TECHNICAL OFFER

MV Switchgear, 6.6kV, 1250A, 60Hz, 25kA/1s, IP4X with Tunnel, Bottom Entry
Un: 6.6 kV Ur: 7.2 kV Busbar Ir 1250 A Ik: 25 kA / 1s
Power frequency withstand voltage 60Hz 1 min(rms kV) 20
Lightning impulse withstand voltage 1.2/50 μs (kV peak)
Switchboard Characteristics Short-circuit making current (KA peak) 65
Breaking Technology Vacuum
Total Depth Of One Switchgear / mm 1405 Reference Number: OP-210419-10768099
Total Hight Of One Switchgear / mm 2730
Neutral System Resistance grounded
Incoming Feeder 1250A Outgoing Feeder Outgoing Feeder Outgoing to VFD O2 Blower BBVT
Cubicle Name
Vacuum Pump Air Blower

Product PiX-12 PiX-M PiX-M PiX-12 PiX-12

Cubicle 6.6kV SWBD 1 1 1 1 1


Short time withstand current 25kA /1s 25kA /1s 25kA /1s 25kA /1s 25kA /1s
Internal arc withstand current 25kA /1s 25kA /1s 25kA /1s 25kA /1s 25kA /1s
Frequency 50Hz 50Hz 50Hz 50Hz 50Hz
Depth / mm 1405 1405 1405 1405 1405
Height / mm (with tunnel/ducts) 2730 2730 2730 2730 2730
Width / mm 650 400 400 650 650
Weight (kg) 720 720 720 720 720
Colour RAL 9003 RAL 9003 RAL 9003 RAL 9003 RAL 9003
(Texture : Orange Peel) (Texture : Orange Peel) (Texture : Orange Peel) (Texture : Orange Peel) (Texture : Orange Peel)

Safety Internal Arc Protection AFLR AFLR AFLR AFLR AFLR


Ceiling Height 3330 3330 3330 3330 3330
Altitude (meter) 0m < H < 1000m 0m < H < 1000m 0m < H < 1000m 0m < H < 1000m 0m < H < 1000m
IP Protection Degree IP4X IP4X IP4X IP4X IP4X
Antiseismic Protection NO NO NO NO NO
Marine Application --- --- --- --- ---
Base Frame --- --- --- --- ---

Busbar Busbar Current @ 35˚C 1250 1250 1250 1250 1250


1190 @40oC 1190 @40oC 1190 @40oC 1190 @40oC 1190 @40oC
Main Horizontal Busbars Copper Copper Copper Copper Copper
Main Vertical Busbars Copper Copper Copper Copper Copper
Earthing Busbars Bare Copper Bare Copper Bare Copper Bare Copper Bare Copper
Main Busbar Insulation (Horizontal+Vertical down until CB) Heat Shrinkable Material Heat Shrinkable Material Heat Shrinkable Material Heat Shrinkable Material Heat Shrinkable Material
Busbar Joints Coating No No No No No
Busbar Joints Insulation (insulboot) YES YES YES YES YES
Busbar Segregation YES --- --- YES YES

Withdrawable or Fixed Withdrawable Contactor Withdrawable Contactor


Switching Compartment Withdrawable CB
Elec. Held Elec. Held
Withdrawable CB ---
Type of Breaker HVX12-25-12 CVX 07/ Vacuum + Fuse CVX 07/ Vacuum + Fuse HVX12-25-06 ---
1250A 1250A
Rated current (A) @ 35˚C 400A 400A ---
(1190A @40oC) (1190A @40oC)
Short time withstand current 6kA w/o Fuse 6kA w/o Fuse
25kA /1s 25kA /1s ---
(40kA with fuse) (40kA with fuse)
Close/Open aux. Contact 1W+8NO+7NC 5NO+5NC 5NO+5NC 1W+8NO+7NC ---
CB Draw in/out aux. Contact 2NO+2NC 2NO+2NC 2NO+2NC 2NO+2NC ---
CB interlocking with door YES YES YES YES ---
Sequence Operation O-0.3s-CO-3min-CO --- --- O-0.3s-CO-3min-CO ---
Unpainted Shutters (with marked) YES YES YES YES ---
Fuse Rating --- --- --- --- ---

Circuit breaker Spring Charging Motor 230 VAC --- --- 230 VAC ---
Closing Coil 230 VAC --- --- 230 VAC ---
First Opening Coil 230 VAC --- --- 230 VAC ---
Second Opening Coil --- --- --- --- ---
Undervoltage Coil --- --- --- --- ---
Motorized draw in/draw out CB --- --- --- --- ---
Electromagnet for CB --- --- --- --- ---

Auxiliary Supplies Protective Relay 230 V AC 230 V AC 230 V AC 230 V AC ---


Digital Measurement 230 V AC 230 V AC 230 V AC 230 V AC ---
Control & Signaling 230 V AC 230 V AC 230 V AC 230 V AC ---
Interior Lighting 230 V AC 230 V AC 230 V AC 230 V AC ---
Heating Resistor 230 V AC 230 V AC 230 V AC 230 V AC ---

