Description: Order no.: Record No.:


DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 1 / 11

1. GENERAL INFORMATION

Designation No. U11-5001 Rated Current 1.00 A


Manufacturer Siemens Rated Voltage 110V (100-120V)
Type No. 7SA522 Rated Freq. 60 Hz
Serial No. 0710091814 Aux. Voltage 125 V D.C

2. MECHANICAL CHECK AND VISUAL INSPECTION (tick if verified)

Item Description
1 Inspect for physical damage / defects.  Yes  N/A
2 Verify connections as per approved drawing.  Yes  N/A
3 Check tightness of all connections.  Yes  N/A

3. ELECTRICAL TESTS (tick if verified)

3.1. Function Test

Item Description
1 Human Machine Interface [HMI] checked.  Yes  N/A
2 Test switch checked for correct function.  Yes  N/A
3 Case earthing checked.  Yes  N/A
4 LED’s function checked.  Yes  N/A
5 Trip contacts checked.  Yes  N/A
6 Reset of indications checked.  Yes  N/A
7 Disturbance report function checked.  Yes  N/A
8 Group active function checked.  Yes  N/A
9 All binary inputs checked.  Yes  N/A
10 All binary outputs checked.  Yes  N/A
11 Protection under test function checked.  Yes  N/A

3.2: Measurement Analog Channels

Tested by: SSS Witnessed by: SEC Witnessed by: SEC


MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 2 / 11

3000 A 380 KV
C.T Ratio: P.T Ratio:
1A 110 V

Secondary measured
Name Injected Values Primary Measured Values
values
IL1 1.00 A 0.997 A 2.99 KA
IL2 1.00 A 0.997 A 2.99 KA
IL3 1.00 A 0.997 A 2.99 KA
U1-Un / U1-U2 63.50 V 64.48 / 109.92 V 219.00 / 380.00KV
U2-Un / U2-U3 63.50 V 64.45 / 109.87 V 219.00 / 380.00KV
U3-Un / U3-U1 63.50 V 64.43 / 109.93 V 219.00 / 380.00KV
Frequency 60.00 Hz 60.00 Hz 60.00 Hz
S(appar power) ----------- ----------- 1.97 Mva
P(active power) ----------- ----------- 1.97 Mw
Q(react power) ----------- ----------- 0.00 Mvar
Powerfactor ----------- 0.99 0.99

3.4: CHECKING OF BINARY INPUTS:


RELAY
BI No’s FUNCTION/ DUTY RESULT
TERMINALS
Tested by: SSS Witnessed by: SEC Witnessed by: SEC
MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 3 / 11

BI.01 K17:K18 SPARE  Yes  N/A


BI.02 J1:J2 SPARE  Yes  N/A
BI.03 J3:J5 CB OPEN  Yes  N/A
BI.04 J4:J5 CB CLOSED  Yes  N/A
BI.05 J6:J5 SPARE  Yes  N/A
BI.06 J7:J8 TIME SYNC  Yes  N/A
BI.07 J9:J10 VT MCB TRIP  Yes  N/A
BI.08 J11:J12 CB MAN CLOSE  Yes  N/A
BI.09 P17:P18 EXT FFR (BLOCK DIST)  Yes  N/A
BI.10 N1:N2 SPARE  Yes  N/A
BI.11 N3:N5 SPARE  Yes  N/A
BI.12 N4:N5 SPARE  Yes  N/A
BI.13 N6:N5 SPARE  Yes  N/A
BI.14 N7:N8 DIST CARR REC  Yes  N/A
BI.15 N9:N10 DEF CARR REC  Yes  N/A
BI.16 N11:N12 SPARE  Yes  N/A
BI.17 H1:H2 SPARE  Yes  N/A
BI.18 H3:H2 SPARE  Yes  N/A
BI.19 H4:H2 SPARE  Yes  N/A
BI.20 H5:H2 SPARE  Yes  N/A
BI.21 H6:H2 SPARE  Yes  N/A
BI.22 H7:H2 SPARE  Yes  N/A

3.5: CHECKING OF OUTPUTS RELAYS:


RELAY
BO No’s FUNCTION/ DUTY RESULT
TERMINALS
BO.01 K6:K5 DIST TRIP  Yes  N/A
BO.02 K7:K5 DEF TRIP  Yes  N/A
BO.03 K8:K5 B/U O/C TRIP  Yes  N/A
Tested by: SSS Witnessed by: SEC Witnessed by: SEC
MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 4 / 11

