You are on page 1of 32

Test Object - Device Settings

Substation/Bay:
Substation: Substation address:
Bay: Bay address:

Device:
Name/description: Transformer Differential Relay Manufacturer: Siemens
Device type: 7UT86 Device address:
Serial/model number: BM2007010236
Additional info 1:
Additional info 2:

Hardware Config

Test Equipment
Type Serial Number
CMC256-6 HH570R

Hardware Check
Performed At Result Details
9/24/2020 10:53:20 Passed
AM

Stability Test:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:36:40 Test End: 24-Sep-2020 12:37:23
User Name: Manager:
Company:

Test Results

Title: ATR Stability Test

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 2.060 A 0.00 ° 50.000 Hz
I L2 2.060 A -120.00 ° 50.000 Hz
I L3 2.060 A 120.00 ° 50.000 Hz

Generator Settings
I L1 2.060A 0.00° +90°
I L2 2.060A -120.00°
I(2)-2
I L3 2.060A 120.00°
I L3
I(2)-1 3.510A 180.00°
I(2)-1 I L1
I(2)-2 3.510A 60.00° 180° 0°
I(2)-3 3.510A 300.00° I L2
I(2)-3
4.0 A -90°

1 / 32
Binary Inputs
Name Slope Time
Bin. in 1 0
Bin. in 2 0
Bin. in 3 0
Bin. in 4 0
Bin. in 5 0
Bin. in 6 0
Bin. in 7 0
Bin. in 8 0
Bin. in 9 0
Bin. in 10 0
Overload 0

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
HV Differential Trip Low Set:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:37:34 Test End: 24-Sep-2020 12:37:51
User Name: Manager:
Company:

Test Results

Title: HV Differential Trip Low Set

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 83.00 mA 0.00 ° 50.000 Hz
I L2 83.00 mA -120.00 ° 50.000 Hz
I L3 83.00 mA 120.00 ° 50.000 Hz

Generator Settings
I L1 0.083A 0.00° +90°
I L2 0.083A -120.00°
I L3
I L3 0.083A 120.00°
I(2)-1 0.000A 180.00°
I L1
I(2)-2 0.000A 60.00° 180° 0°
I(2)-3 0.000A 300.00°
I L2

100.0 mA-90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.035s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

2 / 32
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

HV Differential Trip High Set:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:37:59 Test End: 24-Sep-2020 12:38:07
User Name: Manager:
Company:

Test Results

Title: HV Differential Trip High Set

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 2.474 A 0.00 ° 50.000 Hz
I L2 2.474 A -120.00 ° 50.000 Hz
I L3 2.474 A 120.00 ° 50.000 Hz

Generator Settings
I L1 2.474A 0.00° +90°
I L2 2.474A -120.00°
I L3
I L3 2.474A 120.00°
I(2)-1 0.000A 180.00°
I L1
I(2)-2 0.000A 60.00° 180° 0°
I(2)-3 0.000A 300.00°
I L2

3.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.025s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
LV Differential Trip Low Set:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:38:15 Test End: 24-Sep-2020 12:38:23
User Name: Manager:
Company:

Test Results
3 / 32
Title: LV Differential Trip Low Set

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00° I(2)-2
I L3 0.000A 120.00°
I(2)-1 0.141A 180.00°
I(2)-1
I(2)-2 0.141A 60.00° 180° 0°
I(2)-3 0.141A 300.00°

I(2)-3
150.0 mA-90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.034s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
LV Differential Trip High Set:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:38:30 Test End: 24-Sep-2020 12:38:38
User Name: Manager:
Company:

Test Results

Title: LV Differential Trip High Set

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

4 / 32
Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00° I(2)-2
I L3 0.000A 120.00°
I(2)-1 3.590A 180.00°
I(2)-1
I(2)-2 3.590A 60.00° 180° 0°
I(2)-3 3.590A 300.00°

I(2)-3
4.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.031s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Slope/Trip Time Test: L1:

Test Object - Differential Parameters

Protected Object:
Protected Object: Transformer
Vector Group: YY0
Winding/Leg Name: Primary Secondary
Voltage: 525.00 kV 231.00 kV
Power: 450.00 MVA 450.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No

CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 1200.00 A 1600.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: 200.00 A 800.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a

5 / 32
Protection device:
Reference Winding: Primary
Ibias Calculation: max ( Ip, Is ) (K1 = 1.00)
Zero Seq. Elimination: IL-I0
Reference Current: PO nominal current
Ground CT Used: No
Disable Comb. char.: No

Idiff>: 0.20 In tdiff>: 0.03 s


Idiff>>: 5.00 In tdiff>>: 0.03 s

Itol rel: 2.00 % ttol rel: 3.00 %


Itol abs: 0.05 In ttol abs: 0.01 s

Test Module
Name: OMICRON Diff Operating Version: 4.10
Characteristic
Test Start: 24-Sep-2020 12:38:49 Test End: 24-Sep-2020 12:39:45
User Name: Manager:
Company:

Test Settings:
Testing: Primary / Secondary
Max. Test Time: 10.00 s Delay Time: 0.25 s
Prefault: No
Prefault current: 0.00 In Prefault time: 0.000 s
Vout enabled: No Vout winding: Primary
Time-triggered: No Winding/leg output: Primary

Binary Outputs
Bin. out 1: 0
Bin. out 2: 0
Bin. out 3: 0
Bin. out 4: 0

Test Results for Fault Type L1-E at Reference Side Primary


Nominal Actual Trip
Idiff Ibias State Result
Trip Time Time
0.30 In 1.60 In N/T N/T Tested Passed
1.30 In 4.80 In N/T N/T Tested Passed
1.70 In 5.60 In N/T N/T Tested Passed
4.00 In 8.90 In N/T N/T Tested Passed
4.90 In 9.30 In 0.0300 s 0.0322 s Tested Passed
3.20 In 6.90 In 0.0300 s 0.0323 s Tested Passed
1.60 In 4.70 In 0.0300 s 0.0326 s Tested Passed
0.40 In 1.00 In 0.0300 s 0.0342 s Tested Passed
5.40 In 2.50 In 0.0300 s 0.0288 s Tested Passed

6 / 32
Operating Characteristic Diagram
Idiff [In]

5.0

4.0

3.0

2.0

1.0

0.0
1 2 3 4 5 6 7 8 9 10 11
Ibias [In]

Shot 1 2 3 4 5 6
Idiff: 0.30 In 1.30 In 1.70 In 4.00 In 4.90 In 3.20 In
Ibias: 1.60 In 4.80 In 5.60 In 8.90 In 9.30 In 6.90 In
I Primary L1: 0.660 A 1.979 A 2.309 A 3.670 A 3.835 A 2.846 A
Phase Primary L1: -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 °
I Primary L2: 0.330 A 0.990 A 1.155 A 1.835 A 1.918 A 1.423 A
Phase Primary L2: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Primary L3: 0.330 A 0.990 A 1.155 A 1.835 A 1.918 A 1.423 A
Phase Primary L3: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L1: 0.914 A 2.460 A 2.741 A 3.444 A 3.093 A 2.601 A
Phase Secondary L1: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L2: 0.457 A 1.230 A 1.371 A 1.722 A 1.546 A 1.300 A
Phase Secondary L2: 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 °
I Secondary L3: 0.457 A 1.230 A 1.371 A 1.722 A 1.546 A 1.300 A
Phase Secondary L3: 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 °
I Tertiary L1:
Phase Tertiary L1:
I Tertiary L2:
Phase Tertiary L2:
I Tertiary L3:
Phase Tertiary L3:
V L1:
Phase L1:
V L2:
Phase L2:
V L3:
Phase L3:
Shot 7 8 9
Idiff: 1.60 In 0.40 In 5.40 In
Ibias: 4.70 In 1.00 In 2.50 In
I Primary L1: 1.938 A 0.412 A 1.031 A
Phase Primary L1: -180.000 ° -180.000 ° -180.000 °
I Primary L2: 0.969 A 0.206 A 0.515 A
Phase Primary L2: 0.000 ° 0.000 ° 0.000 °
I Primary L3: 0.969 A 0.206 A 0.515 A
Phase Primary L3: 0.000 ° 0.000 ° 0.000 °
I Secondary L1: 2.179 A 0.422 A 2.039 A
Phase Secondary L1: 0.000 ° 0.000 ° 180.000 °
7 / 32
I Secondary L2: 1.090 A 0.211 A 1.019 A
Phase Secondary L2: 180.000 ° 180.000 ° 0.000 °
I Secondary L3: 1.090 A 0.211 A 1.019 A
Phase Secondary L3: 180.000 ° 180.000 ° 0.000 °
I Tertiary L1:
Phase Tertiary L1:
I Tertiary L2:
Phase Tertiary L2:
I Tertiary L3:
Phase Tertiary L3:
V L1:
Phase L1:
V L2:
Phase L2:
V L3:
Phase L3:

