You are on page 1of 2

Company Name:

Company Address:

Order Number:

General test information: Date/Time: 2017-06-04, 08:20:29 AM


Test device: CT-Analyzer Device Serial No.: EL074Z
File name: HUDARIYAH-Commissioning\HA-01-OG FEEDER BUS A\T032-HA-01_Y\ALCE_2015-1001509134_1_800.x
Assessments: OK

Used test settings:


I-pn: 800.0 A Location: Object:
I-sn: 1.0 A Company: OSAIS Manufacturer: ALCE
Rated burden: 30.0 VA / 0.8 Country: KSA Type: SA2D4H2
Operating burden: 30.0 VA / 0.8 Station: KHUDARIYAH Serial number: 2015-1001509134
Applied standard: IEC 61869-2 Feeder/Bay: HA-01 Core number: 1
Core type (P/M): P Phase: Y Tap: 800
Class: 5P IEC-ID Optional:
ALF: 20.0 Ts:
f: 60.0 Hz max. Rct: 5.462 Ω

Resistance test: Burden test:


Rmeas (30°C): 4.6679 Ω Burden: cos φ: Z:
Rref (75°C): 5.46206 Ω Vmeas: Imeas:

Excitation test:
V-kn: 621.001 V I-kn: 0.012706 A Result with rated burden: Result with operating burden:
V-kn 2: #N/A I-kn 2: #N/A ALF: >23.298915 ALFi: 22.38 ALF: >23.298915 ALFi: 22.38
Ls: 0.0070481H Lm: 143.9891 H Ts: 4.887s Ts: 4.887s
Kr: 91.43 %

Ratio test:
Ratio: 800.0 : 1.00003 ε : 0.0029 % ∆φ: 0.36 min Polarity: OK N: 799.20
εc : 0.0117 %

Excitation curve data


Excitation curve data

1000

100

10
Es / V

0.1

0.01
0.00001 0.0001 0.001 0.01 0.1 1 10

le / A

Series1 (I-kn,V-kn) (I-kn2,V-kn2) Series 2


Current ratio error in % at % of rated current
VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0.8 -0.432 -0.127 -0.078 -0.043 -0.013 0.003 0.006 0.014
15 VA/ 0.8 -0.314 -0.054 -0.018 0.006 0.028 0.039 0.042 0.047
7.5 VA/ 0.8 -0.208 -0.013 0.019 0.036 0.052 0.060 0.061 0.065
3.75 VA/ 1 0.029 0.048 0.060 0.067 0.072 0.076 0.077 0.079
VA/

Phase displacement in [min] at % rated current


VA/cosPhi 1 5 10 20 50 100 120 200
30 VA/ 0.8 14.492 3.846 2.244 1.343 0.669 0.358 0.386 0.499
15 VA/ 0.8 14.804 3.635 2.227 1.358 0.753 0.479 0.423 0.295
7.5 VA/ 0.8 15.516 3.713 2.219 1.370 0.800 0.531 0.483 0.371
3.75 VA/ 1 18.158 4.569 2.739 1.849 1.154 0.856 0.793 0.654
VA/

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 Error Graph
Ratio 20 50 100 120 200
1.00 1.00 1.00
-1.00 -1.00 -1.00
0.100

0.000
0 50 100 150 200 250
Current deviation [%]

-0.100
100% Load

50% Load
-0.200

25% Load

-0.300

-0.400

-0.500

% I-pn

You might also like