole No. of Span Kva-span
98 24.193 1 24.193
99 26.079 2 52.158
100 13.417 3 40.251
116.602

%Kva= ( 113.74 / 116.602) x 100% = 97.55%

Therefore, Transformer no.16 should be installed at pole no.97

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 1- 500,000 CM Hard Drawn Copper Conductor per line

Ra= 0.130 Xa= 0.443

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.443 + 0.035= 0.478
Xc / Ra= 0.478 / 0.130= 3.68

By using 80% power factor, the Drop Factor is 3.23


2.) Calculation of %VR:

Left side

Ispan-1 = 24,330 / 230= 105.78 A.

Vdc= (24 x 105.78 x 100) / 500,000= 0.51 V.

Vac= D.F. x Vdc = 3.23 x 0.51= 1.63 V.

Ispan-2 = 20,300 / 230= 88.26 A.

Vdc= (24 x 88.26 x 100) / 500,000= 0.42 V.

Vac= D.F. x Vdc = 3.23 x 0.42= 1.37 V.

Ispan-3 = 150 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 500,000= 0.00132 V.

Vac= D.F. x Vdc = 3.23 x 0.00132= 0.01 V.

Vac TOTAL = 1.63 + 1.37 + 0.01= 3.01 V.

%VR= (3.01 / 230) x 100%= 1.31%

Right side

Ispan-1 = 24,913 / 230= 108.32 A.

Vdc= (24 x 108.32 x 100) / 500,000= 0.518 V.

Vac= D.F. x Vdc = 3.23 x 0.518= 1.68 V.

Ispan-2 = 26,079 / 230= 113.39 A.

Vdc= (24 x 113.39 x 100) / 500,000= 0.54 V.

Vac= D.F. x Vdc = 3.23 x 0.54= 1.76 V.

Ispan-3 = 13,457 / 230= 50.51 A.

Vdc= (24 x 50.51 x 100) / 500,000= 0.28 V.

Vac= D.F. x Vdc = 3.23 x 0.28= 0.90 V.

Vac TOTAL = 1.68 + 1.76 + 0.90= 4.22 V.

%VR= ( 4.22 / 230) x 100%= 1.84%


Transformer no.17

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
110 0 6 2 0 1
111 0 5 0 0 1
112 0 2 4 0 1
113 0 3 0 0 1
114 0 7 2 0 1
115 0 5 8 0 1
116 0 4 4 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
110 0 24.18 1.166 0 0.15 25.469
111 0 20.15 0 0 0.15 20.3
112 0 8.06 2.332 0 0.15 10.542
113 0 12.09 0 0 0.15 12.24
114 0 28.21 1.166 0 0.15 29.526
115 0 20.15 4.664 0 0.15 24.964
116 0 16.12 2.332 0 0.15 18.602
Total 141.643

Maximum Demand Load:


Assuming:
167 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 141.643 / 167) x 100% = 84.82%

1.) IFL = 167 / 20 = 8.35 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 8.35 = 12.53 A.

3.) The short circuit KVA in the primary:


KVASC = 167 / 0.03 = 5566.67 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 167 / (0.03 x 20) = 278.83 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 278.83 = 445.33 A.
Therfore:
The rating of the distribution transformer shall be 167 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 141.643 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 12.53 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.17 is located at pole no.113

Right side
Pole number Kva / Pole No. of Span Kva-span
110 24.18 3 72.54
111 20.15 2 40.3
112 8.06 1 8.06
120.9

Left side
Pole number Kva / Pole No. of Span Kva-span
114 28.21 1 28.21
115 20.15 2 40.3
116 16.12 3 48.36
116.87

%Kva= ( 120.9 / 116.87) x 100% = 96.7%

Therefore, Transformer no.17 should be installed at pole no.113

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 167,000 / 230 = 726 A.

use: 2- 167,806 CM Hard Drawn Copper Conductor per line

Ra= 0.382 Xa= 0.518

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.518 + 0.035= 0.553
Xc / Ra= 0.553 / 0.382= 1.447

By using 80% power factor, the Drop Factor is 1.7


2.) Calculation of %VR:

Left side

Ispan-1 = 25,469 / 230= 110.73 A.

Vdc= (24 x 110.73 x 100) / 167,806= 1.58 V.

Vac= D.F. x Vdc = 1.7 x 1.58= 2.69 V.

Ispan-2 = 20,300 / 230= 88.26 A.

Vdc= (24 x 88.26 x 100) / 167,806= 1.26 V.

Vac= D.F. x Vdc = 1.7 x 1.26= 2.15 V.

Ispan-3 = 8,060 / 230= 35.04 A.

Vdc= (24 x 35.04 x 100) / 167,806= 0.501 V.

Vac= D.F. x Vdc = 1.7 x 0.501= 0.85 V.

Vac TOTAL = 2.69 + 2.15 + 0.85= 5.69 V.

%VR= (5.69 / 230) x 100%= 2.47%

Right side

Ispan-1 = 29,526 / 230= 128.37 A.

Vdc= (24 x 128.37 x 100) / 167,806= 1.84 V.

Vac= D.F. x Vdc = 1.7 x 1.84= 3.12 V.

Ispan-2 = 24,964 / 230= 108.54 A.

Vdc= (24 x 108.54 x 100) / 167,806= 1.55 V.

Vac= D.F. x Vdc = 1.7 x 1.55= 2.64 V.

Ispan-3 = 18,602 / 230= 80.88 A.

Vdc= (24 x 80.88 x 100) / 167,806= 0.647 V.

Vac= D.F. x Vdc = 1.7 x 0.647= 6.86 V.

Vac TOTAL = 3.12 + 2.64 + 1.10= 6.86 V.

