132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL


CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS

FEWA-EL-SWGR-TD-0112, Rev 1, 2016

PROCESS NAME: MAINTAIN ENGINEERING SPECIFICATIONS


FEWA-ED-L2-AM-P05-F01 REV. NO. 0 REV. DATE: 17.02.2015 PAGE 1 OF 24
132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

TABLE OF CONTENTS

1. Common Features

2. Circuit Breakers

3. Disconnectors

4. Earthing Switch

5. Current Transformers

6. Voltage Transformers

7. Local Control Panels

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 2 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

This document should be read in conjunction with all relevant pages of the complete Tender
document.

No. Description Unit Required Offered

1. COMMON FEATURES

Manufacturer

Country of origin

Type & Manufacturer model


designation

First commercial operation of the


offered type

in the year of

according to the attached reference


Ref : Number
list/ sheet

IEC 62271-
Standards
203

Operating voltage (U) kV 132

Rated voltage kV 145

Rated short-time withstand current


kA 40
(3s)

Rated peak withstand current kA 100

Frequency Hz 50

Insulation medium SF6

Conductor material
Copper/

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 3 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

Aluminium

Aluminium
Material of enclosures
alloy/ steel

Average thickness mm

Weight per feeder kg

Heaviest part kg

Feeder width mm

Lightning impulse withstand voltage


(peak) (1.2/50 μ sec.) at minimum gas kV 650
pressure

Power frequency withstand voltage (1


kV 275
min) at minimum gas pressure

Guaranteed SF6 gas losses per


% < 1.0
compartment/per year less than:

Colour of GIS external RAL 7032

Max. allowable switching over voltage

Drop across main contact V

Surge Impedance Ohms

Max. Expected sound level at 10M AS per IEC


dB
during operation. 61672-1 & 2

Current SF6 gas replenishing required Yes/No No

Design lifetime of moisture absorbers Years

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 4 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

Heat losses per feeder at rated power kW

Design maintenance period Years

Nos. of gas compartments

- busbar pcs

- Double cable feeders pcs

- IBT Bays pcs

- Bus Coupler Pcs

- Bus Section Pcs

Rated gas pressure at 20 C bar abs.

Minimum gas pressure at 20 C bar abs.

Setting of pressure relief device bar abs.

Emergency operation at rated voltage


Yes/No
and a gas pressure of 1 bar abs.

Busbars

- Common enclosed phases Yes/No

- Rated current (IEC rating)


A 3150A
Applicable for 400/132 grid station
or fed from 400/132kV grid station

- Rated current (IEC rating ) A 2500A

CTs in separate compartment Yes/No

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 5 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

Internal arcing withstand time

2. CIRCUIT BREAKERS

Type and Model designation

Standards IEC 62271-100

Common enclosed phases Yes/No

Electrical endurance class Class E1

Restrike performance class Class C2

Mechanical endurance class Class M2

Ratings :

Rated current of feeders at 40 C, IEC


A 1600A
rating

Rated current of feeders at 50C A

Rated current of IBT bays at 40 C,


A 1600A
IEC rating.

Rated current of IBT bays at 50 C A

Rated current Bus coupler at 40 C,


IEC rating.
A 3150 A
Applicable for 400/132 grid station
or fed from 400/132kV grid station

Rated current Bus coupler (IEC


A 2500A
Rating )

Rated short circuit breaking current

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 6 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

- AC component, r.m.s. value kA min. 40

- percentage of DC component %

- DC time constant ms

Rated short time withstand current kA 40


(3s)

Rated short circuit making current kA 100

Rated line charging breaking current A 50

Rated cable charging breaking current A 160

Rated single capacitor bank breaking A 400


current

Rated back to back capacitor bank A 400


breaking current

Rated back to back capacitor bank A 20


inrush making current

Rated small inductive breaking current A

Rated out-of-phase breaking A 10KA


current(factor 2.5)

Maximum inductive breaking current


for switching shunt reactors under site
conditions A

Contact material of Breakers (Kind of


alloy)

Test reports for the all above values Yes/No yes


attached

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 7 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

First-pole-to-clear-factor 1.5

Rated operating sequence of CB O-0.3 sec-CO-


3 min-CO

Closing time ms

- tolerances ms

Dead time ms

- tolerances ms

Break time ms

- tolerances ms

Make time ms

- tolerances ms

Arcing time ms

- tolerances ms

Max. pressure rise in CB due to make Bar abs


or break

Routine test on CB enclosure Bar abs

Pressure type test on CB enclosure Bar abs

Switching over voltage factor Pu

Number of possible operations under

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 8 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

- rated short circuit breaking current No.

- rated normal current No.

