Calculation of R and X

frequency 50
Rating in MVA 30000000 VA Zhv Base
HV side voltage in kV 35000 V Zlv base
LV side Voltage in kV 441 V
No load losses in kW 24000 W
No-load current, % 0.6 %
Full load losses in kW 175000 W
Short circuit impedance in % 6 0.06 pu

R 0.0050333333 pu
X 0.0597885069 pu 0.000387591
Magnetizing resistance, Rm 51041.666667 Ohm
Leakage inductance
Air-core reactance
saturable
40.833333333
0.0064827 % Voltage % No-load current Noload current (A) Coreloss
100 0.6 2.96922995583236 0.6857142857
105 1.01 4.99820375898447 0.72
110 2.05 10.1448690157606 0.792

Leakage inductance 0.007799 H


Air-core reactance 0.015597 H
0.007799 H

No-Load current (A)


data value simulated value
100 2.969 2.917
105 4.75 4.73
110 9.105 9.004
38500
70000
31500
Input to Non-linear (PU)
Magnetizing Current Voltage Current Flux
2.88896564 0.0058378078 1 4.087083 90.93195
4.94607327 0.0099946586 1.05 12.15694 95.47855
10.1139064 0.0204374331 1.1 26.01402 100.0251
10520.06 181.8639
25520

23.989 kW Noload power

9.004
4642
4632.996
0.02164207
Description Value Unit
Horizantal distance 0.5 m
Vertical distance 1 m
Nominal Overall diameter 1.74 in
Diameter of the conductor 0.74 in
Resistivity of conductor 1.72E-08
Outer Diameter of insulator screen 1.53 in
Inner Diameter of insulator screen 1.43 in
Resistivity of insulator 2.84E-08

Description Value Unit


frequency 50 Hz
Rating in MVA 30 MVA
HV side voltage in kV 35 kV
LV side Voltage in kV 0.441 kV
No load losses in kW 30 kW
No-load current, % 0.6 %
Full load losses in kW 175 kW
Short circuit impedance in % 6 %
Noload Current I0% 0.6
Rated MVA 30
Frequency 50
Rated Voltage 35

Inductance (ohm) @ Inductance


Equipment Inductance (H)
110 kV (H) @ 35 kV
Source 2.5359 0.00808 0.00082
Main transformer 23.232 0.07399 0.00749
Transformer to VCB
0.00080
(350 m cable)
VCB to arc furnace
transformer (30 m 0.00007
cable)

Total inductance (Lc) 0.00918

Equipment Capacitance (µF)

350 m cable 0.675714285714286

30 m cable 7.88333333333333

Stray capacitances of
transformer and 0.007
breaker
Total capacitance (C) 8.56604761904762
Sn Rated power of transformer in MVA
Un Rated voltage in kV
f Frequency in Hz
Imag Magnetization current of transformer in %

Lc sum of the all inductances of switched par


C Total capacitance including surge capacitan

Typical Values of R and C

Capacitance= 0.026184 uF

R>(2*sqrt(L/C) 65.476 ohm

2.2969
Inductance mh/km
nsformer in MVA

ent of transformer in % of nominal current

ctances of switched part of the network


ncluding surge capacitances also of switched part of network