CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)

PROJECT : ANNUAL MAINTENANCE TESTING


PAGE No. :

TEST REPORT FOR DIFFERINTIAL PROTECTION RELAY

Location : BLOCK-1
Panel : BLOCK-1 33 KV HT PANEL
Designation : DIFFERINTIAL PROTECTION RELAY
Make : ALSTOM
Model : P645
Sl.No : 34967758/01/20
CT Ratio : HV- 250/1 A LV- 3.600 KA
Date of Testing : 26/12/2023
1. Settings:
A. DIFF

TRANS DIFF ENABLED

SET MODE ADVANCE

IS1 0.200 PU

K1 30%

IS2 1.0 PU

K2 80%

Ih (2) 15%

Ih (5) 30%

B. I> 1

Start Value 1.20 x In

TMS 0.100

Curve IEC (SI)

C. I> 3

Start Value 10.0 x In

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Operating Time 0.020sec

Curve IEC (DT)

D. IN > 1

Start Value 0.400 x In

Curve IEC (SI)

TMS 0.100

E. IN > 2

Start Value 10.0 x In

Operating Time 0.020sec

Curve IEC (DT)

Test Results
Title: MEASUREMENT
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-3
I L3

I(1)-1
I L1
180° 0°

I(1)-2
I L2
254.0 V -90° 1.0 A
V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

I L1 1.000A 0.00°
I L2 1.000A -120.00°
I L3 1.000A 120.00°
I(1)-1 1.000A 0.00°
I(1)-2 1.000A -120.00°
I(1)-3 1.000A 120.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 20:48:49
Title: STABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

V L1-E 0.000V 0.00° +90°


I(1)-2

II L3I L1
180° L2 0°

I(1)-1 I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 210.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 20:55:13
Title: UNSTABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Direct V L1-E 0.00 V 0.00 ° 50.000 Hz


V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

II L3I L1 I(1)-1
180° L2 0°

I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 0.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.026s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
TESTED BY VERIFIED BY WITNESSED BY
CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Assessment
Passed 26-Dec-2023 20:57:15
Title: 1 PHASE PICKUP HV SIDE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 180.0 mA 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I L1
180° 0°

254.0 V -90° 200.0 mA


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.180A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.033s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 20:58:35
Title: 3 PHASE PICKUP HV SIDE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 180.0 mA 0.00 ° 50.000 Hz
I L2 180.0 mA -120.00 ° 50.000 Hz
I L3 180.0 mA 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I L3

I L1
180° 0°

I L2

254.0 V -90° 200.0 mA


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.180A 0.00°
I L2 0.180A -120.00°
I L3 0.180A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Trip 0->1 0.034s


Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 20:59:37
Title: 1 PHASE PICKUP LV SIDE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

180° 0°

I(1)-1

254.0 V -90° 1.5 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.000A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 1.140A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
TESTED BY VERIFIED BY WITNESSED BY
CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.047s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:02:18
Title: 3 PHASE PICKUP LV SIDE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 0.00 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

180° 0°

I(1)-1 I(1)-3

254.0 V -90° 800.0 mA


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.000A 0.00°
I L2 0.000A -120.00°

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

I L3 0.000A 120.00°
I(1)-1 0.670A 210.00°
I(1)-2 0.670A 90.00°
I(1)-3 0.670A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.027s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:04:18
Title: SLOP 30% LV DECREASE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

V L1-E 0.000V 0.00° +90°

I(1)-2

I L3 I L1
180° I L2 0°

I(1)-1 I(1)-3

254.0 V -90° 3.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 2.470A 210.00°
I(1)-2 2.470A 90.00°
I(1)-3 2.470A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.111s
Start 1->0 n/a
Overload 1->0 n/a

Formula
Id/IbX100
0.260/0.873 X100
0.2968X100
= 30%
Analog Inputs
VDCin IDCin
n/a n/a

Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:07:24

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Title: SLOP 80% HV INCREASE


.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 5.422 A 0.00 ° 50.000 Hz
I L2 5.422 A -120.00 ° 50.000 Hz
I L3 5.422 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I(1)-2

