General characteristics KRA0800 KRA1000 KRA1250 KRA1600 KRA2000 KRA2500 KRA3200 KRA4000 KRA5000
Compliance with standards IEC 61439-1 and IEC 61439-6
Protection degree IP 68
Shock resistance IK 10
Nominal rated current at an ambient Inc A 800 1000 1250 1600 2000 2500 3200 4000 5000
Allowable rated peak current Ipk kA 56 56 117 117 143 176 220 220 220
I²t A².s106 729 729 2809 2809 4225 6400 10000 10000 10000
Conductor characteristics
Average resistance at an ambient R20 0.081 0.06 0.048 0.03 0.024 0.02 0.015 0.012 0.01
Other characteristics
Voltage drop Line-to-line voltage drop, in volts (V) per 100 metres and per amp (A) at 50 Hz with load concentrated at the end of a run.
This calculation table applies to three-phase loads. For single-phase loads, the voltage drop given in the table is divided
by 1.732.
1 0.0166 0.0128 0.0102 0.0062 0.0050 0.0045 0.0033 0.0026 0.0023
0.9 0.0169 0.0157 0.0130 0.0091 0.0069 0.0062 0.0048 0.0043 0.0038
0.8 0.0160 0.0160 0.0134 0.0098 0.0072 0.0066 0.0051 0.0048 0.0042
0.7 0.0149 0.0158 0.0133 0.0101 0.0074 0.0067 0.0053 0.0050 0.0044
Average weight
Bus duct total weight 3/4/5 conductors kg/m 21/22/22 26/29/35 30/34/40 43/48/58 52/58/69 61/68/81 85/95/113 102/115/137 120/135/161
Fire load value
Fire Load kWh/m 11.8 15.7 19.2 31.4 35 37.3 62.8 70.1 74.5
68 DEBU031EN