Test State:
Test passed
9 out of 9 points tested.
9 points passed.
0 points failed.
Slope/Trip Time Test: L23:

Test Object - Differential Parameters

Protected Object:
Protected Object: Transformer
Vector Group: YY0
Winding/Leg Name: Primary Secondary
Voltage: 525.00 kV 231.00 kV
Power: 450.00 MVA 450.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No

CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 1200.00 A 1600.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: 200.00 A 800.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a

Protection device:
Reference Winding: Primary
Ibias Calculation: max ( Ip, Is ) (K1 = 1.00)
Zero Seq. Elimination: IL-I0
Reference Current: PO nominal current
Ground CT Used: No
Disable Comb. char.: No

Idiff>: 0.20 In tdiff>: 0.03 s


Idiff>>: 5.00 In tdiff>>: 0.03 s

Itol rel: 2.00 % ttol rel: 3.00 %


Itol abs: 0.05 In ttol abs: 0.01 s

Test Module
Name: OMICRON Diff Operating Version: 4.10
Characteristic
Test Start: 24-Sep-2020 12:40:10 Test End: 24-Sep-2020 12:41:07
User Name: Manager:

8 / 32
Company:

Test Settings:
Testing: Primary / Secondary
Max. Test Time: 10.00 s Delay Time: 0.25 s
Prefault: No
Prefault current: 0.00 In Prefault time: 0.000 s
Vout enabled: No Vout winding: Primary
Time-triggered: No Winding/leg output: Primary

Binary Outputs
Bin. out 1: 0
Bin. out 2: 0
Bin. out 3: 0
Bin. out 4: 0

Test Results for Fault Type L2-L3 at Reference Side Primary


Nominal Actual Trip
Idiff Ibias State Result
Trip Time Time
0.20 In 1.00 In N/T N/T Tested Passed
0.60 In 2.50 In N/T N/T Tested Passed
1.60 In 3.90 In N/T N/T Tested Passed
4.10 In 7.60 In N/T N/T Tested Passed
4.90 In 8.00 In 0.0300 s 0.0323 s Tested Passed
3.20 In 5.70 In 0.0300 s 0.0336 s Tested Passed
1.00 In 2.60 In 0.0300 s 0.0339 s Tested Passed
0.60 In 1.40 In 0.0300 s 0.0334 s Tested Passed
5.40 In 2.70 In 0.0300 s 0.0286 s Tested Passed

Operating Characteristic Diagram


Idiff [In]

5.0

4.0

3.0

2.0

1.0

0.0
1 2 3 4 5 6 7 8 9 10
Ibias [In]

Shot 1 2 3 4 5 6
Idiff: 0.20 In 0.60 In 1.60 In 4.10 In 4.90 In 3.20 In
Ibias: 1.00 In 2.50 In 3.90 In 7.60 In 8.00 In 5.70 In
I Primary L1: 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A
Phase Primary L1: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Primary L2: 0.412 A 1.031 A 1.608 A 3.134 A 3.299 A 2.351 A
Phase Primary L2: -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 °
I Primary L3: 0.412 A 1.031 A 1.608 A 3.134 A 3.299 A 2.351 A

