TR.12500. MTRP.01530
Title:
Annual protection
maintenance on 10MVA,
132/33/11kV Transformer
T1 at Chavuma substation
Date:
01/08/2022
List of Tables
EXECUTIVE SUMMARY
The scope of work involved testing the Protection Relays to prove the availability and
integrity of the protection scheme as well as confirming the trip paths. The
protection relays were tested in line with the technical instruction
TR.12400.TCH.00145. Secondary injection were done to verify the operation of the
protection elements for both pickup and time against the implemented settings. The
secondary injection test set CMC 356 was used for secondary injections in the IEDs.
Work order number 58936600.
1.0 INTRODUCTION
Transformer differential protection is implemented in the RET670 Relay, and the secondary
injection test results are shown below,
HV_MV_L1_L2_L3:
Protected Object:
Protected Object: Transformer
Vector Group: DY1
Winding/Leg Name: Primary Secondary
Voltage: 132.00 kV 33.00 kV
Power: 10.00 MVA 10.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No
CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 100.00 A 400.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: 200.00 A 800.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a
. .
Test Module
Name: OMICRON Diff Operating Version: 4.00
Characteristic
Test Start: 01-Aug-2022 12:57:31 Test End: 01-Aug-2022 12:57:58
User Name: Manager:
Company:
.
Test State:
Test passed
HV_MV_L1_L2:
Protected Object:
Protected Object: Transformer
Vector Group: DY1
Winding/Leg Name: Primary Secondary
Voltage: 132.00 kV 33.00 kV
Power: 10.00 MVA 10.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No
CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 100.00 A 400.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: n/ A 400.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a
. .
Test Module
Name: OMICRON Diff Operating Version: 4.00
Characteristic
Test Start: 01-Aug-2022 12:48:50 Test End: 01-Aug-2022 12:49:13
User Name: Manager:
Company:
Shot 1 2 3 4 5 6
Idiff: 0.50 In 0.20 In 0.20 In 2.50 In 1.60 In 0.90 In
Ibias: 3.40 In 0.80 In 2.40 In 3.40 In 2.30 In 1.30 In
I Primary L1: 1.487 A 0.350 A 1.050 A 1.487 A 1.006 A 0.569 A
Phase Primary L1: -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 °
I Primary L2: 1.487 A 0.350 A 1.050 A 1.487 A 1.006 A 0.569 A
Phase Primary L2: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Primary L3: 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A
Phase Primary L3: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L1: 0.732 A 0.152 A 0.556 A 0.227 A 0.177 A 0.101 A
Phase Secondary L1: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
I Secondary L2: 1.465 A 0.303 A 1.111 A 0.455 A 0.354 A 0.202 A
Phase Secondary L2: 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 ° 180.000 °
I Secondary L3: 0.732 A 0.152 A 0.556 A 0.227 A 0.177 A 0.101 A
Phase Secondary L3: 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 ° 0.000 °
.
Test State:
Test passed
HV_MV_L1-E:
Protected Object:
Protected Object: Transformer
Vector Group: DY1
Winding/Leg Name: Primary Secondary
Voltage: 132.00 kV 33.00 kV
Power: 10.00 MVA 10.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No
CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 100.00 A 400.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: 200.00 A 800.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a
. .
Test Module
Name: OMICRON Diff Operating Version: 4.00
Characteristic
Test Start: 01-Aug-2022 12:35:07 Test End: 01-Aug-2022 12:35:28
User Name: Manager:
Company:
.
Test State:
Test passed
HV_LV_L1-L2-L3
Protected Object:
Protected Object: Transformer
Vector Group: DY1
Winding/Leg Name: Primary Secondary
Voltage: 132.00 kV 11.00 kV
Power: 10.00 MVA 5.00 MVA
Starpoint Grounding: No No
Delta-connected CT: No No
CT:
Winding/Leg Name: Primary Secondary
CT Current Prim: 100.00 A 400.00 A
CT Current Sec: 1.00 A 1.00 A
CT Grounding: tow. Prot. Obj. tow. Prot. Obj.
Gnd CT Prim Current: n/ A 400.00 A
Gnd CT Sec Current: 1.00 A 1.00 A
Gnd CT Grounding: n/a n/a
. .
