The approved updated final settings should be applied and printed out from the relay
by using the software of the relay.
The following test format contains minimum required tests and some of settings are
mentioned as an example and not as limitation.
3. ELECTRICAL TESTS
Burden =7 VA
MEASUREMENTS
Open Degsi 4 Measurement primary value operational value primary after connecting to the relay
& observe the reading, in primary values.
Input CT Applied Value (A) CT Ratio Applied (A) Displayed Secondary Value (A) Displayed Primary Value (A)
R 600 600/5 5 600
S 600 600/5 5 600
T 600 600/5 5 600
N 0
Input CT Applied Value (A) CT Ratio Applied (A) Displayed Secondary Value(A) Displayed Primary Value(A)
N 1 600/5 1 120
Input PT Applied Value PT Ratio Applied Displayed Secondary Value (V) Displayed Primary Value (KV)
R-S 110 33000/110 110 33K
S-T 110 33000/110 110 33K
R-T 110 33000/110 110 33K
R-N 63.51 33000/110 63.51 19.05K
S-N 63.51 33000/110 63.51 19.05K
T-N 63.51 33000/110 63.51 19.05K
1.05X
PHASE Pickup TMS CURVE Injected A 1.05X Relay
Theory
R 10 A 0.65 D.T 10.5 A 0.65 sec 0.662 sec
50-1 S 10 A 0.65 D.T 10.5 A 0.65 sec 0.662 sec
T 10 A 0.65 D.T 10.5 A 0.65 sec 0.662 sec
1.05X
PHASE Pickup TMS CURVE Injected A 1.05X Relay
Theory
R 35 A 0.02 D.T 36.75 A 0.02 sec 0.033 sec
50-2 S 37 A 0.02 D.T 36.75 A 0.02 sec 0.033 sec
T 37 A 0.02 D.T 36.75 A 0.02 sec 0.033 sec
1.05X
PHASE Pickup TMS CURVE Injected A 1.05X Relay
Theory
50N-2 0.5 A 0.3 sec D.T 0.525 0.3 sec 0.312 sec 600/5
50G-1 0.1 0.6 sec D.T 0.105 0.6 sec 0.611 sec 200/1
50G-2 0.5 A 0.3 sec D.T 0.525 0.3 sec 0.315 sec 200/1
K factor Time constant Thermal alarm stage Current alarm set point
0.87 2 90% 4.38 A
49
Trip time Trip time
Injected current
Theory Relay
10 A 25.172 sec 25.194 sec