CVT SITE TEST REPORT

Equipment :
Date : 16/02/2021
CAPACITIVE VOLTAGE TRANSFORMER
R Ph Sl. No : 4218169 Y Ph Sl. No : 4218170 B Ph Sl. No : 4218171
Location & Designation : Guddigudem, West Godavari Page 1 of 7
Customer : Project :
BAY : 401
APTRANSCO ABB & RVR APTRANSCO

Pre-Commissioning Checklist :

1. Check the erection of equipment is carried out as per the approved drawings

2. Check there is no damage to any part of CVT/ PT assembly, and CVT/PT is


cleaned and free from dust/dirt etc.

3. Check the position of the secondary terminal box is as per the approved drawing

4. Check for oil marks/oil leakage, oil level, any damage to the
Primary and secondary terminals

5. Check the earth connections of the equipment are completed as per the drawing

6. For CVT, check the wire between primary HT terminal and tank is removed

7. Check the HF terminal is earthed properly (if not used for PLCC)

8. Check the primary neutral of CVT/ PT is earthed


9. Terminal Box:
a) Secondary connections are completed properly as per the drawing
And terminals are tightened
b) The cable tags, ferrules for all cores are provided

c) Cables are properly dressed and clamped


d) Unused holes are sealed properly

10. Junction Box:


a) Check the cabling from the CVT/ PT to the JB are completed
b) Check external cabling from JB to relay panel is completed
c) The star point has been formed and earthed
d) Links and connections are tightened properly

Remarks :

Tested by Witnessed – Client


Inser Hitech AP Transco
Name
Signature
Date
CVT SITE TEST REPORT
Equipment :
Date : 16/02/2021
CAPACITIVE VOLTAGE TRANSFORMER
R Ph Sl. No : 4218169 Y Ph Sl. No : 4218170 B Ph Sl. No : 4218171
Location & Designation : Guddigudem, West Godavari Page 2 of 7
Customer : Project :
BAY : 401
APTRANSCO ABB & RVR APTRANSCO

Name Plate Details :

Type : CPB-H 420


Highest System volt. KV : 420
Rated Insulation level KV : 420/630/1425
Rated Frequency Hz : 50
Standard : IEC:61869-5
H.V.(PR) Cap : C1 pf : 4632
Int. V(Sec) Cap : C2 pf : 88000
Temperature Category C : -5 TO 50
Total Thermal Burden VA : 750
Class of Insulation : ‘A’
Voltage Devider Ratio : 400000/ /20000/√3
Voltage Factor : 1.2 continuous/1.5 for 30 sec
Rated Voltage : 400/√3
Total Creepage minimum mm : 10500
Wt of oil (Approx) kg : 121
Total weight (Approx) kg : 700
Equ. Cap. (Cn) for PLCC Pf : 4400
Nominal Intermediate Volt.KV : 20/√3
Date of Mfg. Month/Year : DECEMBER-2018
G.A. Drg. No. : 1HYT90270B-002

Core Details :

Rated sec
Terminal Markings Rated Burden VA Accuracy Class
Voltage ‘V’
110/√3 1a-1n 75 0.2
110/√3 2a-2n 75 3P
110/√3 3a-3n 75 3P

Tested by Witnessed – Client


Inser Hitech AP Transco
Name
Signature
Date
CVT SITE TEST REPORT
Equipment :
Date : 16/02/2021
CAPACITIVE VOLTAGE TRANSFORMER
R Ph Sl. No : 4218169 Y Ph Sl. No : 4218170 B Ph Sl. No : 4218171
Location & Designation : Guddigudem, West Godavari Page 3 of 7
Customer : Project :
BAY : 401
APTRANSCO ABB & RVR APTRANSCO

 Atmospheric Temperature : 30◦C

1. Insulation Resistance Test : (values in Mega ohms)

Applied
Circuit Ref. R Y B
Volt (V)
Primary – Earth 5KV >1 TΩ >1 TΩ >1 TΩ
Primary – Core 1 5KV >1 TΩ 879 GΩ 180 GΩ
Primary – Core 2 5KV 898 GΩ 780 GΩ 509 GΩ
Primary – Core 3 5KV 682 GΩ >1 TΩ 674 GΩ
Core 1 – Earth 500V 396 MΩ 385 MΩ >1 GΩ
Core 2 – Earth 500V 365 MΩ 187 MΩ 253 MΩ
Core 3 – Earth 500V 617 MΩ 287 MΩ 715 MΩ
Core 1 – Core 2 500V 900 MΩ 649 MΩ >1 GΩ
Core 2 – Core 3 500V >1 GΩ 527 MΩ >1 GΩ
Core 3 – Core 1 500V >1 GΩ 802 MΩ >1 GΩ

2. Polarity Test :

Core R Y B
Core – 1 OK OK OK
Core – 2 OK OK OK
Core – 3 OK OK OK

3. Winding Resistance :

Resistance in Ohms
Core
R Y B
Core – 1 0.5 0.5 0.5
Core – 2 0.5 0.3 0.5
Core – 3 0.5 0.5 0.5

4. Ratio Test :

Tested by Witnessed – Client


Inser Hitech AP Transco
Name
Signature
Date
CVT SITE TEST REPORT
Equipment :
Date : 16/02/2021
CAPACITIVE VOLTAGE TRANSFORMER
R Ph Sl. No : 4218169 Y Ph Sl. No : 4218170 B Ph Sl. No : 4218171
Location & Designation : Guddigudem, West Godavari Page 4 of 7
Customer : Project :
BAY : 401
APTRANSCO ABB & RVR APTRANSCO