%VR= ( 6.86 / 230) x 100%= 2.98%


Transformer no.18

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
140 0 7 0 0 1
141 0 4 0 0 1
142 0 3 0 0 1
143 0 5 0 0 1
144 0 0 0 0 1
145 0 0 0 0 1
146 0 11 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
140 0 28.21 0 0 0.15 28.36
141 0 16.12 0 0 0.15 16.27
142 0 12.09 0 0 0.15 12.24
143 0 20.15 0 0 0.15 20.3
144 0 0 0 0 0.15 0.15
145 0 0 0 0 0.15 0.15
146 0 44.33 0 0 0.15 44.48
Total 121.95

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 121.95 / 150) x 100% = 81.3%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.
Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 121.95 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.18 is located at pole no.143

Left side
Pole number Kva / Pole No. of Span Kva-span
140 28.36 3 85.08
141 16.27 2 32.27
142 12.24 1 12.24
129.59

Right side
Pole number Kva / Pole No. of Span Kva-span
144 0.15 1 0.15
145 0.15 2 0.3
146 44.48 3 133.44
133.89

%Kva= ( 129.59 / 133.89) x 100% = 96.7%

Therefore, Transformer no.18 should be installed at pole no.143

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 2- 167,806 CM Hard Drawn Copper Conductor per line

Ra= 0.382 Xa= 0.518

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.518 + 0.035= 0.553
Xc / Ra= 0.553 / 0.382= 1.447

By using 80% power factor, the Drop Factor is 1.7


2.) Calculation of %VR:

Left side

Ispan-1 = 28,360 / 230= 122.87 A.

Vdc= (24 x 122.87 x 100) / 167,806= 1.76 V.

Vac= D.F. x Vdc = 1.7 x 1.76= 2.98 V.

Ispan-2 = 16,270 / 230= 70.74 A.

Vdc= (24 x 70.74 x 100) / 167,806= 1.01 V.

Vac= D.F. x Vdc = 1.7 x 1.01= 1.72 V.

Ispan-3 = 12,240 / 230= 53.22 A.

Vdc= (24 x 53.22 x 100) / 167,806= 0.76 V.

Vac= D.F. x Vdc = 1.7 x 0.76= 1.29 V.

Vac TOTAL = 1.76 + 1.72 + 1.29= 4.77 V.

%VR= (4.77 / 230) x 100%= 2.07%

Right side

Ispan-1 = 0.15 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 167,806= 0.092 V.

Vac= D.F. x Vdc = 1.7 x 0.092= 0.16 V.

Ispan-2 = 0.15 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 167,806= 0.092 V.

Vac= D.F. x Vdc = 1.7 x 0.092= 0.16V.

Ispan-3 = 44,480 / 230= 193.39 A.

Vdc= (24 x 193.39 x 100) / 167,806= 2.77 V.

Vac= D.F. x Vdc = 1.77 x 2.77= 4.71 V.

Vac TOTAL = 0.16 + 0.16 + 4.71= 5.03V.

%VR= ( 5.03 / 230) x 100%= 2.18%


Transformer no.19

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
154 0 11 0 0 1
155 0 3 3 0 1
156 0 0 0 0 1
157 0 7 0 0 1
158 0 10 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
154 0 44.33 0 0 0.15 44.48
155 0 12.09 1.749 0 0.15 13.98
156 0 0 0 0 0.15 0.15
157 0 28.21 0 0 0.15 28.36
158 0 40.3 0 0 0.15 40.45
Total 127.429

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 127.429 / 150) x 100% = 84.95%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.

Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 127.429 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.19 is located at pole no.156

Left side
Pole number Kva / Pole No. of Span Kva-span
154 44.48 2 88.96
155 13.98 1 13.98
102.949

Right side
Pole number Kva / Pole No. of Span Kva-span
157 28.36 1 28.36
158 40.45 2 80.9
109.26

%Kva= ( 102.95 / 109.26) x 100% = 94.22%

Therefore, Transformer no.19 should be installed at pole no.156

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 2- 167,806 CM Hard Drawn Copper Conductor per line

Ra= 0.382 Xa= 0.518

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.518 + 0.035= 0.553
Xc / Ra= 0.553 / 0.382= 1.447

By using 80% power factor, the Drop Factor is 1.7

2.) Calculation of %VR:

Left side

Ispan-1 = 44,480 / 230= 193.39 A.

Vdc= (24 x 193.39 x 100) / 167,806= 2.77 V.

Vac= D.F. x Vdc = 1.7 x 2.77= 4.7 V.

Ispan-2 = 13,989 / 230= 60.82 A.

Vdc= (24 x 60.82 x 100) / 167,806= 0.87 V.

Vac= D.F. x Vdc = 1.7 x 0.87= 1.479V.

Vac TOTAL = 4.7 + 1.479= 6.179 V.

%VR= (6.179 / 230) x 100%= 2.69%


Upper side

Ispan-1 = 28,360 / 230= 123.30 A.

Vdc= (24 x 128.30 x 100) / 167,806= 1.49 V.

Vac= D.F. x Vdc = 1.7 x 1.49= 2.55 V.

Ispan-2 = 40,450 / 230= 175.87 A.

Vdc= (24 x 175.87 x 100) / 167,806= 2.52 V.

Vac= D.F. x Vdc = 1.7 x 2.52= 4.28 V.

Vac TOTAL = 2.55 + 4.28= 6.83 V.

%VR= ( 6.83 / 230) x 100%= 2.9%


Transformer no.20

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
160 0 9 0 0 1
161 0 12 6 0 1
162 0 9 4 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
160 0 36.27 0 0 0.15 36.42
161 0 48.36 3.498 0 0.15 52.008
162 0 36.27 2.332 0 0.15 38.752
Total 127.18

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 127.18 / 150) x 100% = 84.79%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.

Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 127.18 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.20 is located at pole no.161

Left side
Pole number Kva / Pole No. of Span Kva-span
160 36.42 1 36.42
36.42

Right side
Pole number Kva / Pole No. of Span Kva-span
162 38.753 1 38.753
38.753

%Kva= ( 36.42 / 38.75) x 100% = 93.90%

Therefore, Transformer no.20 should be installed at pole no.161

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 2- 167,806 CM Hard Drawn Copper Conductor per line

Ra= 0.382 Xa= 0.518

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.518 + 0.035= 0.553
Xc / Ra= 0.553 / 0.382= 1.447

By using 80% power factor, the Drop Factor is 1.7

2.) Calculation of %VR:

Left side

Ispan-1 = 36,270 / 230= 157.69 A.

Vdc= (24 x 157.69 x 100) / 167,806= 2.26 V.

Vac= D.F. x Vdc = 1.7 x 2.26= 3.83 V.

Vac TOTAL = 3.83= 3.83 V.

%VR= (3.83 / 230) x 100%= 1.67%


Upper side

Ispan-1 = 38,752 / 230= 168.49 A.

Vdc= (24 x 168.49 x 100) / 167,806= 2.41 V.

Vac= D.F. x Vdc = 1.7 x 2.41= 4.09 V.

Vac TOTAL = 4.09= 4.09 V.