9 / 32
Phase Primary L3: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L1: 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A
Phase Secondary L1: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L2: 0.562 A 1.336 A 1.617 A 2.460 A 2.179 A 1.757 A
Phase Secondary L2: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L3: 0.562 A 1.336 A 1.617 A 2.460 A 2.179 A 1.757 A
Phase Secondary L3: 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 °
I Tertiary L1:
Phase Tertiary L1:
I Tertiary L2:
Phase Tertiary L2:
I Tertiary L3:
Phase Tertiary L3:
V L1:
Phase L1:
V L2:
Phase L2:
V L3:
Phase L3:
Shot 7 8 9
Idiff: 1.00 In 0.60 In 5.40 In
Ibias: 2.60 In 1.40 In 2.70 In
I Primary L1: 0.000 A 0.000 A 0.000 A
Phase Primary L1: 0.000 ° 0.000 ° 0.000 °
I Primary L2: 1.072 A 0.577 A 1.113 A
Phase Primary L2: -180.000 ° -180.000 ° -180.000 °
I Primary L3: 1.072 A 0.577 A 1.113 A
Phase Primary L3: 0.000 ° 0.000 ° 0.000 °
I Secondary L1: 0.000 A 0.000 A 0.000 A
Phase Secondary L1: 0.000 ° 0.000 ° 180.000 °
I Secondary L2: 1.125 A 0.562 A 1.898 A
Phase Secondary L2: 0.000 ° 0.000 ° 180.000 °
I Secondary L3: 1.125 A 0.562 A 1.898 A
Phase Secondary L3: 180.000 ° 180.000 ° 0.000 °
I Tertiary L1:
Phase Tertiary L1:
I Tertiary L2:
Phase Tertiary L2:
I Tertiary L3:
Phase Tertiary L3:
V L1:
Phase L1:
V L2:
Phase L2:
V L3:
Phase L3:

Test State:
Test passed
9 out of 9 points tested.
9 points passed.
0 points failed.
Slope/Trip Time Test: L123:

Test Object - Differential Parameters

10 / 32
Protected Object:
Protected Object: Transformer
Vector Group: YY0
Winding/Leg Name: Primary Secondary
Voltage: 525.00 kV 231.00 kV
Power: 450.00 MVA 450.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No

CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 1200.00 A 1600.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: 200.00 A 800.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a

Protection device:
Reference Winding: Primary
Ibias Calculation: max ( Ip, Is ) (K1 = 1.00)
Zero Seq. Elimination: IL-I0
Reference Current: PO nominal current
Ground CT Used: No
Disable Comb. char.: No

Idiff>: 0.20 In tdiff>: 0.03 s


Idiff>>: 5.00 In tdiff>>: 0.03 s

Itol rel: 2.00 % ttol rel: 3.00 %


Itol abs: 0.05 In ttol abs: 0.01 s

Test Module
Name: OMICRON Diff Operating Version: 4.10
Characteristic
Test Start: 24-Sep-2020 12:41:20 Test End: 24-Sep-2020 12:42:17
User Name: Manager:
Company:

Test Settings:
Testing: Primary / Secondary
Max. Test Time: 10.00 s Delay Time: 0.25 s
Prefault: No
Prefault current: 0.00 In Prefault time: 0.000 s
Vout enabled: No Vout winding: Primary
Time-triggered: No Winding/leg output: Primary

Binary Outputs
Bin. out 1: 0
Bin. out 2: 0
Bin. out 3: 0
Bin. out 4: 0

Test Results for Fault Type L1-L2-L3 at Reference Side Primary

11 / 32
Nominal Actual Trip
Idiff Ibias State Result
Trip Time Time
0.20 In 1.00 In N/T N/T Tested Passed
0.60 In 2.50 In N/T N/T Tested Passed
1.60 In 3.90 In N/T N/T Tested Passed
4.10 In 7.60 In N/T N/T Tested Passed
4.90 In 8.00 In 0.0300 s 0.0331 s Tested Passed
3.20 In 5.70 In 0.0300 s 0.0329 s Tested Passed
1.00 In 2.60 In 0.0300 s 0.0336 s Tested Passed
0.60 In 1.40 In 0.0300 s 0.0329 s Tested Passed
5.40 In 2.70 In 0.0300 s 0.0288 s Tested Passed

