You are on page 1of 2

Company Name:

Company Address:

Order Number:

General test information: Date/Time: 2017-06-07, 08:05:03 AM


Test device: CT-Analyzer Device Serial No.: EL074Z
File name: LAYSER RESULTS Backup\07-06-2017\HA-45-INCOMER-3\T011-HA-45_R\ALCE_1001508790_1_3600.x
Assessments: OK

Used test settings:


I-pn: 3600.0 A Location: Object:
I-sn: 1.0 A Company: OSAIS Manufacturer: ALCE
Rated burden: 60.0 VA / 1 Country: KSA Type: AR01a
Operating burden: 60.0 VA / 1 Station: KHUDARIYAH Serial number: 1001508790
Applied standard: IEC 61869-2 Feeder/Bay: HA45 Core number: 1
Core type (P/M): P Phase: R Tap: 3600
Class: PX IEC-ID Optional:
f: 60.0 Hz max. Rct: 18.0 Ω Kx: 12.13

Resistance test: Burden test:


Rmeas (30°C): 14.41369 Ω Burden: cos φ: Z:
Rref (75°C): 16.86593 Ω Vmeas: Imeas:

Excitation test:
V-kn: 932.411 V I-kn: 0.005668 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A Kx: 12.13 Kx: 12.13
Ls: Lm: 499.8658H Ts: 6.503s Ts: 6.503s
Kr: 80.56 %
required measured Assessments:
Ek: 800.0 V Ie: 0.03 A Ek: 932.411 V Ie: 0.00567 A #N/A
E1, Vk1 400.0 V Ie1, Ik1 0.00221 A Ie1 Ik1: 0.00221 A #N/A

Ratio test:
Ratio: 3600.0 : 0.99955 ε : -0.0446 % ∆φ: 1.32 min Polarity: OK N: 3599.94
εt : -0.0016 %

Excitation curve data


Excitation curve data

10000

1000

100
Es / V

10

0.1
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
60 VA/ 1 -0.187 -0.125 -0.095 -0.073 -0.056 -0.045 -0.043 -0.040
30 VA/ 1 -0.115 -0.087 -0.069 -0.052 -0.038 -0.030 -0.028 -0.025
15 VA/ 1 -0.070 -0.066 -0.052 -0.040 -0.028 -0.023 -0.021 -0.017
7.5 VA/ 1 -0.047 -0.051 -0.043 -0.033 -0.023 -0.018 -0.017 -0.014
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
60 VA/ 1 13.819 4.440 2.794 1.827 1.171 1.322 1.219 0.949
30 VA/ 1 11.637 3.827 2.355 1.477 0.887 0.815 0.881 0.729
15 VA/ 1 9.957 3.391 2.082 1.285 0.726 0.517 0.475 0.566
7.5 VA/ 1 8.743 3.097 1.905 1.173 0.646 0.441 0.404 0.397
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200

0.000
0 50 100 150 200 250

-0.020

-0.040

-0.060
Current deviation [%]

100% Load
-0.080

50% Load
-0.100

-0.120 25% Load

-0.140

-0.160

-0.180

-0.200

% I-pn

You might also like