%VR= ( 4.09 / 230) x 100%= 1.78%


Transformer no.21

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
163 0 11 0 0 1
164 0 10 0 0 1
165 0 8 0 0 1
166 0 10 0 0 1
167 0 12 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
163 0 44.33 0 0 0.15 44.48
164 0 40.3 0 0 0.15 40.45
165 0 32.24 0 0 0.15 32.39
166 0 40.3 0 0 0.15 40.45
167 0 48.36 0 0 0.15 48.51
Total 206.28

Maximum Demand Load:


Assuming:
250 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 206.28 / 250) x 100% = 82.512%

1.) IFL = 250 / 20 = 12.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 12.5 = 18.75 A.

3.) The short circuit KVA in the primary:


KVASC = 250 / 0.03 = 8333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 250 / (0.03 x 20) = 416.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 416.67 = 666.67 A.

Therfore:
The rating of the distribution transformer shall be 250 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 206.28 KVA, it shall be
protected by 20 Amps Fuse Link. The rating of the fuse cutout shall be 20 Amps. The
maximum fuse setting is 18.75 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.21 is located at pole no.165

Left side
Pole number Kva / Pole No. of Span Kva-span
163 44.48 2 88.96
164 40.45 1 40.45
129.41

Right side
Pole number Kva / Pole No. of Span Kva-span
166 40.45 1 40.45
167 48.51 2 97.02
137.47

%Kva= ( 129.41 / 137.47) x 100% = 94.14%

Therefore, Transformer no.21 should be installed at pole no.94.14

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 250,000 / 230 = 1086.96 A.

use: 2- 400,000 CM Hard Drawn Copper Conductor per line

Ra= 0.162 Xa= 0.458

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.458 + 0.035= 0.493
Xc / Ra= 0.493 / 0.162= 3.04

By using 80% power factor, the Drop Factor is 2.8

2.) Calculation of %VR:

Left side

Ispan-1 = 44,480 / 230= 193.39 A.

Vdc= (24 x 193.39 x 100) / 400,000= 1.16 V.

Vac= D.F. x Vdc = 2.8 x 1.16= 3.25 V.

Ispan-2 = 40,450 / 230= 175.87 A.

Vdc= (24 x 175.87 x 100) / 400,000= 1.06 V.

Vac= D.F. x Vdc = 2.8 x 1.06= 2.95 V.

Vac TOTAL = 3.25 + 2.95= 6.02 V.

%VR= (6.02 / 230) x 100%= 2.69%


Upper side

Ispan-1 = 40,450 / 230= 175.87 A.

Vdc= (24 x 175.87 x 100) / 400,000= 1.06 V.

Vac= D.F. x Vdc = 2.8 x 1.06= 2.97 V.

Ispan-2 = 48,510 / 230= 210.91 A.

Vdc= (24 x 210.91 x 100) / 400,000= 1.06 V.

Vac= D.F. x Vdc = 2.8 x 1.06= 2.95 V.

Vac TOTAL = 3.95 + 2.95= 6.02 V.

%VR= ( 6.02 / 230) x 100%= 2.69%


Transformer no.22

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
168 0 12 0 0 1
169 0 9 0 0 1
170 0 5 0 0 1
171 0 12 0 0 1
172 0 6 0 0 1
173 0 9 0 0 1
174 0 13 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
168 0 48.86 0 0 0.15 48.51
169 0 36.27 0 0 0.15 36.42
170 0 20.15 0 0 0.15 20.3
171 0 48.36 0 0 0.15 48.51
172 0 24.18 0 0 0.15 24.33
173 0 36.27 0 0 0.15 36.42
174 0 52.39 0 0 0.15 5.54
Total 267.08

Maximum Demand Load:


Assuming:
333 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 267.08 / 333) x 100% = 80.2%

1.) IFL = 333 / 20 = 16.65 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 16.65 = 24.975 A.

3.) The short circuit KVA in the primary:


KVASC = 333 / 0.03 = 11,100 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 333 / (0.03 x 20) = 555 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 555 = 888 A.
Therfore:
The rating of the distribution transformer shall be 333 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 267.08 KVA, it shall be
protected by 25 Amps Fuse Link. The rating of the fuse cutout shall be 25 Amps. The
maximum fuse setting is 24.975 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.22 is located at pole no.171

Left side
Pole number Kva / Pole No. of Span Kva-span
168 48.51 3 145.53
169 36.42 2 72.84
170 20.3 1 20.3
238.67

Right side
Pole number Kva / Pole No. of Span Kva-span
172 24.33 1 24.33
173 36.42 2 72.84
174 52.54 3 157.62
254.79

%Kva= ( 238.67 / 254.79) x 100% = 93.57%

Therefore, Transformer no.22 should be installed at pole no.171

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 333,000 / 230 = 1447.83 A.

use: 3-300,000 CM Hard Drawn Copper Conductor per line

Ra= 0.250 Xa= 0.476

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.476 + 0.035= 0.511
Xc / Ra= 0.511 / 0.250= 2.044

By using 80% power factor, the Drop Factor is 2.1


2.) Calculation of %VR:

Left side

Ispan-1 = 48,510 / 230= 210.19 A.

Vdc= (24 x 210.19 x 100) / 300,000= 1.51 V.

Vac= D.F. x Vdc = 2.1 x 1.51= 3.171 V.

Ispan-2 = 36,420 / 230= 158.35 A.

Vdc= (24 x 158.35 x 100) / 300,000= 1.14 V.

Vac= D.F. x Vdc = 2.1 x 1.14= 2.39 V.

Ispan-3 = 20,300 / 230= 88.26 A.

Vdc= (24 x 88.26 x 100) / 300,000= 0.635 V.

Vac= D.F. x Vdc = 2.1 x 0.635= 1.33 V.

Vac TOTAL = 3.171 + 2.39 + 1.33= 6.89 V.

%VR= (6.89 / 230) x 100%= 2.9%

Right side

Ispan-1 = 24,330 / 230= 105.78 A.

Vdc= (24 x 105.78 x 100) / 300,000= 0.71 V.

Vac= D.F. x Vdc = 2.1 x 0.71= 1.5 V.

Ispan-2 = 36,420 / 230= 158.35 A.

Vdc= (24 x 158.35 x 100) / 300,000= 1 V.

Vac= D.F. x Vdc = 2.1 x 1= 2.1 V.

Ispan-3 = 52,540 / 230= 228.43 A.

Vdc= (24 x 228.43 x 100) / 300,000= 1.55 V.

