a. RELAY DATA:
b. FIELD DATA:
4. MEASUREMENT CHECK:
INOMINAL: 1 A
Hardware
Output Description Remarks
Channel
D2, D3 (NO) OK
1. Watchdog
D2, D4 (NC) OK
Output 1 AUTO D5, D6 (NO) OK
Output 2 UPPER LIMIT REACH D7, D8 (NO) OK
Output 3 LOWER LIMIT REACH D9, D10 (NO) OK
Output 4 AUTO COMMAND FROM SAS E1, E2 (NO) OK
Output 5 MAN. COMMAND FROM SAS E3, E4 (NO) OK
Output 6 UV/OV/OC BLOCK(SPARE) E5, E6 (NO) OK
Output 7 UV TO ABTS G1, G2 (NO) OK
Output 8 SPARE G3, G4 (NO) OK
Output 9 SPARE G5, G6 (NO) OK
Output 10 SPARE G7, G8 (NO) OK
Output 11 SPARE G9, G10 (NO) OK
Output 12 SPARE H1, H2 (NO) OK
9. TIMER CHECK:
TO MEASURE T2, MEASURE THE TOTAL TIME OF T1+T2, THEN FIND T2.
9.3 Run Back Voltage Test: (relay will not see T1 ,will raise instantatly)
Runback Voltage
Runback Voltage value MEASURED Measured time for REMARK
final Setting
corresponding to %Un Voltage (V) T1 CMD (sec) S
(%Un)
110% 126.5 126.5 1.03 OK
Operation time is between 0.5 s and 1.5 s.
Under Voltage final Under Voltage value Measured Pick up Measured Drop off
REMARKS
setting (%Un) corresponding to (%Un) Value (V) Value (V)
80.0 92 92 94.6 OK
Accuracy: ±0.1% or ±50 mV (the greater)
Over current final Over Current value Measured Pick up Measured Drop off
REMARKS
setting (% In) corresponding to (%In) Value (A) Value (A)
120 1.2 1.204 1.186 OK
Accuracy: ±0.1% or ±2 mA (the greater)
Under Voltage final Under Voltage value Measured Pick up Measured Drop off
REMARKS
setting (%Un) corresponding to (%Un) Value (V) Value (V)
144.0 144 144.1 137.3 OK
Accuracy: ±0.1% or ±50 mV (the greater)
Test Equipment:
1-Freja 300
S.NO:1302708
CAL.EXPIRY:26.9.2017
2-Multimeter FLUKE
S.NO:30850238
CAL.EXPIRY:17.11.2017