BO.04 K9:K10 DIST SEND  Yes  N/A


BO.05 K11:K12 DEF SEND  Yes  N/A
BO.06 K13:K14 PROTN FW START  Yes  N/A
BO.07 K15:K16 PROTN REV START  Yes  N/A
BO.08 R1:R5 A/R INI PH-A  Yes  N/A
BO.09 R2:R5 A/R INI PH-B  Yes  N/A
BO.10 R3:R5 A/R INI PH-C  Yes  N/A
BO.11 R4:R5 A/R BLOCK  Yes  N/A
BO.12 R6:R5 SPARE  Yes  N/A
BO.13 R7:R8 SPARE  Yes  N/A
BO.14 R9:R10 SPARE  Yes  N/A
BO.15 R11:R12 SPARE  Yes  N/A
BO.16 P3:P4 SPARE  Yes  N/A
BO.17 P6:P5 ZONE-1 OPTD  Yes  N/A
BO.18 P7:P5 ZONE-2 OPTD  Yes  N/A
BO.19 P8:P5 ZONE-3 OPTD  Yes  N/A
BO.20 P9:P10 DIST REV START  Yes  N/A
BO.21 P11:P12 DEF REV START  Yes  N/A
BO.22 P13:P14 ZONE-4/5 OPTD  Yes  N/A
BO.23 P15:P16 SPARE  Yes  N/A
BO.24 H10:H16 DIST PH-A START  Yes  N/A
BO.25 H11:H16 DIST PH-B START  Yes  N/A
BO.26 H12:H16 DIST PH-C START  Yes  N/A
BO.27 H13:H16 DIST PH-AB START  Yes  N/A
BO.28 H14:H16 DIST PH-BC START  Yes  N/A
BO.29 H15:H16 DIST PH-CA START  Yes  N/A

3.5: CHECKING OF OUTPUTS RELAYS:


RELAY
BO No’s FUNCTION/ DUTY RESULT
TERMINALS
BO.30 H17:H16 DIST PH-ABC START  Yes  N/A
BO.31 H18:H16 SPARE  Yes  N/A
BO.32 G5:G3 DIST AIDED TRIP  Yes  N/A
BO.33 G6:G3 DEF TRIP  Yes  N/A
Tested by: SSS Witnessed by: SEC Witnessed by: SEC
MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 5 / 11

BO.34 G7:G3 DIST SOTF TRIP  Yes  N/A


BO.35 G8:G3 DIST WEI TRIP  Yes  N/A
BO.36 G9:G3 DIST WEI CB OPEN TRIP  Yes  N/A
BO.37 G10:G3 DEF WEI TRIP  Yes  N/A
BO.38 G11:G3 DEF WEI CB OPEN TRIP  Yes  N/A
BO.39 G12:G3 DIST PSB OPTD  Yes  N/A
BO.40 G4:G3 SPARE  Yes  N/A
BO.41 G2:G3 SPARE  Yes  N/A
BO.42 G1:G3 SPARE  Yes  N/A
BO.43 H8:H9 FUSE FAILURE OPTD  Yes  N/A

3.6: CHECKING OF LED's:


LED’S Function (Duty) LED Mode Checked
LED 01 START PH-A Latched  Yes  N/A
LED 02 START PH-B Latched  Yes  N/A
LED 03 START PH-C Latched  Yes  N/A
LED 04 START PH-N Latched  Yes  N/A
LED 05 DIST TRIP Latched  Yes  N/A
LED 06 DIST TRIP 1PH Latched  Yes  N/A
LED 07 ZONE-1 OPTD Latched  Yes  N/A
Tested by: SSS Witnessed by: SEC Witnessed by: SEC
MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 6 / 11

LED 08 ZONE-1B OPTD Latched  Yes  N/A


LED 09 ZONE-2 OPTD Latched  Yes  N/A
LED 10 ZONE-3/4/5 OPTD Latched  Yes  N/A
LED 11 DEF TRIP Latched  Yes  N/A
LED 12 SOTF TRIP Latched  Yes  N/A
LED 13 CARR REC Latched  Yes  N/A
LED 14 FUSE / PSB OPTD Unlatched  Yes  N/A

Tested by: SSS Witnessed by: SEC Witnessed by: SEC


MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 7 / 11

SECONDARY INJECTION TEST:

4: Distance Protection :

4.1 Zone reach measurements :

ITEM Description Checked


1 Print out from Freja attached. OK

4.2 Timing Test:

ITEM Description Checked


1 Print out from Freja attached. OK

4.3: Power Swing Detection

Tested by: SSS Witnessed by: SEC Witnessed by: SEC


MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 8 / 11

1. Power swing detected: : OK Blocking Time Measured


Set Optd
2. Blocking of Measuring Zones : All Zones 5.00 Sec 5.064 Sec
:
4.4: Distance Scheme Communication Logic

1. Permissive Under Reach Scheme : PUTT


Send Logic : CS = ZM1 : OK
Trip Logic : Trip = ZM1B+CR : OK

2. Permissive Over Reach Scheme : POTT


Send Logic : CS = ZM1B : OK
Trip Logic : Trip = ZM1B+CR : OK

3. Blocking Scheme :
Send Logic : CS = ZM5 (Rev) : OK
Trip Logic : Trip = ZM1B+No CR : OK

4. Direct Transfer Trip


Trip logic : Trip = CR : OK

4.5: Distance WEI Function :