Vac= D.F. x Vdc = 2.1 x 1.55= 3.26 V.

Vac TOTAL = 1.5 + 2.1 + 3.261= 6.87 V.

%VR= ( 6.87 / 230) x 100%= 2.99%


Transformer no.23

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
177 0 9 0 0 1
178 0 12 0 0 1
179 0 0 0 0 1
180 0 9 0 0 1
181 0 10 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
177 0 36.27 0 0 0.15 36.42
178 0 48.86 0 0 0.15 48.51
179 0 30 0 0 0.15 0.15
180 0 36.27 0 0 0.15 36.42
181 0 40.3 0 0 0.15 40.45
Total 161.95

Maximum Demand Load:


Assuming:
200 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=(161.95 / 200) x 100% = 80.975%

1.) IFL = 200 / 20 = 10 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 10 = 15 A.

3.) The short circuit KVA in the primary:


KVASC = 200 / 0.03 = 6,666.67 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 200 / (0.03 x 20) = 333.33 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 333.33 = 533.33 A.

Therfore:
The rating of the distribution transformer shall be 200 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 161.95 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 15 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.23 is located at pole no.179

Left side
Pole number Kva / Pole No. of Span Kva-span
181 40.3 2 80.6
180 36.42 1 36.42
117.02

Right side
Pole number Kva / Pole No. of Span Kva-span
178 48.51 1 48.51
177 36.42 2 72.84
121.35

%Kva= ( 117.02 / 121.35) x 100% = 96.43%

Therefore, Transformer no.23 should be installed at pole no.179

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 200,000 / 230 = 869.57 A.

use: 2- 300,000 CM Hard Drawn Copper Conductor per line

Ra= 0.250 Xa= 0.476

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.476 + 0.035= 0.511
Xc / Ra= 0.511 / 0.250= 2.044

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 36,420 / 230= 158.35 A.

Vdc= (24 x 158.35 x 100) / 300,000= 1.267 V.

Vac= D.F. x Vdc = 2.1 x 1.267= 2.66 V.

Ispan-2 = 48,510 / 230= 210.91 A.

Vdc= (24 x 210.91 x 100) / 300,000= 1.69 V.

Vac= D.F. x Vdc = 2.1 x 1.69= 3.54 V.

Vac TOTAL = 2.66 + 3.54= 6.2 V.

%VR= (6.2 / 230) x 100%= 2.69%


Right side

Ispan-1 = 36,420 / 230= 158.35 A.

Vdc= (24 x 158.35 x 100) / 300,000= 1.267 V.

Vac= D.F. x Vdc = 2.1 x 1.267= 2.66 V.

Ispan-2 = 48,450 / 230= 175.87 A.

Vdc= (24 x 175.87 x 100) / 300,000= 1.41 V.

Vac= D.F. x Vdc = 2.1 x 1.41= 2.96 V.

Vac TOTAL = 2.66 + 2.96= 5.615 V.

%VR= ( 5.615 / 230) x 100%= 2.44%


Transformer no.24

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
184 0 8 0 0 1
185 0 6 0 0 1
186 0 1 0 0 1
187 0 6 0 0 1
188 0 9 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
184 0 32.24 0 0 0.15 32.39
185 0 24.18 0 0 0.15 24.33
186 0 4.03 0 0 0.15 4.18
187 0 24.18 0 0 0.15 24.33
188 0 36.27 0 0 0.15 24.33
Total 121.65

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 121.65 / 150) x 100% = 81.1%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.

Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 121.65 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.24 is located at pole no.186

Right side
Pole number Kva / Pole No. of Span Kva-span
184 32.39 2 64.78
185 24.33 1 24.33
89.11

Left side
Pole number Kva / Pole No. of Span Kva-span
187 24.33 1 24.33
188 36.42 2 72.84
97.17

%Kva= ( 89.11 / 97.17) x 100% = 91.71%

Therefore, Transformer no.24 should be installed at pole no.186

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 1- 500,000 CM Hard Drawn Copper Conductor per line

Ra= 0.130 Xa= 0.443

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.443 + 0.035= 0.478
Xc / Ra= 0.478 / 0.130= 3.68

By using 80% power factor, the Drop Factor is 3.23

2.) Calculation of %VR:

Left side

Ispan-1 = 32,390 / 230= 140.83 A.

Vdc= (24 x 140.83 x 100) / 500,000= 0.675 V.

Vac= D.F. x Vdc = 3.23 x 0.675= 2.18 V.

Ispan-2 = 24,330 / 230= 105.78 A.

Vdc= (24 x 105.78 x 100) / 500,000= 0.51 V.

Vac= D.F. x Vdc = 3.23 x 0.51= 1.64 V.

Vac TOTAL = 2.18 + 1.64= 3.82 V.

%VR= (3.82 / 230) x 100%= 1.66%


Upper side

Ispan-1 = 24,333 / 230= 105.78 A.

Vdc= (24 x 105.78 x 100) / 500,000= 0.51 V.

Vac= D.F. x Vdc = 3.23 x 0.51= 1.04 V.

Ispan-2 = 36,420 / 230= 158.35 A.

Vdc= (24 x 158.35 x 100) / 500,000= 0.76 V.

Vac= D.F. x Vdc = 3.23 x 0.76= 2.46 V.

Vac TOTAL = 1.04 + 2.46= 3.5 V.

%VR= ( 3.5 / 230) x 100%= 1.52%


Transformer no.25

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
195 0 15 0 0 1
196 0 4 0 0 1
197 0 3 0 0 1
198 0 4 0 0 1
199 0 16 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
195 0 60.45 0 0 0.15 60.6
196 0 16.12 0 0 0.15 16.27
197 0 12.09 0 0 0.15 12.24
198 0 16.12 0 0 0.15 16.27
199 0 64.48 0 0 0.15 64.63
Total 170.01

Maximum Demand Load:


Assuming:
200 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 170.01 / 200) x 100% = 85.01%

1.) IFL = 200 / 20 = 10 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 10 = 15 A.

3.) The short circuit KVA in the primary:


KVASC = 200 / 0.03 = 6,666.67 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 200 / (0.03 x 20) = 333.33 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 333.33 = 533.33 A.