Material of main contacts

Arcing quenching medium SF6

Auxiliary contacts :

- number (NO/NC) pcs-pcs As per scheme


requirement

- wiping contacts pcs

- voltage V DC 110

Operating mechanism:

- for closing

- for opening

Making coil:

- number pcs 2

- rated power each W

- DC resistance each Ohms

Trip coil:

- numbers pcs 2

- rated power each W

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 9 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

- DC resistance each Ohms

Motor voltage V DC 110

Motor power W

Spring charging time Sec.

Hand operating facility Yes/No Yes

Rated gas pressure at 20 C Bar abs

Minimum gas pressure at 20 C Bar abs

SF6 lockout pressure at 20 C Bar abs

Setting of pressure relief device Bar abs

Gas quantity of complete CB Kg

3. DISCONNECTORS/ISOLATOR

Type

Standards IEC62271-102

Disconnector endurance class M1

Ratings

Rated current feeders at 40C, IEC A 1600A


rating

Rated current feeders at 50 C A

Rated current Bus coupler/Bus A 3150A

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 10 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

section at 40 C, IEC rating

Applicable for 400/132 grid station


or fed from 400/132kV grid station

Rated current Bus coupler/Bus A 2500A


section (IEC Rating

Rated current of IBT Bays at 40 C, A 1600A


IEC rating.

Rated current of IBT Bays at 50C A

Rated current of bus VT disconnector A


at 40C

Rated current of Bus VT disconnector A


at 50C

Rated short-time withstand current kA 40


(3s)

Rated peak withstand current kA 100

Auxiliary contacts :

- number (NO/NC) pcs/pcs As required

- voltage V DC 110

Operating mechanism: Motor-operated

Motor voltage V DC 110

Motor power W

Hand-operating facilities Yes/no Yes

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 11 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

4. EARTHING SWITCH

a) (MAINTENANCE EARTH SWITCH)

Type

Standards IEC62271-102

Earth switch endurance class

Rated voltage of earth switch KV 10


insulation terminal – Continuous

Rated current of Earth switch A


insulation Terminal

Rated current of Earth switch A 1600A


insulation Terminal (15minutes)

Rated short-time withstand current kA 40


(3s)

Rated peak withstand current kA 100

Auxiliary contacts :

- number (NO/NC) pcs/pcs As required

- voltage V DC 110

Operating mechanism: Motor-


operated

Motor voltage V DC 110

Motor power W

Hand-operating facilities Yes/no Yes

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 12 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

CT primary injection facility for earth Yes/no Yes


switch

B) (FAULT MAKING TYPE)

Type

Standards IEC62271-102

Earth switch endurance class E1

Rated voltage of earth switch KV 10


insulation terminal

Rated current of Earth switch A


insulation Terminal

Rated current of Earth switch A 1600A


insulation Terminal (15 minutes)

Rated short-time withstand current kA 40


(3s)

Rated peak withstand current kA 100

Rated making current kA 100

Auxiliary contacts :

- number (NO/NC) pcs/pcs As required

- voltage V DC 110

Operating mechanism: Motor-charged


spring

Motor voltage V DC 110

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 13 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

Motor power W

Hand-operating facilities Yes/no Yes

CT primary injection facility for earth Yes/no Yes


switch

5. CURRENT TRANSFORMERS

To be filled-in for each type of C.T.


(C.T. data are subject to separate
approval)

- Manufacturer

- Country of Manufacturer

- Insulation level KV

- Years of experience Years

- Type

5.1 IBT BAY CT’S

Transformer differential & Ref.


Protection (Separate core shall be
a) provided as per SLD)

- Ratio A 400/1A

- Class PX

- Vk : Rated knee point voltage V

- Magnetizing current at Vk/2 A

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 14 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

- Rct : secondary winding resistance ohm


at 75 C

b) Over current/earth fault and CB fail


protection

- Ratio A 400/1A

- Class 5P20

- Burden VA

c) Metering/Instruments

- Ratio A 400/1A

- Class 0.2S Fs5

- Burden VA

5.2 IDT BAY CT’s

Transformer differential & Ref.


Protection(Separate core shall be
a) provided as per SLD)

- Ratio A 300/1A

- Class PX

- Vk : Rated knee point voltage V

- Magnetizing current at Vk/2 mA

- Rct : secondary winding resistance ohm


at 75 C

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 15 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

b) Over current/earth fault and CB fail


protection

- Ratio A 300/1A

- Class 5P20

- Burden VA

c) Metering/Instruments

- Ratio A 300/1A

- Class 0.2S Fs5

- Burden VA

5.3 CABLE FEEDER CT’s

a) Fibre Optic current differential


protection

(Main-1) with built in distance

- Ratio A 1200/1

- Class TPY

- Rb : Resistive Burden

- Duty cycle

- Kssc

b) Fibre Optic current differential


protection

(Main-2) with built in distance

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 16 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

