SITE INSPECTION AND TEST RECORD

Description: Contract No ::
ACCEPTANCE TEST FOR CBF RELAY
ABB ( REQ 650 ) 44000040233
Customer: End Client: Sheet:
AL TOUKHI NATIONAL GRID SA Page 1 of 4
Site: Circuit name:
Panel / Designation / Location no.:
S/S 9063 380 / 132 / 33 KV 380 KV CBF-2 PROTECTION
=8BF.C02+R2
PANEL (DIA-C02)

1. GENERAL INFORMATION:
A- Bay (Circuit) data:
Panel NO. 8BF.C02+R2 Circuit Name BF PROTN. RELAY(52CBF2/K230)
CT Ratio 3000/1 AMPS Frequency 60 HZ
B- Relay data:
TYPE REQ 650 VERSION 1.3
Serial No. T1539112 Ordering No 1MRK006518-AD
MAKE ABB SOFTWARE PCM 600
RATED VOLTAGE 125 VDC RATED FREQUENCY 50/60 HZ

2. MECHANICAL CHECK AND VISUAL INSPECTION

Item Description
1 Inspect for physical damage / defects.  Yes  N/A
2 Check tightness of all connections.  Yes  N/A
3. ELECTRICAL TESTS
A. Function Test
Item Description
1 Human Machine Interface [ HMI ] checked.  Yes  N/A
2 Case Earthing checked.  Yes  N/A
3 Indications checked.  Yes  N/A
4 Binary Input checked  Yes  N/A
5 Checked all Binary Output configured as per scheme  Yes  N/A
6 Disturbance Report Function checked  Yes  N/A
7 Watch Dog contact  Yes  N/A
8 Test Switch fn. Checked as per drawing  Yes  N/A
9 Serial no. checked  Yes  N/A

Tested by : ALFANAR (AT&C) Witnessed by :


Name : ESLAM FARID ( SEC ID : FAN-192 ) Name :

Signature & Date :


Signature & Date :
25/10/2016
SITE INSPECTION AND TEST RECORD
Description: Contract No ::
ACCEPTANCE TEST FOR CBF RELAY
ABB ( REQ 650 ) 44000040233
Customer: End Client: Sheet:
AL TOUKHI NATIONAL GRID SA Page 2 of 4
Site: Circuit name:
Panel / Designation / Location no.:
S/S 9063 380 / 132 / 33 KV 380 KV CBF-2 PROTECTION
=8BF.C02+R2
PANEL (DIA-C02)

C- CURRENT MEASUREMENT:

INJECTED CURRENT IN AMPS EXPECTED CURRENT IN AMPS MEASURED CURRENT IN AMPS

R-N 1.000 3000 3000


Y-N 1.000 3000 3001
B-N 1.000 3000 2999

D- CBF PROTECTION FUNCTION:

1- PICK UP & DROP OFF TEST:

R-PHASE Y-PHASE B-PHASE


SETTING
PICK UP DROP OFF PICK UP DROP OFF PICK UP DROP OFF
I=0.20, IN=0.20A 0.201 0.2 0.2 0.201 0.201 0.2
I=0.15, IN=0.15A 0.151 0.15 0.151 0.15 0.151 0.15

I=0.10, IN=0.10A 0.101 0.1 0.101 0.1 0.101 0.1

2- TIMING TEST:

Setting current (mA) Injected current (mA) SETTING(ms) R Y B

100 200 250 267 269 268

100 200 200 221 217 219

100 200 150 168 168 165

Accuracy: operate current +/-1% reset ratio:95%


Operate time for current detection:20 mS / timers: +/-5%. / Technical manual SH: 140

4-CHECK THE BINARY INPUTS (With Relay Energized):


Tested by : ALFANAR (AT&C) Witnessed by :
Name : ESLAM FARID ( SEC ID : FAN-192 ) Name :

Signature & Date :


Signature & Date :
25/10/2016
SITE INSPECTION AND TEST RECORD
Description: Contract No ::
ACCEPTANCE TEST FOR CBF RELAY
ABB ( REQ 650 ) 44000040233
Customer: End Client: Sheet:
AL TOUKHI NATIONAL GRID SA Page 3 of 4
Site: Circuit name:
Panel / Designation / Location no.:
S/S 9063 380 / 132 / 33 KV 380 KV CBF-2 PROTECTION
=8BF.C02+R2
PANEL (DIA-C02)

TEST METHOD RESULT


INPUT NO.
(Energize with 125V DC)
BIO3 I/P 1 RELAY TB NO. X324:1,2 OK
BIO3 I/P 2 RELAY TB NO.X324:4,5 OK
BIO3 I/P 3 RELAY TB NO. X324:4,6 OK
BIO3 I/P 4 RELAY TB NO. X324:8,9 OK
BIO3 I/P 5 RELAY TB NO. X324:8,10 OK
BIO3 I/P 6 RELAY TB NO. X324:12,13 OK
BIO3 I/P 7 RELAY TB NO. X324:12,14 OK
BIO3 I/P 8 RELAY TB NO. X324:16,17 OK
BIO3 I/P 9 RELAY TB NO. X324:16,18 OK
BIO4 I/P 1 RELAY TB NO. X329:1,2 OK
BIO4 I/P 2 RELAY TB NO.X329:4,5 OK
BIO4 I/P 3 RELAY TB NO. X329:4,6 OK
BIO4 I/P 4 RELAY TB NO. X329:8,9 OK
BIO4 I/P 5 RELAY TB NO. X329:8,10 OK
BIO4 I/P 6 RELAY TB NO. X329:12,13 OK
BIO4 I/P 7 RELAY TB NO. X329:12,14 OK
BIO4 I/P 8 RELAY TB NO. X329:16,17 OK
BIO4 I/P 9 RELAY TB NO. X329:16,18 OK