I L3 I L1
180° I L2 0°
I(1)-1 I(1)-3

254.0 V -90° 15.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 5.422A 0.00°
I L2 5.422A -120.00°
I L3 5.422A 120.00°
I(1)-1 10.020A 210.00°
I(1)-2 10.020A 90.00°
I(1)-3 10.020A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.037s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:13:03
Title: SLOP 80% LV DECREASE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 2.622 A 0.00 ° 50.000 Hz
I L2 2.622 A -120.00 ° 50.000 Hz
I L3 2.622 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

I L3 I L1
180° I L2 0°

I(1)-1 I(1)-3

254.0 V -90° 6.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 2.622A 0.00°
I L2 2.622A -120.00°
I L3 2.622A 120.00°
I(1)-1 5.420A 210.00°
I(1)-2 5.420A 90.00°
I(1)-3 5.420A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.035s
Start 1->0 n/a
Overload 1->0 n/a

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Id1-Id2/Ib1-Ib2X100
3.220-1.385/4.625/2.322X100
1.835/2.303X100
=0.796X100
=80%

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:16:13
Title: I H2
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 100.00 Hz
V L2-E 0.00 V -120.00 ° 100.00 Hz
V L3-E 0.00 V 120.00 ° 100.00 Hz
I L1 100.0 mA 0.00 ° 100.00 Hz
I L2 100.0 mA -120.00 ° 100.00 Hz
I L3 100.0 mA 120.00 ° 100.00 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

I L1
II L2
180° L3 0°

I(1)-1 I(1)-3

254.0 V -90° 1.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.100A 0.00°
I L2 0.100A -120.00°
I L3 0.100A 120.00°
I(1)-1 1.000A 210.00°
I(1)-2 1.000A 90.00°

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

I(1)-3 1.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.023s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:22:43
Title: I H5
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 100.00 Hz
V L2-E 0.00 V -120.00 ° 100.00 Hz
V L3-E 0.00 V 120.00 ° 100.00 Hz
I L1 200.0 mA 0.00 ° 250.00 Hz
I L2 200.0 mA -120.00 ° 250.00 Hz
I L3 200.0 mA 120.00 ° 250.00 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

I L1
I L3
L2
180° 0°

I(1)-1 I(1)-3

254.0 V -90° 1.0 A


V L2-E 0.000V -120.00°

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

V L3-E 0.000V 120.00°


I L1 0.200A 0.00°
I L2 0.200A -120.00°
I L3 0.200A 120.00°
I(1)-1 1.000A 210.00°
I(1)-2 1.000A 90.00°
I(1)-3 1.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.015s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:24:18
Title: LV2 STABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

V L1-E 0.000V 0.00° +90°


I(1)-2

II L3I L1
180° L2 0°

I(1)-1 I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 210.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:31:26
Title: LV3 UNSTABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Direct V L1-E 0.00 V 0.00 ° 50.000 Hz


V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

II L3I L1 I(1)-1
180° L2 0°

I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 0.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.028s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
TESTED BY VERIFIED BY WITNESSED BY
CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Assessment
Passed 26-Dec-2023 21:32:55
Title: LV3 MEASUREMENT
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2
I L3

I(1)-1
I L1
180° 0°

I L2 I(1)-3

254.0 V -90° 1.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 1.000A 0.00°
I L2 1.000A -120.00°
I L3 1.000A 120.00°
I(1)-1 1.000A 0.00°
I(1)-2 1.000A 90.00°
I(1)-3 1.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Analog Inputs
VDCin IDCin
n/a n/a

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:35:06
Title: LV3 STABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

L3I L1
II L2
180° 0°

I(1)-1 I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 210.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Trip 0
Start 0
Overload 0

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:36:25
Title: LV3 UNSTABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

II L3I L1 I(1)-1
180° L2 0°

I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 0.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.027s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:37:19
Title: LV4 MEASUREMENT
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2
I L3

I(1)-1
I L1
180° 0°

I L2 I(1)-3

254.0 V -90° 1.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 1.000A 0.00°

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

I L2 1.000A -120.00°
I L3 1.000A 120.00°
I(1)-1 1.000A 0.00°
I(1)-2 1.000A 90.00°
I(1)-3 1.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:40:26
Title: LV4 STABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

V L1-E 0.000V 0.00° +90°


I(1)-2

II L3I L1
180° L2 0°

I(1)-1 I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 210.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Start 0
Overload 0

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:41:12
Title: LV4 UNSTABLE
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Direct V L1-E 0.00 V 0.00 ° 50.000 Hz


