Site Test Report

Contract No. – N-6166.1 CONSORTIIUM


New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:11.06.2012 Bay/Feeder : =E03 – Cable Feeder (ZYSC) Page 1 of 3

High Voltage Switchgear Type 8DN8 72,5 kV and above


Current Transformers
Hochspannungsschaltanlagen 8D . . ab 72,5 kV
Stromwandler
Customer: Contract No.:
Kunde: TRANSCO Vertragsnr.: N-6166.1
Consultant: Bay/Feeder:
Berater: ENERGO CONSULT Abzweig: =E03
Substation: Serial No.:
Anlage: ADNEC Fabrik-Nr.: 31 259 837
Switchgear type: Rated voltage:
Schaltanlagentyp: 8DN8 Bemessungsspannung: 145 kV

Current transformer: item designation: Type: P2 in direction busbar


Stromwandler: Betriebsmittelkennz.: T2 Typ: AMT145/3 in Richtung SaS*/Feld*

Serial-No.:
Fabrik-Nr.: L1: 11/101 203 L2: 11/101 203 L3: 11/101 203

Core-No.
Kern-Nr. Core 1 Core 2 Core 3 Core 4
Core data Kern 1 Kern 2 Kern 3 Kern 4
Kerndaten
Nominal power VA 30-20 VA
Nennleistung
Nominal Ratio 1500-1000/1A 1500-1000/1A
Nennübersetzung
Class PX 0.5FS 5
Klasse
Magnetizing – U0 ≥600-400 V V
Magnetizing – I0 ≤50-80 mA mA
Resistance Rct ≤6-4 Ω ≤ 3.5 - 2.5 Ω
Earthed at 1S3 2S3
Geerdet an
Used for BUSBAR PRTN BCU
Verwendet für
Polarity check Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error: Error:
Polaritätsprüfung Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer Refer
Secondary circuits
checked up to: +S3 +S3
Sekundärverdrahtung
geprüft bis:

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:11.06.2012 Bay/Feeder : =E03 – Cable Feeder (ZYSC) Page 2 of 3

INSULATION TEST (with 1000V insulation tester) Amb Temp:31.4 °C

TERMINAL WINDINGS R Y B
MARKING C.T + LEAD WIRE C.T + LEAD WIRE C.T + LEAD WIRE
UPTO TB UPTO TB UPTO TB

Core1-Earth 6.41 G Ω 4.65 G Ω 6.26 G Ω


T2 Core2-Earth 6.54 G Ω 5.03 G Ω 6.69 G Ω

Core 1-Core2 12.5 G Ω 9.18 G Ω 12.2 G Ω

RESISTANCE MEASUREMENT OF SECONDARY WINDINGS


Amb Temp:28.4 °C

CORE Resistance at Amb Temp in Ohms Resistance at 75˚C in Ohms


PHASE 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3 1S1-1S2 1S1-1S3 2S1-2S2 2S1-2S3
R 2.842 4.394 1.515 2.371 3.351 5.181 1.787 2.796
Y 2.860 4.414 1.511 2.358 3.372 5.205 1.782 2.780
B 2.855 4.410 1.513 2.365 3.367 5.200 1.784 2.788

CT RATIO TEST

CURRENT CURRENT MEASURED ACROSS


% ERROR
INJECTED SECONDARY TERMINALS (mA)
CT RATIO
TERMINALS ACROSS
(A)
PRIMARY R-Phase Y-Phase B-Phase R-Phase Y-Phase B-Phase
(A)
1S1-1S2 1000/1A 600 599.0 598.9 598.8 -0.15 -0.15 -0.17
1S1-1S3 1500/1A 600 399.2 399.2 399.1 -0.18 -0.18 -0.21
2S1-2S2 1000/1A 600 600.3 600.3 600.1 -0.07 -0.07 -0.05
2S1-2S3 1500/1A 600 399.8 399.8 399.7 -0.03 -0.03 -0.06

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO
Site Test Report
Contract No. – N-6166.1 CONSORTIIUM
New 132/11KV Substations at E12,Zayed Sports
City, ADNEC Capital Centre, 132/22kv SIEMENS-
Substations at New Airport and Capital District ELECTROMECHANICAL
and All Related 132kv Cable works

Date:11.06.2012 Bay/Feeder : =E03 – Cable Feeder (ZYSC) Page 3 of 3

Used Instruments Stock no Calibration Certificate Certificate valid until


available
OMICRON CPC-100 JH808Q(VI) YES 09.05.2013
MEGGER MIT 510 3381 YES 08.05.2013

Remarks:
Bemerkungen: For Magnetizing Curve -See attached Printouts of CPC 100
For C.T Secondary Winding Resistance- See attached Printouts of CPC 100

For Polarity test done as per approved drawing - See attached Printouts of CPC 100

For Ratio Test- See attached Printouts of CPC 100

TESTED BY WITNESSED BY WITNESSED / APPROVED BY

Signature: Signature: Signature:

Name: TIMM Name: SENTHIL KUMAR Name:

Date Date Date


CSE ENERGO CONSULT L.L.C TRANSCO