Operating Characteristic Diagram


Idiff [In]

5.0

4.0

3.0

2.0

1.0

0.0
1 2 3 4 5 6 7 8 9 10
Ibias [In]

Shot 1 2 3 4 5 6
Idiff: 0.20 In 0.60 In 1.60 In 4.10 In 4.90 In 3.20 In
Ibias: 1.00 In 2.50 In 3.90 In 7.60 In 8.00 In 5.70 In
I Primary L1: 0.412 A 1.031 A 1.608 A 3.134 A 3.299 A 2.351 A
Phase Primary L1: -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 °
I Primary L2: 0.412 A 1.031 A 1.608 A 3.134 A 3.299 A 2.351 A
Phase Primary L2: 60.000 ° 60.000 ° 60.000 ° 60.000 ° 60.000 ° 60.000 °
I Primary L3: 0.412 A 1.031 A 1.608 A 3.134 A 3.299 A 2.351 A
Phase Primary L3: -60.000 ° -60.000 ° -60.000 ° -60.000 ° -60.000 ° -60.000 °
I Secondary L1: 0.562 A 1.336 A 1.617 A 2.460 A 2.179 A 1.757 A
Phase Secondary L1: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L2: 0.562 A 1.336 A 1.617 A 2.460 A 2.179 A 1.757 A
Phase Secondary L2: -120.000 ° -120.000 ° -120.000 ° -120.000 ° -120.000 ° -120.000 °
I Secondary L3: 0.562 A 1.336 A 1.617 A 2.460 A 2.179 A 1.757 A
Phase Secondary L3: 120.000 ° 120.000 ° 120.000 ° 120.000 ° 120.000 ° 120.000 °
I Tertiary L1:
Phase Tertiary L1:
I Tertiary L2:
Phase Tertiary L2:
I Tertiary L3:
Phase Tertiary L3:
V L1:
Phase L1:
V L2:
Phase L2:
V L3:

12 / 32
Phase L3:
Shot 7 8 9
Idiff: 1.00 In 0.60 In 5.40 In
Ibias: 2.60 In 1.40 In 2.70 In
I Primary L1: 1.072 A 0.577 A 1.113 A
Phase Primary L1: -180.000 ° -180.000 ° -180.000 °
I Primary L2: 1.072 A 0.577 A 1.113 A
Phase Primary L2: 60.000 ° 60.000 ° 60.000 °
I Primary L3: 1.072 A 0.577 A 1.113 A
Phase Primary L3: -60.000 ° -60.000 ° -60.000 °
I Secondary L1: 1.125 A 0.562 A 1.898 A
Phase Secondary L1: 0.000 ° 0.000 ° 180.000 °
I Secondary L2: 1.125 A 0.562 A 1.898 A
Phase Secondary L2: -120.000 ° -120.000 ° 60.000 °
I Secondary L3: 1.125 A 0.562 A 1.898 A
Phase Secondary L3: 120.000 ° 120.000 ° -60.000 °
I Tertiary L1:
Phase Tertiary L1:
I Tertiary L2:
Phase Tertiary L2:
I Tertiary L3:
Phase Tertiary L3:
V L1:
Phase L1:
V L2:
Phase L2:
V L3:
Phase L3:

Test State:
Test passed
9 out of 9 points tested.
9 points passed.
0 points failed.
HV O/C Inverse:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:45:20 Test End: 24-Sep-2020 12:46:14
User Name: Manager:
Company:

Test Results

Title: HV O/C Inverse

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.480 A 0.00 ° 50.000 Hz
I L2 1.480 A -120.00 ° 50.000 Hz
I L3 1.480 A 120.00 ° 50.000 Hz

13 / 32
Generator Settings
I L1 1.480A 0.00° +90°
I L2 1.480A -120.00° I L3
I L3 1.480A 120.00°
I(2)-1 0.000A 180.00°
I L1
I(2)-2 0.000A 60.00° 180° 0°
I(2)-3 0.000A 300.00°

