Contractor : NCC SITE TEST RECORD Customer:SEC-EOA

Contract # : 11001172/00 CIRCUIT “A” Sheet :1 of 5

Description : 132 KV LINE S/S 8838 – S/S 8824 OHTL Testing Date:17-4-2016

General Information:

Circuit : Circuit –A

Station A : S/S 8838

Station B : S/S 8824

Line Length : 23.75 km

Test Conducted at S/S 8838

Electrical Tests:

1. Phasing Test:

Isolate the three phases from both ends.


Ground one phase from remote end connect the local end with the insulation tester
MEGGER between the phase and ground.
Repeat for other two phases.

Results:

Phase Checked Remarks

R
Y
B

2. Phase Rotation Test:

Connect 3-phase 380V AC supply (generator) to the line.


Conect phase sequence meter on both ends of the line. Read the phase sequence
At sending and receiving ends.

Results:

TESTED BY : XERVON WITNESSED BY: SEC/COA

NAME : FAISAL IQBAL NAME :

SIGNATURE: SIGNATURE:
[
[
Contractor : NCC SITE TEST RECORD Customer:SEC-EOA

Contract # : 11001172/00 CIRCUIT “A” Sheet :2 of 5

Description : 132 KV LINE S/S 8838 – S/S 8824 OHTL Testing Date:17-4-2016

3. Continuity / Conductivity Test:

Short the three phases together from other end. Using insulation tester MEGGER apply
5kV DC between phase R and Y observe the reading on the MEGGER.
Repeat for Y and B phases

Results:

Phase Reading Continuity Remarks

R-Y
Y-B
B-R

4. Insulation Test:

Keep three phases without ground to both end of the line. Using MEGGER check the
insulation resistance between phases and between each phase and ground.

Result:

Reading
Phase Remarks
(GΩ)

R-Y

Y-B

B-R

R-G

Y-G

B-G

TESTED BY : XERVON WITNESSED BY: SEC/COA

NAME : FAISAL IQBAL NAME :

SIGNATURE: SIGNATURE:
[
[
Contractor : NCC SITE TEST RECORD Customer:SEC-EOA

Contract # : 11001172/00 CIRCUIT “A” Sheet :3 of 5

Description : 132 KV LINE S/S 8838 – S/S 8824 OHTL Testing Date:17-4-2016

5. Susceptance Test:

Isolate the three phase from both ends. Connect phase-phase 380 V AC source to the
line. Apply voltage and observe the reading of the ammeter and voltmeter.
Calculate the phase –phase Susceptance as per the formula below.
Fill the results in the test record.

X=2V/I in OHM

B=1/(-JX) in MOH

Result:

Phase X (Ohm) B ( Moh) Remarks

R-Y
Y-B
B-R

VRY = VRB = VYB =

IA = IB = IC =

TESTED BY : XERVON WITNESSED BY: SEC/COA

NAME : FAISAL IQBAL NAME :

SIGNATURE: SIGNATURE:
[
[
Contractor : NCC SITE TEST RECORD Customer:SEC-EOA

Contract # : 11001172/00 CIRCUIT “A” Sheet :4 of 5

Description : 132 KV LINE S/S 8838 – S/S 8824 OHTL Testing Date:17-4-2016

6. Impedance Test:

 Zero Sequence Impedance(Zo):

Short the three phase from both ends. Connect the CPC and CU1 as shown
Take the CPC100 readings

Result:

Impedance Results R (Ω) X (Ω) Z (Ω) Phi (O)

Zero sequence impedance ZO


Zero sequence impedance per km ZO/KM

Calculated Value ZO/KM :

Measured Value ZO/KM :


Note: See attached sheets

 Positive Sequence Impedence (Z1):

Short the three phases from one end . Conect the CPC100 and CP CU1 as shown for
phase R-Y. Take the CPC100 readings.
Repeat for phases Y-B and B-R

Result:

Impedance Results R (Ω) X (Ω) Z (Ω) Phi (O)

Positive sequence impedance Z1


Positive sequence impedance per km Z1/KM

TESTED BY : XERVON WITNESSED BY: SEC/COA

NAME : FAISAL IQBAL NAME :

SIGNATURE: SIGNATURE:
[
[
Contractor : NCC SITE TEST RECORD Customer:SEC-EOA

Contract # : 11001172/00 CIRCUIT “A” Sheet :5 of 5

Description : 132 KV LINE S/S 8838 – S/S 8824 OHTL Testing Date:17-4-2016

Calculated Value Z1/KM :


Measured Value Z1/KM :

 Mutual Impedeance (for double circuit):

Short the three phases for each line (Circuit-A & Circuit-B) from both ends and connect
the two circuit to ground at the remote end only.
Connect the cpc100 as shown. Take the CPC100 readings

Result:

Impedance Results R (Ω) X (Ω) Z (Ω) Phi (O)

Positive sequence impedance Z1


Zero sequence impedance Z0
Mutual coupling impedance ZM
Mutual coupling zero sequence Z0M
Mutual coupling impedance per km ZM/KM
Mutual coupling zero sequence per km Z0M/KM

TESTED BY : XERVON WITNESSED BY: SEC/COA

NAME : FAISAL IQBAL NAME :

SIGNATURE: SIGNATURE:
[
[