Voltage Drop Calculation

A Base Selection
Base KV

6.6

kV

Base MVA

15.0

MVA

Base Current = Base MVA *1000/ ( 1.732 X Base KV)

Amp

Base Impedance = (Base KV)2 / Base MVA

1312.20

2.9040

Ohm

B Transformer Details
Rating of Transformer in MVA

15.0

MVA

Transformer Primary Voltage ( KV)

33

kV

Transformer Secondary Voltage ( KV)

6.6

kV

% Impedance of the Transformer

10

Fault kA at Transformer HV Terminals (kA) =

4.00

kA

Impedance of the Transformer =

0.29

ohm

Ztrf (p.u.)

0.1

Fault MVA at Transformer HV Terminals =

228.63

Zsource =Source Impedance = Base MVA * (Rated voltage)^2 / Fault MVA * (Base kV)^2

0.0656

Zt = Total Impedance = Ztrf + Zsource

0.16561

MVA
pu
90

C Load Details
Load Voltage

6.1838

kV

Average current

600

Running Power Factor

0.9

Running Load in MVA

6.860

Running Current =

640.50

-25.85

MVA

Running Current in p.u = Running Current / Base Current (It)

0.488

-25.85

0.4393

-0.2128

D Cable-1 from Transformer to HV Swgr - 1


The size of cable selected per phase = 300 sqmm
Number of cable runs

Length of Cable From Transformer to HV Swgr-1 in Meter

900

Cable Resistance at 90 deg. Cent. (Ohm / Meter)

0.0000837

R=

0.084

Ohm/ KM)

Cable Reactance at 50 Hz (Ohm / Meter)

0.000082

X=

0.082

Ohm/ KM)

Cable Impedance in Ohm

0.105

44.42

Zc1 = Cable Impedance in p.u = Cable Impedance / Base Impedance

0.036

44.42

E Cable-2 from HV Swgr-1 to HV Swgr-2


The size of cable selected per phase = 2 x 240 sqmm
Number of cable runs

Length of Cable From HV swgr-1 to HV Swgr-2 in Meter

1100

Cable Resistance at 90 deg. Cent. (Ohm / Meter)

0.000052

R=

0.104

Ohm/ KM)

Cable Reactance at 50 Hz (Ohm / Meter)

0.0000425

X=

0.085

Ohm/ KM)

Cable Impedance in Ohm

0.074

39.26

Zc2 = Cable Impedance in p.u = Cable Impedance / Base Impedance

0.025

39.26

0.08084

64.15

0.0352

0.0727

0.0177

18.57

0.0168

0.0056

0.0124

13.41

0.0121

0.0029

0.1032

51.73

0.0641

0.0813

0.6812

51.73

0.4219

0.5348

6.1857

-5.17

6.1781

-0.5348

F Calculation of Voltage Drop


V1 = Voltage Drop at Trafo Sec Term. = Running Current in pu X Impedance upto Trafo Sec Term. = It x Zt
V2 = Voltage drop in Cable1 = Running current in p.u X Cable Impedance in p.u = It x Zc1
V3 = Voltage drop in Cable-2 = Running current in p.u X Cable Impedance in p.u = It x Zc2
Total Voltage Drop HV Swgr-2 = V1 + V2 + V3 in p.u
Total Voltage Drop upto HV Swgr-2 in KV = Total Voltage drop in p.u X Base Voltage in KV
=

V4 =Voltage available at HV Swgr-2 in KV = Load Voltage in KV- Voltage Drop in KV =

% Voltage Drop at HV Swgr-2 = ((Load Voltage - V4)/Load Volatge) X 100

6.28