Echo Checked U< (Ph-E) Set OK
Tested by: SSS Witnessed by: SEC Witnessed by: SEC
MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 9 / 11

Echo Time 25.00 V 50 ms


Trip Checked OK

4.6 Switch onto Fault Function.


2.520 A
SOTF overcurrent set : 2.50 A Measured :
19 ms

4.7 Fuse Failure Function.

1. Fuse failure voltage measurements.


Min volt threshold Voltage Injected (V) Prot function
S.No.
FFM U A B C blocked
1 30.00 V 30.09 V 63.50 V 63.50 V OK
2 30.00 V 63.50 V 29.95 V 63.50 V
3 30.00 V 63.50 V 63.50 V 30.01 V

2. Fuse failure function measurements.


Fuse failure
Settings Measured Comments
Functions
FFM I (max) 0.100 A 0.103 A Max current threshold I
FFM U<max 5.00 V Max volt threshold U
5.00 V
(3ph) 3phase
VT fuse failure (alarm 10
VT Fuse fail  10s 10.00 Sec 10.016 Sec
sec)

4.8: Earthfault Over Current Function Test.

Tested by: SSS Witnessed by: SEC Witnessed by: SEC


MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 10 / 11

Voltage Current Trip Time Optd


Ph Remarks
Injected 3I0>DIR Forward Dir
Set Optd Set Optd
AN 0.198 A 2.00 Sec 2.025 Sec
BN 63.50 V 0.200 A 0.200 A 2.00 Sec 2.024 Sec
CN 0.200 A 2.00 Sec 2.026 Sec

4.9: DEF Protection:-


Voltage Current Trip Time Optd
Ph Remarks
Injected Injected Forward Dir
AN 0.400 A 26 ms
BN 63.50 V 0.400 A 26 ms
CN 0.400 A 26 ms

4.10: Backup Over Current Function Test.

Trip Time Optd


Ph I> I>> Remarks
Sec
Set Optd Set Optd Set Optd
ABC 1.570 A 1.570 A 1.570 A 1.570 A 2.00 2.021
AN 0.100 A 0.101 A 0.100 A 0.101 A 2.00 2.023
BN 0.100 A 0.101 A 0.100 A 0.101 A 2.00 2.023
CN 0.100 A 0.101 A 0.100 A 0.101 A 2.00 2.028

4.11: Brocken Conductor:-


Checked : OK

4.12: Fault Locator Test:


Set:- 112 Km, 0.2710  / Km

Fault reactance Calculated Display at relay


Setting
Type of fault value injected by value of Distance Remarks
(/km)
Test set X () distance Km Km (%)
Tested by: SSS Witnessed by: SEC Witnessed by: SEC
MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.
SSSS SSSSSSSSSS SSS SSSS SSSSSS 
Description: Order no.: Record No.:
DISTANCE PROTECTION RELAY- 7SA522 SMM/7SA522/1
Customer: Customer ref.: Project no.:
SEC - SRB -
Site: Drawing ref.: Sheet::
380/132/13.8 KV ABHA EAST SA-000292 11 / 11

AN 0.2710 30.352 100 % 112.50 Km


BN 0.2710 15.176 50 % 56.10 Km
CN 0.2710 7.588 25 % 28.10 Km
AB 0.2710 30.352 100 % 112.40 Km
BC 0.2710 15.176 50 % 56.20 Km
CA 0.2710 7.588 25 % 28.10 km
ABC 0.2710 30.352 100 % 112.40 Km

Faults injected at 87 Line Angle.

4.13 Autoreclosing function check.


1. AR timings test
Dead time (sec) Reclaim time (sec)
Phase
Setting Meas Setting Meas
AN 0.35 Sec 0.350 Sec 8.00 Sec 7.999 Sec
AB 0.35 Sec 0.346 Sec 8.00 Sec 8.000 Sec
ABC 0.35 Sec 0.349 Sec 8.00 Sec 8.000 Sec

2. AR initiation & blocking checked : OK

5: Disturbance Report:

Checked disturbance report recording through Digsi Software : OK

Checked event recording through Digsi Software : OK

Tested by: SSS Witnessed by: SEC Witnessed by: SEC


MA.Ramesha Ahmed EL-Baz
Date: Test Equipment Used: Designation no.: C03+RA2
01/08/2009 to 04/08/2009 FREJA 300 SHUQAIQ 380 KV LINE-2 SET-2 PROTECTION PANEL

SSS Contracting Co. Ltd.


P.O. Box 91926 Tel: +966-(0)1-2650090
Riyadh 11643 Fax: +966-(0)1-2652077
K.S.A.