Therfore:
The rating of the distribution transformer shall be 200 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 170.01 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 15 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.25 is located at pole no.1

Left side
Pole number Kva / Pole No. of Span Kva-span
195 60.6 2 121.2
196 16.27 1 16.27
137.47

Right side
Pole number Kva / Pole No. of Span Kva-span
198 16.12 1 16.12
199 64.48 2 128.96
145.08

%Kva= ( 137.47 / 145.08) x 100% = 94.75%

Therefore, Transformer no.25 should be installed at pole no.197

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 200,000 / 230 = 869.57 A.

use: 2- 300,000 CM Hard Drawn Copper Conductor per line

Ra= 0.250 Xa= 0.476

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.476 + 0.035= 0.511
Xc / Ra= 0.511 / 0.250= 2.044

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 60,600 / 230= 263.48 A.

Vdc= (24 x 263.48 x 100) / 300,000= 2.11 V.

Vac= D.F. x Vdc = 2.1 x 2.11= 4.43 V.

Ispan-2 = 16,270 / 230= 70.79 A.

Vdc= (24 x 70.79 x 100) / 300,000= 0.566 V.

Vac= D.F. x Vdc = 2.1 x 0.566= 1.188 V.

Vac TOTAL = 4.43 + 1.188= 5.614 V.

%VR= (5.614 / 230) x 100%= 2.44%


Right side

Ispan-1 = 16,270 / 230= 70.74 A.

Vdc= (24 x 70.74 x 100) / 300,000= 0.566 V.

Vac= D.F. x Vdc = 2.1 x 0.566= 1.188 V.

Ispan-2 = 64,480 / 230= 280.35 A.

Vdc= (24 x 280.35 x 100) / 300,000= 2.24 V.

Vac= D.F. x Vdc = 2.1 x 2.24= 4.71 V.

Vac TOTAL = 1.12 + 4.71= 5.89 V.

%VR= ( 5.89 / 230) x 100%= 2.56%


Transformer no.26

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
191 0 7 0 0 1
200 0 15 0 0 1
201 0 7 0 0 1
202 0 11 0 0 1
203 0 10 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
191 0 28.21 0 0 0.15 28.36
200 0 60.45 0 0 0.15 60.6
201 0 28.21 0 0 0.15 28.36
202 0 44.33 0 0 0.15 44.48
203 0 40.3 0 0 0.15 40.45
Total 202.25

Maximum Demand Load:


Assuming:
250 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 202.25 / 250) x 100% = 80.9%

1.) IFL = 250 / 20 = 12.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 12.5 = 18.75 A.

3.) The short circuit KVA in the primary:


KVASC = 250 / 0.03 = 8,333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 250 / (0.03 x 20) = 416.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 416.67 = 666.66 A.

Therfore:
The rating of the distribution transformer shall be 250 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 202.25 KVA, it shall be
protected by 20 Amps Fuse Link. The rating of the fuse cutout shall be 20 Amps. The
maximum fuse setting is 18.75 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.26 is located at pole no.201

Left side
Pole number Kva / Pole No. of Span Kva-span
191 28.36 2 56.72
200 60.6 1 60.6
117.32

Right side
Pole number Kva / Pole No. of Span Kva-span
202 44.48 1 44.48
203 40.45 2 40.45
125.38

%Kva= ( 117.32 / 125.38) x 100% = 93.57%

Therefore, Transformer no.26 should be installed at pole no.201

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 250,000 / 230 = 1086.96 A.

use: 2- 300,000 CM Hard Drawn Copper Conductor per line

Ra= 0.250 Xa= 0.476

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.476 + 0.035= 0.511
Xc / Ra= 0.511 / 0.250= 2.044

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 28,360 / 230= 123.3 A.

Vdc= (24 x 123.3 x 100) / 300,000= 0.986 V.

Vac= D.F. x Vdc = 2.1 x 0.986= 2.1 V.

Ispan-2 = 60,600 / 230= 263.48 A.

Vdc= (24 x 263.48 x 100) / 300,000= 2.11 V.

Vac= D.F. x Vdc = 2.1 x 2.11= 4.431 V.

Vac TOTAL = 2.1 + 4.431= 6.531 V.

%VR= (6.531 / 230) x 100%= 2.84%


Right side

Ispan-1 = 44,480 / 230= 193.39 A.

Vdc= (24 x 193.39 x 100) / 300,000= 1.55 V.

Vac= D.F. x Vdc = 2.1 x 1.55= 3.249 V.

Ispan-2 = 40,450 / 230= 175.87 A.

Vdc= (24 x 175.87 x 100) / 300,000= 1.41 V.

Vac= D.F. x Vdc = 2.1 x 1.41= 2.95 V.

Vac TOTAL = 3.249 + 2.95= 6.199 V.

%VR= ( 6.199 / 230) x 100%= 2.69%


Transformer no.27

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
205 0 13 0 0 1
206 0 0 0 0 1
207 0 5 0 0 1
208 0 0 0 0 1
209 0 14 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
205 0 52.39 0 0 0.15 52.54
206 0 0 0 0 0.15 0.15
207 0 20.15 0 0 0.15 20.3
208 0 0 0 0 0.15 0.15
209 0 56.42 0 0 0.15 56.57
Total 129.71

Maximum Demand Load:


Assuming:
150 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 129.71 / 150) x 100% = 86.47%

1.) IFL = 150 / 20 = 7.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 7.5 = 11.25 A.

3.) The short circuit KVA in the primary:


KVASC = 150 / 0.03 = 5000 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 150 / (0.03 x 20) = 250 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 250 = 400 A.

Therfore:
The rating of the distribution transformer shall be 150 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 129.71 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 11.25 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.27 is located at pole no.207

Left side
Pole number Kva / Pole No. of Span Kva-span
205 52.54 2 105.08
206 0.15 1 0.15
105.23

Right side
Pole number Kva / Pole No. of Span Kva-span
208 0.15 1 0.15
209 56.57 2 113.14
113.29

%Kva= ( 105.23 / 113.29) x 100% = 92.89%

Therefore, Transformer no.27 should be installed at pole no.207

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 150,000 / 230 = 652.17 A.

use: 1- 500,000 CM Hard Drawn Copper Conductor per line

Ra= 0.130 Xa= 0.443

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.443 + 0.035= 0.478
Xc / Ra= 0.478 / 0.130= 3.68

By using 80% power factor, the Drop Factor is 3.23

2.) Calculation of %VR:

Left side

Ispan-1 = 52,540 / 230= 228.4 A.

Vdc= (24 x 228.4 x 100) / 500,000= 1.09 V.

Vac= D.F. x Vdc = 3.23 x 1.09= 3.54 V.

Ispan-2 = 150 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 500,000= 0.003 V.

