Professional Documents
Culture Documents
Overall assessement OK
Asset
Ipn 75.0 A Object Location
Isn 1.0 A Manufacturer ABB Company ALPHA POWER
Rated burden 5.0 VA /0.80 Type TPU 40.23 Country UAE
Operating burden 5.0 VA /0.80 Serial number 1VLT5120055249 Station 33/11 PU 3
Standard IEC 61869-2 Core M Feeder K04
Application Metering Tap 1S1-1S2 Phase Y
Class 0.5 Optional IEC-ID 61869-2
Frequency 50.0 Hz Comment
Rct max 0.957 Ω ?
FS 5.0
Ext Ipn 120 %
Burden
Burden cos φ: Z
V-meas I-meas
Excitation
Ls 0.000150 H Lm 11.420704 H Results at rated burden (5.00 VA) Results at operating burden (5.00 VA)
Kr 72.73 % FS 2.00 FSi 1.88 FS 2.00 FSi 1.88
Standard IEC 61869-2 εci (@ FS=5) > 43.175 % εci (@ FS=5) > 43.175 %
V-kn 8.895 V I-kn 0.002 A Ts 2.304 s Ts 2.304 s
Ratio
Turns ratio 74.6612 Results at rated burden (5.00 VA) Results at operating burden (5.00 VA)
εt -0.4518 % Ratio 75.0 : 1.003 Ratio 75.0 : 1.003
Polarity OK ε 0.2969 % ∆φ 0.53 min ε 0.2969 % ∆φ 0.53 min
εc 0.2973 % εc 0.2973 %
Residual magnetism
Residual flux
Residual magnetism
Excitation curve
100.00
X1_X2_1
10.00
Voltage [V]
1.00
0.000 0.000 0.000 0.001 0.010 0.100 1.00 10.00
0.010
Ie [A]
1/2
Current ratio error in % at % of rated current at rated burden (5.00 VA)
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
5.00/0.80 0.1448 0.1325 0.1307 0.1644 0.2348 0.2969 0.3074 -3.3241
2.50/1.00 0.4479 0.4352 0.4051 0.3709 0.3594 0.3656 0.3699 0.3854
1.25/1.00 0.4506 0.4474 0.4376 0.4154 0.3965 0.3938 0.3953 0.4024
0.63/1.00 0.4247 0.4505 0.4478 0.4362 0.4163 0.4135 0.4129 0.4145
0 1.250 VA
-0.5
0.625 VA
-1
-1.5
Limits
-2
-2.5 Limits
-3
-3.5
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
200
2.500 VA
150
Phase [min]
1.250 VA
100
0.625 VA
50
Limits
0
-50 Limits
-100
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
2/2