V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 874.0 mA 0.00 ° 50.000 Hz
I L2 874.0 mA -120.00 ° 50.000 Hz
I L3 874.0 mA 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°
I(1)-2

II L3I L1 I(1)-1
180° L2 0°

I(1)-3

254.0 V -90° 4.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.874A 0.00°
I L2 0.874A -120.00°
I L3 0.874A 120.00°
I(1)-1 3.340A 0.00°
I(1)-2 3.340A 90.00°
I(1)-3 3.340A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.028s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
TESTED BY VERIFIED BY WITNESSED BY
CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Assessment
Passed 26-Dec-2023 21:42:37
Title: I> 1 2 TIMES
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 2.400 A 0.00 ° 50.000 Hz
I L2 2.400 A -120.00 ° 50.000 Hz
I L3 2.400 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I L3
I L1
180° 0°

I L2

254.0 V -90° 3.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 2.400A 0.00°
I L2 2.400A -120.00°
I L3 2.400A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 1.028s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:45:12
Title: I> 1 5 TIMES
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 6.000 A 0.00 ° 50.000 Hz
I L2 6.000 A -120.00 ° 50.000 Hz
I L3 6.000 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I L3
I L1
180° 0°
I L2

254.0 V -90° 8.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 6.000A 0.00°
I L2 6.000A -120.00°
I L3 6.000A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Trip 0->1 0.440s


Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:45:46
Title: I> 3
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 10.10 A 0.00 ° 50.000 Hz
I L2 10.10 A -120.00 ° 50.000 Hz
I L3 10.10 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I L3
I L1
180° 0°
I L2

254.0 V -90° 15.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 10.100A 0.00°
I L2 10.100A -120.00°
I L3 10.100A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
TESTED BY VERIFIED BY WITNESSED BY
CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.072s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:46:32
Title: IN> 1 2 TIMES
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 800.0 mA 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I L1
180° 0°

254.0 V -90° 800.0 mA


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 0.800A 0.00°
I L2 0.000A -120.00°

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

I L3 0.000A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 1.022s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:47:12
Title: IN> 1 5 TIMES
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz
V L2-E 0.00 V -120.00 ° 50.000 Hz
V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 2.000 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

V L1-E 0.000V 0.00° +90°

I L1
180° 0°

254.0 V -90° 2.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 2.000A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.448s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 26-Dec-2023 21:47:41
Title: IN> 3
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 0.00 V 0.00 ° 50.000 Hz

TESTED BY VERIFIED BY WITNESSED BY


CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

V L2-E 0.00 V -120.00 ° 50.000 Hz


V L3-E 0.00 V 120.00 ° 50.000 Hz
I L1 10.10 A 0.00 ° 50.000 Hz
I L2 0.00 A -120.00 ° 50.000 Hz
I L3 0.00 A 120.00 ° 50.000 Hz
Generator Settings
V L1-E 0.000V 0.00° +90°

I L1
180° 0°

254.0 V -90° 15.0 A


V L2-E 0.000V -120.00°
V L3-E 0.000V 120.00°
I L1 10.100A 0.00°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(1)-1 0.000A 210.00°
I(1)-2 0.000A 90.00°
I(1)-3 0.000A 330.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 0.064s
Start 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
n/a n/a
.
Comment

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
TESTED BY VERIFIED BY WITNESSED BY
CLIENT : TATA POWER (120 MW AKKALKOT SOLAR PARK)
PROJECT : ANNUAL MAINTENANCE TESTING
PAGE No. :

Passed 26-Dec-2023 21:48:11

Comment
Summary
26 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

2. Functional Check:

S.no Parameters Checked


1 Auxiliary Supply Ok
2 Relay Earth Connection Ok
3 LED operations Ok
4 Power up relay and check relay healthy Ok

3. Remarks:
 Alstom P645 relay to master trip relay wires were not terminated because H1 and H2 contacts
were found faulty internally (Permanently NC).
 Relay contacts G9 and G10 re-configured for NO and master trip relay wires are terminated at G9
and G10.
 Primary and secondary injection tests were carried out to check for breaker tripping.
 Breaker found to be tripped in primary injection and secondary injection
 Thus, issue got resolved.

TESTED BY VERIFIED BY WITNESSED BY