Vac= D.F. x Vdc = 3.23 x 0.003= 0.01 V.

Vac TOTAL = 3.54 + 0.01= 3.55 V.

%VR= (3.55 / 230) x 100%= 1.54%


Right side

Ispan-1 = 150 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 500,000= 0.003 V.

Vac= D.F. x Vdc = 3.23 x 0.003= 0.01 V.

Ispan-2 = 56,570 / 230= 245.96 A.

Vdc= (24 x 245.96 x 100) / 500,000= 1.181 V.

Vac= D.F. x Vdc = 3.23 x 1.181= 3.82 V.

Vac TOTAL = 0.01 + 3.82= 3.82 V.

%VR= ( 3.82 / 230) x 100%= 1.66%


Transformer no.28

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
211 0 7 0 0 1
212 0 0 0 0 1
213 0 3 0 0 1
214 0 0 0 0 1
215 0 2 0 0 1
216 0 0 0 0 1
217 0 8 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
211 0 28.21 0 0 0.15 28.36
212 0 0 0 0 0.15 0.15
213 0 12.09 0 0 0.15 12.24
214 0 0 0 0 0.15 0.15
215 0 8.06 0 0 0.15 8.21
216 0 0 0 0 0.15 0.15
217 0 32.24 0 0 0.15 32.39
Total 81.65

Maximum Demand Load:


Assuming:
100 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 81.65 / 100) x 100% = 86.47%

1.) IFL = 100 / 20 = 5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 10 = 7.5 A.

3.) The short circuit KVA in the primary:


KVASC = 100 / 0.03 = 3,333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 100 / (0.03 x 20) = 166.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 166.67 = 266.67 A.
Therfore:
The rating of the distribution transformer shall be 100 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 81.65 KVA, it shall be
protected by 10 Amps Fuse Link. The rating of the fuse cutout shall be 10 Amps. The
maximum fuse setting is 7.5 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.28 is located at pole no.214

Left side
Pole number Kva / Pole No. of Span Kva-span
211 28.36 3 85.08
212 0.15 2 0.3
213 12.24 1 12.24
97.62

Right side
Pole number Kva / Pole No. of Span Kva-span
215 8.06 1 8.06
214 0.15 2 0.3
217 32.24 3 96.72
105.08

%Kva= ( 97.62 / 105.08) x 100% = 92.9%

Therefore, Transformer no.28 should be installed at pole no.214

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 100,000 / 230 = 434.78 A.

use: 1- 300,000 CM Hard Drawn Copper Conductor per line

Ra= 0.250 Xa= 0.476

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.476 + 0.035= 0.511
Xc / Ra= 0.511 / 0.250= 2.04

By using 80% power factor, the Drop Factor is 2.1


2.) Calculation of %VR:

Left side

Ispan-1 = 28,360 / 230= 123.3 A.

Vdc= (24 x 123.3 x 100) / 300,000= 0.986 V.

Vac= D.F. x Vdc = 2.1 x 0.986= 2.07 V.

Ispan-2 = 150 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 300,000= 0.0052 V.

Vac= D.F. x Vdc = 2.1 x 0.005= 2.97 V.

Ispan-3 = 12,240 / 230= 83.22 A.

Vdc= (24 x 83.22 x 100) / 300,000= 0.426 V.

Vac= D.F. x Vdc = 2.1 x 0.426= 0.89 V.

Vac TOTAL = 2.07 + 0.01 + 0.89= 2.97 V.

%VR= (2.97 / 230) x 100%= 1.29%

Right side

Ispan-1 = 8,290 / 230= 35.69 A.

Vdc= (24 x 35.69 x 100) / 300,000= 0.286 V.

Vac= D.F. x Vdc = 2.1 x 0.286= 0.6 V.

Ispan-2 = 150 / 230= 0.65 A.

Vdc= (24 x 0.65 x 100) / 300,000= 0.0052 V.

Vac= D.F. x Vdc = 2.1 x 0.0052= 0.01 V.

Ispan-3 = 32,390 / 230= 140.83 A.

Vdc= (24 x 140.83 x 100) / 300,000= 1.127 V.

Vac= D.F. x Vdc = 2.1 x 1.127= 2.37 V.

Vac TOTAL = 0.6 + 0.01 + 2.37= 2.98V.

%VR= ( 2.98 / 230) x 100%= 1.29%


Transformer no.29

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
218 0 11 0 0 1
219 0 6 0 0 1
220 0 4 0 0 1
221 0 7 0 0 1
222 0 12 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
218 0 44.33 0 0 0.15 44.48
219 0 24.18 0 0 0.15 24.33
220 0 16.12 0 0 0.15 16.27
221 0 28.21 0 0 0.15 28.36
222 0 48.36 0 0 0.15 48.51
Total 161.95

Maximum Demand Load:


Assuming:
200 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 161.95 / 200) x 100% = 80.97%

1.) IFL = 200 / 20 = 10 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 10 = 15 A.

3.) The short circuit KVA in the primary:


KVASC = 200 / 0.03 = 6,666.67 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 200 / (0.03 x 20) = 333.33 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 333.33 = 533.33 A.

Therfore:
The rating of the distribution transformer shall be 200 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 161.95 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 15 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.29 is located at pole no.220

Left side
Pole number Kva / Pole No. of Span Kva-span
218 44.48 2 88.96
219 24.33 1 24.33
113.29

Right side
Pole number Kva / Pole No. of Span Kva-span
221 28.36 1 28.36
222 48.51 2 97.02
125.38

%Kva= ( 113.29 / 125.38) x 100% = 90.36%

Therefore, Transformer no.29 should be installed at pole no.220

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 200,000 / 230 = 869.57 A.

use: 2- 300,000 CM Hard Drawn Copper Conductor per line

Ra= 0.250 Xa= 0.476

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.476 + 0.035= 0.511
Xc / Ra= 0.511 / 0.250= 2.04

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 44,480 / 230= 193.39 A.

Vdc= (24 x 193.39 x 100) / 300,000= 1.55 V.

Vac= D.F. x Vdc = 2.1 x 1.55= 3.25 V.

Ispan-2 = 24,330 / 230= 105.28 A.

Vdc= (24 x 105.28 x 100) / 300,000= 0.85 V.

Vac= D.F. x Vdc = 2.1 x 0.85= 1.78 V.

Vac TOTAL = 3.25 + 1.78= 5.1 V.

%VR= (5.1 / 230) x 100%= 2.1%


Right side

Ispan-1 = 28,360 / 230= 123.3 A.

