Professional Documents
Culture Documents
Equipment
Capacitive Voltage Transformer Date:24.12.2015 Sheet No 1 of 7
Year: 2013
Tested by Witnessed
INSER ABB INDIA LTD ISOLUX SEUPPTCL
HITECH
Name
Signature
Date
-1-
Doc. No.
SITE TEST REPORT
Equipment
Capacitive Voltage Transformer Date:24.12.2015 Sheet No 2 of 7
7. Polarity Test:
Tested by Witnessed
INSER ABB INDIA LTD ISOLUX SEUPPTCL
HITECH
Name
Signature
Date
-2-
Doc. No.
SITE TEST REPORT
Equipment
Capacitive Voltage Transformer Date:24.12.2015 Sheet No 3 of 7
Core 1 OK OK OK
Core 2 OK OK OK
Core 3 OK OK OK
8. Ratio Test:
Core-1:
Core-2:
Core-3:
Name
Signature
Date
-3-
Doc. No.
SITE TEST REPORT
Equipment
Capacitive Voltage Transformer Date:24.12.2015 Sheet No 4 of 7
primary in volts R Y B
1000 0.143 0.143 0.143
Tested by Witnessed
INSER ABB INDIA LTD ISOLUX SEUPPTCL
HITECH
Name
Signature
Date
-4-
Doc. No.
SITE TEST REPORT
Equipment
Capacitive Voltage Transformer Date:24.12.2015 Sheet No 5 of 7
9.1: R-PHASE
Applied Voltage-10 KV
Temperature:30° C Frequency-50 HZ
Test Mode GST UST UST GST
Reference Bottom Middle Upper Top to bottom
U(KV) 9.9962 9.97002 9.9889 10.002
I(mA) 80.4729 79.7948 79.9862 27.009
C(pF) 25623.5 25481.4 25489.5 8597.07
% TAN D 0.140933 0.116159 0.118663 0.178365
P(W) 1.3303 0.923851 0.948411 0.48219
% VDF 0.059675 0.050272 0.067417 0.058827
9.1: Y-PHASE
Tested by Witnessed
INSER ABB INDIA LTD ISOLUX SEUPPTCL
HITECH
Name
Signature
Date
-5-
Doc. No.
SITE TEST REPORT
Equipment
Capacitive Voltage Transformer Date:24.12.2015 Sheet No 6 of 7
Applied Voltage-10 KV
Temperature:30° C Frequency-50 HZ
Test Mode GST UST UST GST
Reference Bottom Middle Upper Top to bottom
U(KV) 9.99269 9.99782 10.0007 9.97959
I(mA) 79.9819 80.4452 80.0162 26.9682
C(pF) 25478.3 25612.6 25468.0 8603.54
% TAN D 0.137783 0.110106 0.107214 0.160897
P(W) 1.10119 0.886143 0.858526 0.433291
% VDF 0.058012 0.068724 0.062979 0.054504
9.1: B-PHASE
Tested by Witnessed
INSER ABB INDIA LTD ISOLUX SEUPPTCL
HITECH
Name
Signature
Date
-6-
Doc. No.
SITE TEST REPORT
Equipment
Capacitive Voltage Transformer Date:24.12.2015 Sheet No 7 of 7
Applied Voltage-10 KV
Temperature:30° C Frequency-50 HZ
Test Mode GST UST UST GST
Reference Bottom Middle Upper Top to bottom
U(KV) 9.98501 9.98187 9.99119 9.985512
I(mA) 80.448 80.3546 80.3296 27.1393
C(pF) 25646.9 25627.8 25591.5 8651.66
% TAN D 0.121188 0.103797 0.0108981 0.185811
P(W) 0.973279 0.833764 0.875352 0.503888
% VDF 0.051626 0.062794 0.06565 0.068127
Tested by Witnessed
INSER ABB INDIA LTD ISOLUX SEUPPTCL
HITECH
Name
Signature
Date
-7-