The relay LCD Display should ON with backlit on & VA burden tolerances are
1) Should be <15 Watt for DC and <24 VA for AC – Relay with LAN card
1.1 VA Burden Test on DC auxiliary supply:
Measured Measured
Test Voltage Range Test Voltage Result
Current (A) Wattage (W)
Lower Nominal 19.20 VDC 0.55 10.56 OK
Upper Nominal 276.00 VDC 0.031 8.55 OK
2.1 Observe secondary current value on Relay Display & RTV2 Software: (CT secondary 1 Amp)
Applied Observed Current (A)
Tolerance
Current A ph. B ph. C ph. N
(A)
(A) Relay RTV2 Relay RTV2 Relay RTV2 Relay RTV2
1.00 0.98-1.02 0.99 0.99 1.00 1.00 0.99 0.99 1.00 1.00
2.2 Observe secondary current value on Relay Display & RTV2 Software: (CT secondary 5 Amp)
Applied Observed Current (A)
Tolerance
Current A ph. B ph. C ph. N
(A)
(A) Relay RTV2 Relay RTV2 Relay RTV2 Relay RTV2
5.00 4.90 – 5.10 5.01 5.01 5.01 5.01 5.01 5.00 5.01 5.02
2.3 Observe secondary voltage value on Relay Display & RTV2 Software:
Applied Observed voltage (VAC)
Tolerance
Voltage A ph. B ph. C ph. N
(VAC)
(VAC) Relay RTV2 Relay RTV2 Relay RTV2 Relay RTV2
63.5 62.23 – 64.77 63.51 63.52 63.57 63.56 63.57 63.56 63.62 63.62
3.1 Observe I1 & I2 current value on Relay Display for CT Polarity Test:
For 1A
Ia 1.000 A 240
Ic 1.000 A 120
For 5A
Ia 5.000 A 0.0
Ib 5.000 A 240 5.00 0.00 5.01 0.01
Ic 5.000 A 120
For
5A
Expected Current (A) Observed Current (A)
Phase Applied Current Phase Angle
I1 I2 I1 I2
Ia 5.000 A 240
Ic 5.000 A 120
3.2 Observe V1 & V2 Voltage value on Relay Display for PT Polarity Test:
FOR CT 1A:
Page 2 of 7
A 1.0 0 63.5 0 0.707 0.642 to 0.766 Trang A= 0.701
FOR CT 5A:
Phase Applied Current Applied Voltage Expected Tolerance Observed Torque
Current Phase Angle Voltage Phase Angle Torque
(A) (Degree) (VAC) (Degree)
FOR CT 1A:
Van=63.5 0
-0.642 to -
N 1.0 0 Vbn=63.5 0 - 0.707 -0.704
0.766
Vcn=63.5 0
FOR CT 5A:
Van=63.5 0
-0.642 to -
N 5.0 0 Vbn=63.5 0 - 0.707 - 0.705
0.766
Vcn=63.5 0
FOR CT 1A:
Page 3 of 7
B 1.0 0 Vbn=63.5 0
C 1.0 0 Vcn=63.5 0
FOR CT 5A:
A 5.0 0 Van=63.5 0
-0.642 to -
B 5.0 0 Vbn=63.5 0 - 0.707 - 0.705
0.766
C 5.0 0 Vcn=63.5 0
4.4 TORQUE ANGLE CHECK FOR NEGATIVE PHASE SEQUENCE [V2] & EF:
FOR CT 1A:
Van=63.5 0
-0.642 to -
N 1.0 0 Vbn=63.5 120 - 0.707 -0.704
0.766
Vcn=63.5 240
4.5 TORQUE ANGLE CHECK FOR NEGATIVE PHASE SEQUENCE [V2] & 3IO:
FOR CT 5A:
A 5.0 0 Van=63.5 0
-0.642 to -
B 5.0 0 Vbn=63.5 120 -0.707 -0.703
0.766
C 5.0 0 Vcn=63.5 240
Test Success criteria: Opto input should ON within +/- 4 volts OR 5% whichever is greater.
Page 4 of 7
for DC ± 4VOLT OR± 5 % ± 4volts OR ± 5% ± 4volts OR ± 5% ± 4volts OR ± 5%
Observed
Bank Details Threshold Voltage Bank Details Result
for DC (V) / Result
1 78 1 OK
2 78 2 OK
3 77 3 OK
Logic Inputs 4 76 Logic Outputs 4 OK
H Bank 5 77 J Bank 5 OK
6 78 6 OK
7 78 7 OK
8 77 8 OK
1 78 Logic Outputs 1 OK
2 76 K Bank 2 OK
3 77
Logic Inputs 4 78
I Bank 5 78
6 77
7 76
8 78
Accuracy for protection function as per ADR244B instruction manual page no. 36, as follows:
CT sec: 1Amp.
Page 5 of 7
Keep Phase, EF & SEF DT= 0s, TMS at X0.02
Observe Operating Value (A)
Curve Select Tolerance (A)
Setting A B C N
IEC S Inv 0.20 0.21 0.21 0.21 0.21 0.20 – 0.22
IEEE M Inv 4.00 4.12 4.11 4.12 4.12 4.00 – 4.40
Definite Time 35.00 35.32 35.34 35.33 35.32 35.00 – 38.50
Applied Expected Time Tolerance Observe Operating Time for phase (Sec)
Result
Current (Sec) (Sec) A ph. B ph. C ph. N
8. HMI Test
TARGET RESET
OK L3 (GREEN AND RED) OK L11(GREEN AND RED) OK
KEY
PROT. RESET KEY OK L6 (GREEN AND RED) OK L14 (GREEN AND RED) OK
- / ▼KEY OK
► KEY OK
9. Communication Test:
Page 6 of 7