Test device Date/Time 07/06/2022 08:13

Test device CT-Analyzer Device serial no PC033N


Hardware version 01/01/09/05/01/11

Asset
Ipn 1200.0 A Object Location
Isn 1.0 A Manufacturer ENPAY Company SOFIDEL
Standard IEC 61869-2 Type Country UK
Application Protection Serial number Station SOFIDEL
Class PX Core 2 Feeder T2
Frequency 50.0 Hz Tap 2S1-2S2 Phase 2U
Optional IEC-ID IEC 61869-2
Comment

Secondary winding resistance


R-meas (13.0 °C) 4.007 Ω I-DC 0.990950 A V-DC 3.9711 V
R-ref (75.0 °C) 5.011 Ω

Ratio
Ratio 1200.0 : 1.0 Polarity OK
ε 0.001 %
∆φ 0.83 min

Excitation
Ls 0.004611 H Lm 104.1082 H
Standard IEC 61869-2
V-kn 358.48 V I-kn 0.0123 A

Excitation
1000.00

100.00
X1_X2_1
Rectified voltage

10.00

1.00

0.10 Knee IEC 61869-2

0.01
0.00 0.00 0.001 0.01 0.10 1.00 10.00
RMS current

1/1