Vdc= (24 x 123.3 x 100) / 300,000= 0.99 V.

Vac= D.F. x Vdc = 2.1 x 0.099= 2.1 V.

Ispan-2 = 48,510 / 230= 210.91 A.

Vdc= (24 x 210.91 x 100) / 300,000= 1.69 V.

Vac= D.F. x Vdc = 2.1 x 1.69= 3.54 V.

Vac TOTAL = 2.1 + 3.54= 5.64 V.

%VR= ( 5.64 / 230) x 100%= 2.45%


Transformer no.30

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
224 0 20 0 0 1
225 0 11 0 0 1
226 0 21 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
224 0 80.6 0 0 0.15 80.75
225 0 44.33 0 0 0.15 44.48
226 0 84.63 0 0 0.15 84.78
Total 210.01

Maximum Demand Load:


Assuming:
250 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 210.01 / 250) x 100% = 84%

1.) IFL = 250 / 20 = 12.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 12.5 = 18.75 A.

3.) The short circuit KVA in the primary:


KVASC = 250 / 0.03 = 8,333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 250 / (0.03 x 20) = 416.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 416.67 = 666.67 A.

Therfore:
The rating of the distribution transformer shall be 250 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 210.1 KVA, it shall be
protected by 20 Amps Fuse Link. The rating of the fuse cutout shall be 20 Amps. The
maximum fuse setting is 18.75 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.30 is located at pole no.225

Left side
Pole number Kva / Pole No. of Span Kva-span
224 80.75 1 80.75
80.75

Right side
Pole number Kva / Pole No. of Span Kva-span
226 84.78 1 84.78
84.78

%Kva= ( 80.75 / 84.78) x 100% = 95.25%

Therefore, Transformer no.30 should be installed at pole no.225

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 250,000 / 230 = 1086.95 A.

use: 2- 400,000 CM Hard Drawn Copper Conductor per line

Ra= 0.162 Xa= 0.458

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.458 + 0.035= 0.493
Xc / Ra= 0.0.493 / 0.162= 3.04

By using 80% power factor, the Drop Factor is 2.8

2.) Calculation of %VR:

Left side

Ispan-1 = 80,750 / 230= 351.1 A.

Vdc= (24 x 351.1 x 100) / 400,000= 2.1 V.

Vac= D.F. x Vdc = 2.8 x 2.1= 5.88 V.

Vac TOTAL = 5.88= 5.88 V.

%VR= (5.88 / 230) x 100%= 2.56%


Right side

Ispan-1 = 84,780 / 230= 368.61 A.

Vdc= (24 x 368.61 x 100) / 400,000= 2.21 V.

Vac= D.F. x Vdc = 2.8 x 2.21= 6.192 V.

Vac TOTAL = 6.192= 6.192 V.

%VR= ( 6.192 / 230) x 100%= 2.69%


Transformer no.31

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
227 0 17 0 0 1
228 0 19 0 0 1
229 0 18 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
227 0 68.51 0 0 0.15 68.66
228 0 76.57 0 0 0.15 76.62
229 0 72.54 0 0 0.15 72.69
Total 218.07

Maximum Demand Load:


Assuming:
250 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 218.07 / 250) x 100% = 87.23%

1.) IFL = 250 / 20 = 12.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 12.5 = 18.75 A.

3.) The short circuit KVA in the primary:


KVASC = 250 / 0.03 = 8,333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 250 / (0.03 x 20) = 416.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 416.67 = 666.67 A.

Therfore:
The rating of the distribution transformer shall be 250 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 218.07 KVA, it shall be
protected by 20 Amps Fuse Link. The rating of the fuse cutout shall be 20 Amps. The
maximum fuse setting is 18.75 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.31 is located at pole no.228

Left side
Pole number Kva / Pole No. of Span Kva-span
227 68.66 1 68.66
68.66

Right side
Pole number Kva / Pole No. of Span Kva-span
229 72.69 1 72.69
72.69

%Kva= ( 68.66 / 72.69) x 100% = 94.95%

Therefore, Transformer no.31 should be installed at pole no.228

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 250,000 / 230 = 1086.95 A.

use: 2- 400,000 CM Hard Drawn Copper Conductor per line

Ra= 0.162 Xa= 0.458

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.458 + 0.035= 0.493
Xc / Ra= 0.0.493 / 0.162= 3.04

By using 80% power factor, the Drop Factor is 2.8

2.) Calculation of %VR:

Left side

Ispan-1 = 68,660 / 230= 298.5 A.

Vdc= (24 x 298.5 x 100) / 400,000= 1.79 V.

Vac= D.F. x Vdc = 2.8 x 1.79= 5.1 V.

Vac TOTAL = 5.1= 5.1 V.

%VR= (5.1 / 230) x 100%= 2.18%


Right side

Ispan-1 = 72,640 / 230= 320.39 A.

Vdc= (24 x 320.29 x 100) / 400,000= 1.92 V.

Vac= D.F. x Vdc = 2.8 x 1.92= 5.38 V.

Vac TOTAL = 5.38= 5.38 V.

%VR= ( 5.38 / 230) x 100%= 2.34%


Transformer no.32

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
223 0 11 0 0 1
234 0 5 0 0 1
235 0 7 0 0 1
236 0 7 0 0 1
237 0 7 0 0 1
238 0 5 0 0 1
239 0 12 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
223 0 44.33 0 0 0.15 44.48
234 0 20.15 0 0 0.15 20.3
235 0 28.21 0 0 0.15 28.36
236 0 28.21 0 0 0.15 28.36
237 0 28.21 0 0 0.15 28.36
238 0 20.15 0 0 0.15 20.3
239 0 48.36 0 0 0.15 40.51
Total 218.67

Maximum Demand Load:


Assuming:
250 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 218.67 / 250) x 100% = 87.47%

1.) IFL = 250 / 20 = 12.5 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 12.5 = 18.75 A.

3.) The short circuit KVA in the primary:


KVASC = 250 / 0.03 = 8,333.33 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 250 / (0.03 x 20) = 416.67 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 416.67 = 666.67 A.
Therfore:
The rating of the distribution transformer shall be 250 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 218.67 KVA, it shall be
protected by 20 Amps Fuse Link. The rating of the fuse cutout shall be 20 Amps. The
maximum fuse setting is 18.75 Amps. The lightning Arrester shall be 21 KV line type.