I L2
1.5 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 2.013s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

HV E/F Inverse:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:46:22 Test End: 24-Sep-2020 12:46:47
User Name: Manager:
Company:

Test Results

Title: HV E/F Inverse

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 288.0 mA 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.288A 0.00° +90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(2)-1 0.000A 180.00°
I L1
I(2)-2 0.000A 60.00° 180° 0°
I(2)-3 0.000A 300.00°

300.0 mA-90°

Binary Inputs
Name Slope Time

14 / 32
Bin. in 1 0->1 4.033s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
HV O/C E/F Instantaneous :

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:46:55 Test End: 24-Sep-2020 12:47:20
User Name: Manager:
Company:

Test Results

Title: HV O/C Instantaneous

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 4.070 A 0.00 ° 50.000 Hz
I L2 4.070 A -120.00 ° 50.000 Hz
I L3 4.070 A 120.00 ° 50.000 Hz

Generator Settings
I L1 4.070A 0.00° +90°
I L2 4.070A -120.00°
I L3
I L3 4.070A 120.00°
I(2)-1 0.000A 180.00°
I L1
I(2)-2 0.000A 60.00° 180° 0°
I(2)-3 0.000A 300.00°
I L2

5.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.038s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Title: HV E/F Instantaneous

15 / 32
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 4.070 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 4.070A 0.00° +90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(2)-1 0.000A 180.00°
I L1
I(2)-2 0.000A 60.00° 180° 0°
I(2)-3 0.000A 300.00°

5.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.037s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
LV O/C Inverse:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:47:28 Test End: 24-Sep-2020 12:47:39
User Name: Manager:
Company:

Test Results

Title: LV O/C Inverse

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

16 / 32
Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00°
I L3 0.000A 120.00° I(2)-2
I(2)-1 2.250A 180.00°
I(2)-1
I(2)-2 2.250A 60.00° 180° 0°
I(2)-3 2.250A 300.00°
I(2)-3

3.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 2.016s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
LV E/F Inverse:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:47:46 Test End: 24-Sep-2020 12:48:36
User Name: Manager:
Company:

Test Results

Title: LV E/F Inverse

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00°
I L3 0.000A 120.00°
I(2)-1 0.352A 180.00°
I(2)-1
I(2)-2 0.000A 60.00° 180° 0°
I(2)-3 0.000A 300.00°

400.0 mA-90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 3.520s

17 / 32
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
LV Cross Trip:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:48:45 Test End: 24-Sep-2020 12:49:31
User Name: Manager:
Company:

Test Results

Title: Cross Trip Stage-1

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00°
I(2)-2
I L3 0.000A 120.00°
I(2)-1 3.200A 180.00°
I(2)-1
I(2)-2 3.200A 60.00° 180° 0°
I(2)-3 3.200A 300.00°
I(2)-3

4.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 1->0 n/a
Bin. in 2 0->1 1.027s
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Title: Cross Trip Stage-2

Fault Calculator:
18 / 32
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00° I(2)-2
I L3 0.000A 120.00°
I(2)-1 3.700A 180.00°
I(2)-1
I(2)-2 3.700A 60.00° 180° 0°
I(2)-3 3.700A 300.00°

I(2)-3
4.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 1->0 n/a
Bin. in 2 0->1 0.519s
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Neutral E/F:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:49:39 Test End: 24-Sep-2020 12:50:12
User Name: Manager:
Company:

Test Results

Title: Neutral EF

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 220.0 mA 0.00 ° 50.000 Hz

Generator Settings
I L1 0.220A 0.00° +90°

I L1
180° 0°

300.0 mA-90°

Binary Inputs

19 / 32
Name Slope Time
Bin. in 1 0->1 1.531s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Tertiary O/C:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:50:20 Test End: 24-Sep-2020 12:50:43
User Name: Manager:
Company:

Test Results

Title: Tertiary O/C

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 510.0 mA 0.00 ° 50.000 Hz

Generator Settings
I L1 0.510A 0.00° +90°

I L1
180° 0°

600.0 mA-90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 1.327s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Tertiary E/F:
20 / 32
Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:50:51 Test End: 24-Sep-2020 12:51:07
User Name: Manager:
Company:

Test Results

Title: Tertiary E/F

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 220.0 mA 0.00 ° 50.000 Hz

Generator Settings
I L1 0.220A 0.00° +90°

I L1
180° 0°

300.0 mA-90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 1.332s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Thermal Overload:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:51:26 Test End: 24-Sep-2020 12:54:32
User Name: Manager:
Company:

Test Results

Title: Thermal Overload (Without Pre Load)

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz

21 / 32
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00°
I L3 0.000A 120.00° I(2)-2
I(2)-1 1.054A 180.00°
I(2)-1
I(2)-2 1.054A 60.00° 180° 0°
I(2)-3 1.054A 300.00°
I(2)-3

1.5 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 46.419s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Title: Thermal Overload (With Pre Load)

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 0.000 A 0.00 ° 50.000 Hz
I L2 0.000 A -120.00 ° 50.000 Hz
I L3 0.000 A 120.00 ° 50.000 Hz

Generator Settings
I L1 0.000A 0.00° +90°
I L2 0.000A -120.00°
I L3 0.000A 120.00° I(2)-2
I(2)-1 1.054A 180.00°
I(2)-1
I(2)-2 1.054A 60.00° 180° 0°
I(2)-3 1.054A 300.00°
I(2)-3

1.5 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 11.044s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
22 / 32
Test passed

LV REF:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 12:58:59 Test End: 24-Sep-2020 13:01:20
User Name: Manager:
Company:

Test Results

Title: External Fault

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz

Generator Settings
I L1 1.000A 0.00° +90°
I(2)-1 1.000A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I(2)-1
I L1
180° 0°

1.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0
Bin. in 2 0
Bin. in 3 0
Bin. in 4 0
Bin. in 5 0
Bin. in 6 0
Bin. in 7 0
Bin. in 8 0
Bin. in 9 0
Bin. in 10 0
Overload 0

Title: Internall Fault

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz

Generator Settings
I L1 1.000A 0.00° +90°
I(2)-1 1.000A 180.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I(2)-1 I L1
180° 0°

1.0 A -90°

23 / 32
Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.037s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Title: Internall Fault below threshold

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 140.0 mA 180.00 ° 50.000 Hz

Generator Settings
I L1 0.140A 180.00° +90°
I(2)-1 2.000A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

2.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0
Bin. in 2 0
Bin. in 3 0
Bin. in 4 0
Bin. in 5 0
Bin. in 6 0
Bin. in 7 0
Bin. in 8 0
Bin. in 9 0
Bin. in 10 0
Overload 0

Title: Internall Fault above threshold

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 145.0 mA 180.00 ° 50.000 Hz

24 / 32
Generator Settings
I L1 0.145A 180.00° +90°
I(2)-1 0.145A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

150.0 mA-90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.036s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Title: Internall Fault below slope

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 145.0 mA 180.00 ° 50.000 Hz

Generator Settings
I L1 0.145A 180.00° +90°
I(2)-1 2.000A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

2.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0
Bin. in 2 0
Bin. in 3 0
Bin. in 4 0
Bin. in 5 0
Bin. in 6 0
Bin. in 7 0
Bin. in 8 0
Bin. in 9 0
Bin. in 10 0
Overload 0

Title: Internall Fault above slope

Fault Calculator:

25 / 32
Table Inputmode Parameters (All values are secondary)
Direct I L1 160.0 mA 180.00 ° 50.000 Hz

Generator Settings
I L1 0.160A 180.00° +90°
I(2)-1 2.000A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

2.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.037s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
6 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
HV REF:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 13:01:29 Test End: 24-Sep-2020 13:04:37
User Name: Manager:
Company:

Test Results

Title: External Fault

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz

Generator Settings
I L1 1.000A 0.00° +90°
I(2)-1 1.000A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I(2)-1
I L1
180° 0°