Measured Sec. Voltage


Primary
Core Ref. Voltage
Applied(V) R % Error Y % Error B % Error

Tested by Witnessed – Client


Inser Hitech AP Transco
Name
Signature
Date
CVT SITE TEST REPORT
Equipment :
Date : 16/02/2021
CAPACITIVE VOLTAGE TRANSFORMER
R Ph Sl. No : 4218169 Y Ph Sl. No : 4218170 B Ph Sl. No : 4218171
Location & Designation : Guddigudem, West Godavari Page 5 of 7
Customer : Project :
BAY : 401
APTRANSCO ABB & RVR APTRANSCO

1KV 0.277 -0.72727 0.277 -0.72727 0.279 -1.45455

2KV 0.553 -0.54546 0.557 -1.27273 0.555 -0.90909

Core- 1 3KV 0.830 -0.60606 0.834 -1.09091 0.827 -0.24243

4KV 1.113 -1.18182 1.109 -0.81818 1.108 -0.72727

5KV 1.377 -0.14546 1.380 -0.36364 1.381 -0.43636

1KV 0.277 -0.72727 0.278 -1.09091 0.277 -0.72727

2KV 0.553 -0.54546 0.557 -1.27273 0.556 -1.09091

Core- 2 3KV 0.830 -0.60606 0.834 -1.09091 0.827 -0.24243

4KV 1.114 -1.27273 1.108 -0.72727 1.111 -1

5KV 1.376 -0.07273 1.372 0.21818 1.379 -0.29091

1KV 0.277 -0.72727 0.278 -1.09091 0.277 -0.72727

2KV 0.553 -0.54546 0.556 -1.09091 0.559 -1.63636

Core- 3 3KV 0.831 -0.72727 0.830 -0.60606 0.829 -0.48485

4KV 1.113 -1.18182 1.109 -0.81818 1.111 -1


1.376
5KV -0.07273 1.376 -0.07273 0.279 -0.43636

5. Capacitance and Tan - Delta Measurement :

 Atmospheric Temperature : 32◦C

Phase
Applied Measured Capacitance Dissipation
& Ref. Mode
Voltage (V) Current (mA) (pf) Factor (%)
SI No.

Tested by Witnessed – Client


Inser Hitech AP Transco
Name
Signature
Date
CVT SITE TEST REPORT
Equipment :
Date : 16/02/2021
CAPACITIVE VOLTAGE TRANSFORMER
R Ph Sl. No : 4218169 Y Ph Sl. No : 4218170 B Ph Sl. No : 4218171
Location & Designation : Guddigudem, West Godavari Page 6 of 7
Customer : Project :
BAY : 401
APTRANSCO ABB & RVR APTRANSCO

2KV 2.762 mA 4.393 pf 0.380


TOP –
GST 5KV 6.908 mA 4.394 pf 0.358
BOTTOM
10KV 13.817 mA 4.394 pf 0.385

2KV 5.449 mA 8.672 pf 0.1772


R – Phase TOP –
UST 5KV 13.621 mA 8.678 pf 0.435
4218169 MIDDLE
10KV 27.233 mA 8.666 pf 0.1234

2KV 5.510 mA 8.765 pf 0.4834


MIDDLE
– GST 5KV 13.778 mA 8.767 Pf 0.4358
BOTTOM
10KV 27.560 mA 8.769 pf 0.4056

Tested by Witnessed – Client


Inser Hitech AP Transco
Name
Signature
Date
CVT SITE TEST REPORT
Equipment :
Date : 16/02/2021
CAPACITIVE VOLTAGE TRANSFORMER
R Ph Sl. No : 4218169 Y Ph Sl. No : 4218170 B Ph Sl. No : 4218171
Location & Designation : Guddigudem, West Godavari Page 7 of 7
Customer : Project :
BAY : 401
APTRANSCO ABB & RVR APTRANSCO

Phase
Applied Measured Capacitance Dissipation
& Ref. Mode
Voltage (V) Current (mA) (pf) Factor (%)
SI No.
2KV 2.779 mA 4.420 pf 0.392
TOP -
GST 5KV 6.949 mA 4.421 pf 0.374
BOTTOM
10KV 13.898 mA 4.420 pf 0.328

2KV 5.508 mA 8.765 pf 0.200


Y – Phase TOP -
UST 5KV 13.768 mA 8.761 pf 0.142
4218169 MIDDLE
10KV 27.518 mA 8.758 pf 0.110

2KV 5.523 mA 8.786 pf 0.505


MIDDLE
– GST 5KV 13.811 mA 8.789 pf 0.436
BOTTOM
10KV 27.518 mA 8.789 pf 0.399

Phase
Applied Measured Capacitance Dissipation
& Ref. Mode
Voltage (V) Current (mA) (pf) Factor (%)
SI No.
2KV 2.791 mA 4.439 pf 0.396
TOP -
GST 5KV 6.980 mA 4.442pf 0.373
BOTTOM
10KV 13.959 mA 4.440 pf 0.327

2KV 5.521 mA 8.834 pf 0.1770


B – Phase TOP -
UST 5KV 13.873 mA 8.831 pf 0.132
4218171 MIDDLE
10KV 27.739 mA 8.828 pf 0.108

2KV 2.779 mA 8.803 pf 0.530


MIDDLE
– GST 5KV 6.949 mA 8.805 pf 0.456
BOTTOM
10KV 13.898 mA 8.905 pf 0.413

Tested by Witnessed – Client


Inser Hitech AP Transco
Name
Signature
Date