You are on page 1of 2

SITE INSPECTION AND TEST RECORD

Contract No:
PIC P - 7703
Name of Substation: 10J SUBSTATION
Description: AUX RELAY TEST RESULT
Panel: Location: Page 1 of 2

1. GENERAL DATA AND INFORMATION

Bay Name Relay Ref


Order No. 7PG110 Serial No
Aux. Voltage 110-125 VDC Manufacture ALSTOM-AR111
Contacts 4 NO Reset Type SELF RESET

2. MECHANICAL CHECKS AND VISUAL INSPECTION

ITEM DESCRIPTION STATUS


1 Inspection for physical damage/defects OK
2 Check tightness of all connections OK
3 Verify connections as per approved drawings OK
4 Check Ferrules OK

3. ELECTRICAL TESTS

A) FUNCTION TEST:

ITEM DESCRIPTION STATUS


1 All contacts checked OK
2 All output contacts resistance measured OK
3 Flag operation (if available) checked OK

B) PICK UP AND DROP OFF TEST:

Pick-Up Drop-Off
Voltage (V) Current (A) Voltage (V) Current (A)

Limits:
Minimum operating voltage 70% to 115% of rated voltage
C) PICKUP AND DROPOFF TIME TEST (at 125 V DC)

TESTED BY WITNESSED BY
xx/xx/20xx
ALFANAR T&C SIEMENS MARAFIQ RCA
Name Eng. Eng. Eng. Eng.
Signature
SITE INSPECTION AND TEST RECORD

Contract No:
PIC P - 7703
Name of Substation: 10J SUBSTATION
Description: AUX RELAY TEST RESULT
Panel: Location: Page 2 of 2

Pick-Up Time (ms) Contact Drop-Off Time (ms) Contact


5-7 5-7

Limits:
The operating time is 10ms to 50ms for voltages within the voltage rating (Technical data page 3)

D) RELAY BURDEN TEST:

Voltage (V) Current (mA) Power (W)

Limits:
Relay Burden = 3W (Publication R6050; Technical data page 3)

TESTED BY WITNESSED BY
xx/xx/20xx
ALFANAR T&C SIEMENS MARAFIQ RCA
Name Eng. Eng. Eng. Eng.
Signature