Selection of the most advantageous transformer location

assume that Transformer no.32 is located at pole no.236

Left side
Pole number Kva / Pole No. of Span Kva-span
223 44.48 3 133.14
234 20.3 2 40.6
235 28.36 1 28.36
202.1

Right side
Pole number Kva / Pole No. of Span Kva-span
237 28.26 1 28.36
238 20.3 2 40.6
239 48.51 3 145.53
214.49

%Kva= ( 202.1 / 214.49) x 100% = 94.22%

Therefore, Transformer no.32 should be installed at pole no.236

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 250,000 / 230 = 1086.95 A.

use: 2- 400,000 CM Hard Drawn Copper Conductor per line

Ra= 0.162 Xa= 0.458

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.458 + 0.035= 0.493
Xc / Ra= 0.0.493 / 0.162= 3.04

By using 80% power factor, the Drop Factor is 2.8


2.) Calculation of %VR:

Left side

Ispan-1 = 44,480 / 230= 193.39 A.

Vdc= (24 x 193.39 x 100) / 400,000= 1.16 V.

Vac= D.F. x Vdc = 2.8 x 1.16= 3.25 V.

Ispan-2 = 20,300 / 230= 88.26 A.

Vdc= (24 x 88.26 x 100) / 400,000= 0.521 V.

Vac= D.F. x Vdc = 2.8 x 0.521= 1.49 V.

Ispan-3 = 28,360 / 230= 123.3 A.

Vdc= (24 x 123.3 x 100) / 400,000= 0.74 V.

Vac= D.F. x Vdc = 2.8 x 0.74 = 2.07 V.

Vac TOTAL = 3.25 + 1.49 + 2.07= 6.8 V.

%VR= (6.8 / 230) x 100%= 2.96%

Right side

Ispan-1 = 28,360 / 230= 123.3 A.

Vdc= (24 x 123.3 x 100) / 400,000= 0.74 V.

Vac= D.F. x Vdc = 2.8 x 0.74= 2.07 V.

Ispan-2 = 20,300 / 230= 88.26 A.

Vdc= (24 x 88.26 x 100) / 400,000= 0.529 V.

Vac= D.F. x Vdc = 2.8 x 0.529= 1.48 V.

Ispan-3 = 48,510 / 230= 210.91 A.

Vdc= (24 x 210.91 x 100) / 400,000= 1.542 V.

Vac= D.F. x Vdc = 2.8 x 1.542= 3.542 V.

Vac TOTAL = 2.07 + 1.48 + 3.54= 7.09 V.

%VR= ( 7.09 / 230) x 100%= 3%


Transformer no.33

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
241 0 7 0 0 1
242 0 8 0 0 1
243 0 9 0 0 1
244 0 7 0 0 1
245 0 8 0 0 1
Total

Pole no. Residential Loads Other Loads Street Lights Kva / Pole
Class A Class B Class C
241 0 28.21 0 0 0.15 28.36
242 0 32.24 0 0 0.15 32.39
243 0 36.27 0 0 0.15 36.42
244 0 28.21 0 0 0.15 28.36
245 0 32.24 0 0 0.15 32.36
Total 157.89

Maximum Demand Load:


Assuming:
200 KVA, Single phase, 20 KV Distribution transformer with 3% impedance,
115V/230V, 60 Hz.

%Loading=( 157.89 / 200) x 100% = 78.95%

1.) IFL = 200 / 20 = 10 A.

2.) The maximum settings over current protection device in the primary:
I = 1.5( IFL) = 1.5 x 10 = 15 A.

3.) The short circuit KVA in the primary:


KVASC = 200 / 0.03 = 6,666.67 Kva

4.) The symmetrical short circuit current in the primary side:


ISCsym = 200 / (0.03 x 20) = 333.33 A.

5.) The Asymmetrical short circuit current in primary side:


ISCasym =1.6(ISCsym ) =1.6 x 333.33 = 533.33 A.

Therfore:
The rating of the distribution transformer shall be 200 KVA, 20 KV, 115V/230V,
60 Hz, Single phase with 3% Impedance. The total expected load is 157.89 KVA, it shall be
protected by 15 Amps Fuse Link. The rating of the fuse cutout shall be 15 Amps. The
maximum fuse setting is 15 Amps. The lightning Arrester shall be 21 KV line type.
Selection of the most advantageous transformer location

assume that Transformer no.33 is located at pole no.243

Left side
Pole number Kva / Pole No. of Span Kva-span
241 28.36 2 56.72
242 32.39 1 32.39
89.11

Right side
Pole number Kva / Pole No. of Span Kva-span
244 28.36 1 28.36
245 32.36 2 69.72
93.08

%Kva= ( 89.11 / 93.08) x 100% = 95.73%

Therefore, Transformer no.33 should be installed at pole no.243

1.) Determining the conductor size in secondary side of transformer:

Current at secondary side of transformer (load side):

I= 200,000 / 230 = 869.57 A.

use: 2- 300,000 CM Hard Drawn Copper Conductor per line

Ra= 0.250 Xa= 0.476

use 9” spacing between secondary


Xd= 0.035
Xc= Xa + Xd= 0.476 + 0.035= 0.511
Xc / Ra= 0.511 / 0.250= 2.04

By using 80% power factor, the Drop Factor is 2.1

2.) Calculation of %VR:

Left side

Ispan-1 = 28,360 / 230= 123.3 A.

Vdc= (24 x 123.3 x 100) / 300,000= 0.97 V.

Vac= D.F. x Vdc = 2.1 x 0.97= 2.07V.

Ispan-2 = 32,390 / 230= 140.83 A.

Vdc= (24 x 140.83 x 100) / 300,000= 1.127 V.

Vac= D.F. x Vdc = 2.1 x 1.127= 2.37 V.

Vac TOTAL = 2.07 + 2.37= 4.44 V.

%VR= ( 4.44 / 230) x 100%= 1.9%


Right side

Ispan-1 = 28,360 / 230= 128.3 A.

Vdc= (24 x 128.3 x 100) / 300,000= 0.97 V.

Vac= D.F. x Vdc = 2.1 x 0.97= 2.07 V.

Ispan-2 = 32,360 / 230= 140.69 A.

Vdc= (24 x 140.69 x 100) / 300,000= 1.126 V.

Vac= D.F. x Vdc = 2.1 x 1.126= 2.36V.

Vac TOTAL = 2.07 + 2.36= 4.434 V.

%VR= ( 4.434 / 230) x 100%= 1.93%