5-CHECK THE OUTPUTS (With Relay Energized):

Tested by : ALFANAR (AT&C) Witnessed by :


Name : ESLAM FARID ( SEC ID : FAN-192 ) Name :

Signature & Date :


Signature & Date :
25/10/2016
SITE INSPECTION AND TEST RECORD
Description: Contract No ::
ACCEPTANCE TEST FOR CBF RELAY
ABB ( REQ 650 ) 44000040233
Customer: End Client: Sheet:
AL TOUKHI NATIONAL GRID SA Page 4 of 4
Site: Circuit name:
Panel / Designation / Location no.:
S/S 9063 380 / 132 / 33 KV 380 KV CBF-2 PROTECTION
=8BF.C02+R2
PANEL (DIA-C02)

Contact Checked
OUTPUT RELAY NO. RELAY CONTACT NO. CONTACT
Res <0.2 Ω

Tested by : ALFANAR (AT&C) Witnessed by :


Name : ESLAM FARID ( SEC ID : FAN-192 ) Name :

Signature & Date :


Signature & Date :
25/10/2016
SITE INSPECTION AND TEST RECORD
Description: Contract No ::
ACCEPTANCE TEST FOR CBF RELAY
ABB ( REQ 650 ) 44000040233
Customer: End Client: Sheet:
AL TOUKHI NATIONAL GRID SA Page 5 of 4
Site: Circuit name:
Panel / Designation / Location no.:
S/S 9063 380 / 132 / 33 KV 380 KV CBF-2 PROTECTION
=8BF.C02+R2
PANEL (DIA-C02)

BIO3-B/O 1 X321:1,2 NO OK
BIO3-B/O 2 X321:3,4 NO OK
BIO3-B/O 3 X321:5,6 NO OK
BIO3-B/O 4 X321:7,8 NO OK
BIO3-B/O 5 X321:9,10 NO OK
BIO3-B/O 6 X321:11,12 NO OK
BIO3-B/O 7 X321:13,15 NO OK
BIO3-B/O 8 X321:14,15 NO OK
BIO3-B/O 9 X321:16,17,18 NC – NO - C OK
BIO4-B/O 1 X326:1,2 NO OK
BIO4-B/O 2 X326:3,4 NO OK
BIO4-B/O 3 X326:5,6 NO OK
BIO4-B/O 4 X326:7,8 NO OK
BIO4-B/O 5 X326:9,10 NO OK
BIO4-B/O 6 X326:11,12 NO OK
BIO4-B/O 7 X326:13,15 NO OK
BIO4-B/O 8 X326:14,15 NO OK
BIO4-B/O 9 X326:16,17,18 NC – NO - C OK
PSM2-TCS1 X317:1,2 NO OK
PSM2-TCS2 X317:3,4 NO OK
PSM2-TCS3 X317:5,6 NO OK
PSM2-PO4 X317:7,8 NO OK
PSM2-PO5 X317:9,10 NO OK
PSM2-PO6 X317:11,12 NO OK
PSM2-PO7 X317:13,14 NO OK
PSM2-PO8 X317:15,16 NO OK
PSM2-PO9 X317:17,18 NO OK

6- LEDS CHECK:

LED NO. FUNCTION LED STATUS

LED 1 CBF INI OK

LED 2 CBF TRIP OK

LED 3 SPARE OK

LED 4 SPARE OK

Tested by : ALFANAR (AT&C) Witnessed by :


Name : ESLAM FARID ( SEC ID : FAN-192 ) Name :

Signature & Date :


Signature & Date :
25/10/2016
SITE INSPECTION AND TEST RECORD
Description: Contract No ::
ACCEPTANCE TEST FOR CBF RELAY
ABB ( REQ 650 ) 44000040233
Customer: End Client: Sheet:
AL TOUKHI NATIONAL GRID SA Page 6 of 4
Site: Circuit name:
Panel / Designation / Location no.:
S/S 9063 380 / 132 / 33 KV 380 KV CBF-2 PROTECTION
=8BF.C02+R2
PANEL (DIA-C02)

LED 5 SPARE OK

LED 6 SPARE OK

LED 7 SPARE OK

LED 8 SPARE OK

LED 9 SPARE OK

LED 10 SPARE OK

LED 11 SPARE OK

LED 12 SPARE OK

LED 13 SPARE OK

LED 14 SPARE OK

LED 15 SPARE OK

Tested by : ALFANAR (AT&C) Witnessed by :


Name : ESLAM FARID ( SEC ID : FAN-192 ) Name :

Signature & Date :


Signature & Date :
25/10/2016