1.0 A -90°

Binary Inputs
Name Slope Time

26 / 32
Bin. in 1 0
Bin. in 2 0
Bin. in 3 0
Bin. in 4 0
Bin. in 5 0
Bin. in 6 0
Bin. in 7 0
Bin. in 8 0
Bin. in 9 0
Bin. in 10 0
Overload 0

Title: Internal Fault

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 180.00 ° 50.000 Hz

Generator Settings
I L1 1.000A 180.00° +90°
I(2)-1 1.000A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

1.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.034s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Title: Internal Fault below threshold

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 140.0 mA 180.00 ° 50.000 Hz

Generator Settings
I L1 0.140A 180.00° +90°
I(2)-1 2.000A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

2.0 A -90°

27 / 32
Binary Inputs
Name Slope Time
Bin. in 1 0
Bin. in 2 0
Bin. in 3 0
Bin. in 4 0
Bin. in 5 0
Bin. in 6 0
Bin. in 7 0
Bin. in 8 0
Bin. in 9 0
Bin. in 10 0
Overload 0

Title: Internal Fault above threshold

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 145.0 mA 180.00 ° 50.000 Hz

Generator Settings
I L1 0.145A 180.00° +90°
I(2)-1 0.145A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

150.0 mA-90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.034s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Title: Internal Fault below slope

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 160.0 mA 180.00 ° 50.000 Hz

28 / 32
Generator Settings
I L1 0.160A 180.00° +90°
I(2)-1 2.900A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

3.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0
Bin. in 2 0
Bin. in 3 0
Bin. in 4 0
Bin. in 5 0
Bin. in 6 0
Bin. in 7 0
Bin. in 8 0
Bin. in 9 0
Bin. in 10 0
Overload 0

Title: Internal Fault above slope

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 160.0 mA 180.00 ° 50.000 Hz

Generator Settings
I L1 0.160A 180.00° +90°
I(2)-1 2.700A 0.00°
I(2)-2 0.000A -120.00°
I(2)-3 0.000A 120.00°
I L1 I(2)-1
180° 0°

3.0 A -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.032s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a
Overload 1->0 n/a

Summary
6 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Overexcitation:
29 / 32
Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 13:04:46 Test End: 24-Sep-2020 13:07:52
User Name: Manager:
Company:

Test Results

Title: Over Excitation Trip-2

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L2-E 103.0 V 0.00 ° 50.000 Hz

Generator Settings
V L2-E 103.000V 0.00° +90°

V L2-E
180° 0°

150.0 V -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 7.883s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a

Title: Over Excitation Trip-1

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L2-E 100.0 V 0.00 ° 50.000 Hz

Generator Settings
V L2-E 100.000V 0.00° +90°

V L2-E
180° 0°

100.0 V -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 10.127s

30 / 32
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a

Summary
2 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Over Voltage:

Test Module
Name: OMICRON QuickCMC Version: 4.10
Test Start: 24-Sep-2020 13:08:33 Test End: 24-Sep-2020 13:10:13
User Name: Manager:
Company:

Test Results

Title: Over Voltage High Set

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L2-E 89.00 V 0.00 ° 50.000 Hz

Generator Settings
V L2-E 89.000V 0.00° +90°

V L2-E
180° 0°

100.0 V -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 0.035s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a

Title: Over Voltage Low Set

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L2-E 76.50 V 0.00 ° 50.000 Hz

31 / 32
Generator Settings
V L2-E 76.500V 0.00° +90°

V L2-E
180° 0°

80.0 V -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 10.024s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a

Title: Over Voltage Inverse

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L2-E 75.50 V 0.00 ° 50.000 Hz

Generator Settings
V L2-E 75.500V 0.00° +90°

V L2-E
180° 0°

80.0 V -90°

Binary Inputs
Name Slope Time
Bin. in 1 0->1 37.983s
Bin. in 2 1->0 n/a
Bin. in 3 1->0 n/a
Bin. in 4 1->0 n/a
Bin. in 5 1->0 n/a
Bin. in 6 1->0 n/a
Bin. in 7 1->0 n/a
Bin. in 8 1->0 n/a
Bin. in 9 1->0 n/a
Bin. in 10 1->0 n/a

Summary
3 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

32 / 32