- Ratio A 1200/1

- Class TPY

- Rb : Resistive Burden

- Duty cycle

- Kssc

c) Dir. Over current/earth fault and CB


fail protection

- Ratio A 1200/1

- Class 5P20

- Burden VA

d) Instruments and tariff meters :

- Ratio A 1200/1

- Class 0.2 Fs5

- Burden VA

5.4 OHL FEEDER

a) Fibre Optic current differential


protection

(Main-1)

- Ratio A 1200/1

- Class TPY

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 17 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

- Rb : Resistive Burden

- Duty cycle

- Kssc

b) Distance protection(Main-2)

- Ratio A 1200/1

- Class TPY

- Rb : Resistive Burden

- Duty cycle

- Kssc

c) Dir. Over current/earth fault and CB


fail protection

- Ratio A 1200/1

- Class 5P20

- Burden VA

d) Instruments and tariff meters

- Ratio A 1200/1

- Class 0.2 Fs5

- Burden VA

5.5 BUS COUPLER

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 18 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

a) Over current/earth fault & CB Fail


Protection:

- Ratio A 2500/1

- Class 5P20

- Burden VA

b) CB Fail & Instruments:

- Ratio A 2500/1

- Class 5P20

- Burden VA

5.6 Busbar protection CTs – All circuits

(Check zone and Disc. Zone) – Two


cores (For bus coupler on either side
of CB):

- Ratio A 2500/1

- Class PX

- Vk : Knee point voltage V

- Magnetizing current at Vk/2 mA

- Rct : secondary winding resistance ohm


at 75C

6. VOLTAGE TRANSFORMERS

To be filled-in for each type of V.T.


(V.T. data are subject to separate

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 19 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

approval)

- Manufacturer

- Country of Manufacturer

- Type

For protection & metering, synch.


purposes

Ratio : VA

- primary kV 132
3

- secondary V 110 110


,
3 3

- Class of accuracy 0.2/3P for each


ratio/winding

- Rated output VA > 100

- Rated thermal burden VA

- Rated voltage factor 1.2 continuous & 1.9 for 30


seconds

7. LOCAL CONTROL PANELS


(INDOOR):

Manufacturer

Country of origin

Material Sheet steel

Steel thickness (minimum):

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 20 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

- door mm 2.5

- side/top/rear panels mm 2.5

- Mounting plates mm 3

Paint colour - External RAL 7032

Paint thickness (average) Microns 90

Paint thickness (minimum) Microns 80

Dimensions:

- Length mm

- Width mm

- Height mm

- Total net weight Kg.

Control cables connected by plug and Yes/no


socket (Except CT/VT cables)

- At GIS Yes/no

- At LCC Yes/no

Plugs & sockets are non- Yes/no Yes


interchangeable

Degree of protection IP52

Cross section of earth bar Sq.mm 185

Method of mounting control switches Glass panel/

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 21 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

& mimic etc. swing frame

Type of Terminal Blocks:

- CT circuits

- VT circuits

- Other circuits

Voltage grade of wires inside panels KV 0.6/1.0


wiring

Wire cross section:

- CT circuits mm2 4

- VT & AC circuits mm2 2.5

- DC circuits mm2 1.5

Colour code for wiring Yes/no Yes

Shrouds for AC wiring Yes/no Yes

Segregation of wiring of each Yes/no Yes


application

Heater, Humidistat, Heater on/off Yes/no Yes


switch indication

Panel illumination, door switch Yes/no Yes

Socket outlet Yes/no Yes

8. 132 kV CABLE TERMINATIONS

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 22 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

Manufacturer

Country of origin

Applicable standard IEC 62271-209

Type

Rated voltage kV 145

Rated current at 40 C IEC rating A 1600A

Rated current at 50 C A

Rated short time withstand current kA 40


(3sec)

Power frequency withstand voltage kV 275


(1min.) (for GIS test voltage)

Cable HVAC test voltage withstand kV/Hr

Cable HVAC test voltage withstand kV/Minute 650

Lighting impulse withstand voltage kV 650


(1.2/50µ Sec)

Provision for solid bonding Yes/No

Suitable for XLPE cable size mm2 up to 1200

Suitable for periodic sheath test Yes/No Yes

Creepage distance mm

Type test conducted as per relevant Yes/No Yes


standard

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 23 OF 24


132KV GAS INSULATED SWITCHGEAR (GIS) AND LOCAL FEDERAL ELECTRICITY AND WATER AUTHORITY
CONTROL CUBICLE (LCC) TECHNICAL DATA SHEETS TECHNICAL SPECIFICATIONS

Manufacturer catalogue, literature, Yes/No Yes


type test report etc. enclosed

Inbuilt PDM sensors/couplers Yes/No Yes

DATE: TENDERER’S STAMP & SIGNATURE:

FEWA-EL-SWGR-TD-0112, Rev 1, 2016 PAGE 24 OF 24