Test Module
Name: OMICRON Diff Operating Version: 4.00
Characteristic
Test Start: 01-Aug-2022 14:26:39 Test End: 01-Aug-2022 14:27:32
User Name: Manager:
Company:
Shot 1 2 3 4 5 6
Idiff: 0.70 In 0.90 In 2.50 In 0.40 In 0.10 In 2.00 In
Ibias: 4.10 In 1.30 In 3.90 In 2.70 In 0.50 In 3.40 In
I Primary L1: 1.793 A 0.569 A 1.706 A 1.181 A 0.219 A 1.487 A
Phase Primary L1: -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 ° -180.000 °
I Primary L2: 1.793 A 0.569 A 1.706 A 1.181 A 0.219 A 1.487 A
Phase Primary L2: 60.000 ° 60.000 ° 60.000 ° 60.000 ° 60.000 ° 60.000 °
I Primary L3: 1.793 A 0.569 A 1.706 A 1.181 A 0.219 A 1.487 A
Phase Primary L3: -60.000 ° -60.000 ° -60.000 ° -60.000 ° -60.000 ° -60.000 °
I Secondary L1: 4.461 A 0.525 A 1.837 A 3.018 A 0.525 A 1.837 A
Phase Secondary L1: -30.000 ° -30.000 ° -30.000 ° -30.000 ° -30.000 ° -30.000 °
I Secondary L2: 4.461 A 0.525 A 1.837 A 3.018 A 0.525 A 1.837 A
Phase Secondary L2: -150.000 ° -150.000 ° -150.000 ° -150.000 ° -150.000 ° -150.000 °
I Secondary L3: 4.461 A 0.525 A 1.837 A 3.018 A 0.525 A 1.837 A
Phase Secondary L3: 90.000 ° 90.000 ° 90.000 ° 90.000 ° 90.000 ° 90.000 °
.
.
Test State:
Test passed
F51_0C_RET670_HV:
Test Object - Overcurrent Parameters
.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I #1 Phase IEC Normal Inverse 0.62 Iref 0.25 0.95 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 4.00
Test Start: 01-Aug-2022 14:46:37 Test End: 01-Aug-2022 14:47:37
User Name: Manager:
Company:
.
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 I #1 Phase 1.452 900.0 m A n/a 4.678 s 4.730 s 1.114 % No Passed
L1-L2 I #1 Phase 3.065 1.900 A n/a 1.545 s 1.584 s 2.497 % No Passed
L1-L2 I #1 Phase 4.677 2.900 A n/a 1.117 s 1.148 s 2.809 % No Passed
L1-L2 I #1 Phase 6.290 3.900 A n/a 934.2 ms 968.2 ms 3.639 % No Passed
L1-L2 I #1 Phase 7.903 4.900 A n/a 829.1 ms 857.2 ms 3.383 % No Passed
L2-L3 I #1 Phase 1.452 900.0 m A n/a 4.678 s 4.743 s 1.383 % No Passed
L2-L3 I #1 Phase 3.065 1.900 A n/a 1.545 s 1.577 s 2.044 % No Passed
L2-L3 I #1 Phase 4.677 2.900 A n/a 1.117 s 1.147 s 2.710 % No Passed
L2-L3 I #1 Phase 6.290 3.900 A n/a 934.2 ms 966.1 ms 3.414 % No Passed
L2-L3 I #1 Phase 7.903 4.900 A n/a 829.1 ms 862.5 ms 4.023 % No Passed
L3-L1 I #1 Phase 1.452 900.0 m A n/a 4.678 s 4.729 s 1.082 % No Passed
L3-L1 I #1 Phase 3.065 1.900 A n/a 1.545 s 1.584 s 2.477 % No Passed
L3-L1 I #1 Phase 4.677 2.900 A n/a 1.117 s 1.153 s 3.211 % No Passed
L3-L1 I #1 Phase 6.290 3.900 A n/a 934.2 ms 965.5 ms 3.350 % No Passed
L3-L1 I #1 Phase 7.903 4.900 A n/a 829.1 ms 856.8 ms 3.335 % No Passed
L1-L2-L3 I #1 Phase 1.452 900.0 m A n/a 4.678 s 4.722 s 0.9277 % No Passed
L1-L2-L3 I #1 Phase 3.065 1.900 A n/a 1.545 s 1.582 s 2.400 % No Passed
L1-L2-L3 I #1 Phase 4.677 2.900 A n/a 1.117 s 1.149 s 2.835 % No Passed
L1-L2-L3 I #1 Phase 6.290 3.900 A n/a 934.2 ms 966.2 ms 3.425 % No Passed
L1-L2-L3 I #1 Phase 7.903 4.900 A n/a 829.1 ms 861.9 ms 3.950 % No Passed
.
Charts for Fault
Types:
Type Angle
L1-L2 n/a
t/s
F51_0C_RET670_MV:
Test Object - Overcurrent Parameters
.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I #1 Phase IEC Normal Inverse 0.52 Iref 0.20 0.95 Non Directional
. .
Test Module
Name: OMICRON Overcurrent Version: 4.00
Test Start: 01-Aug-2022 15:11:35 Test End: 01-Aug-2022 15:12:31
User Name: Manager:
Company:
F51_0C_RET670_LV:
Test Object - Overcurrent Parameters
.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I #1 Phase IEC Normal Inverse 0.78 Iref 0.20 0.95 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 4.00
Test Start: 01-Aug-2022 15:01:38 Test End: 01-Aug-2022 15:02:40
User Name: Manager:
Company:
The electrical and mechanical protection trip matrix is shown in table below.
5.0 CONCLUSION
Routine annual maintenance on the protection system on 10MVA, 132/33/11KV
Transformer T1 at Chavuma substation was successfully carried out and the test
results are within the acceptable limits. Winding and oil temperature trip the unit
instead of offloading the unit,need to review the tripping philosophy.