Contactor Frequency --- 50Hz 50Hz --- ---


Holding Coil 230 VAC 230 VAC
--- --- ---
(from External) (from External)
Mechanical Latch --- --- --- --- ---
3/xxx (Fusarc or Equiv.)' 3/xxx (Fusarc or Equiv.)'
MV Fuse --- Detailed will be conducted during Detailed will be conducted during --- ---
engineering stage engineering stage

Line DS Operation --- --- --- --- ---


Auxiliary contact --- --- --- --- ---

Earthing Switch Switch YES / CABLE YES / CABLE YES / CABLE YES / CABLE ---
Aux. Contact 2NO +2NC 2NO +2NC 2NO +2NC 2NO +2NC ---
Rated short-time withstand current and duration for earthing circuits 25kA /1s 25kA /1s 25kA /1s 25kA /1s ---
Electrical Interlock for ES YES YES
--- --- ---
(with upstream) (with upstream)
Key Interlock for ES and BBES --- YES YES --- ---

Voltage Transformer Q'ty / Manufacturer 3 / Trafindo or equiv. --- --- 3 / Trafindo or equiv. 3 / Trafindo or equiv.
Withdrawable or Fixed Withdrawable without shutter at Withdrawable without shutter at Withdrawable without shutter at
--- ---
cable compartment cable compartment cable compartment
Type Block Type --- --- Block Type Block Type
Primary/Secondary Voltage (kV) 6.6/V3 / 0.11V3 / 0.19/33 --- --- 6.6/V3 / 0.11V3 / 0.19/33 6.6/V3 / 0.11V3 / 0.19/33
1. Secondary Cl. 0.5 30VA --- --- Cl. 0.5 30VA Cl. 0.5 30VA
2. Secondary Cl. 3P 30VA --- --- Cl. 3P 30VA Cl. 3P 30VA
3. Secondary --- --- --- --- ---
Mv fuse YES --- --- YES YES

1st Current Transfomer Q'ty / Manufacturer 3 / Trafindo or equiv. 3 / Trafindo or equiv. 3 / Trafindo or equiv. 3 / Trafindo or equiv. ---
Type Block Type Ring Type Ring Type Block Type ---
Primary/Secondary Current Ratio 1250/5-5 A Ratio 100/5-5 A Ratio 100/5-5 A Ratio 1250/5-5 A ---
1. Secondary Core 1: CL 5P20, burden 15VA Core 1: CL 5P20, burden 2VA Core 1: CL 5P20, burden 2VA Core 1: CL 5P20, burden 15VA ---
2. Secondary Core 2: CL 0.5, burden 15 VA Core 2: CL 0.5, burden 2 VA Core 2: CL 0.5, burden 2 VA Core 2: CL 0.5, burden 15 VA ---
3. Secondary --- --- --- --- ---
Ith 25kA /1s 40kA /1s 40kA /1s 25kA /1s ---

2nd Current Transfomer Q'ty / Manufacturer --- --- --- --- ---
Type --- --- --- --- ---
Primary/Secondary Current --- --- --- --- ---
1. Secondary --- --- --- --- ---
2. Secondary --- --- --- --- ---
3. Secondary --- --- --- --- ---
Ith --- --- --- --- ---

Type ZTA or equiv. (Trafindo or equiv.) CSH200 CSH200 CSH200 CSH200


Core Balance CT (Schneider) (Schneider) (Schneider) (Schneider)
---

Interposing CT Isolsec or equiv. --- --- --- --- ---

Cable Connection Bottom Entry by cable Bottom by Cable Bottom by Cable Bottom Entry by cable ---
Cable Type 2x630mm²/phase 1x240mm²/phase 1x240mm²/phase 2x630mm²/phase ---
Cable Box --- --- --- --- ---
Non Magnetic Gland Plate --- --- --- --- ---
Surge Arrester HE05 (Qty : 3) HE05 (Qty : 3) HE05 (Qty : 3) HE05 (Qty : 3)
---
Tri Delta or equiv. Tri Delta or equiv. Tri Delta or equiv. Tri Delta or equiv.
Voltage Presence Indicators (VPIS) YES YES YES YES ---
Heater for Cable Compartment 230VAC 45W 230VAC 45W 230VAC 45W 230VAC 45W ---

LV Compartment Door Lock YES YES YES YES YES


Internal Lighting YES YES YES YES YES
Outlet Socket ( max 250VAC, 1PH+1N+PE,13A) --- --- --- --- ---

LV Equipment Hygrostat for Heater YES YES YES YES ---


Local Remote Selector Switch YES YES YES YES ---
CB/VCS “On/off” spring return selector switch YES YES YES YES ---
Power Quality Meter --- --- --- --- ---
Multifunction Digital Meter PM5350 --- --- PM5350 ---
Ampere Transducer --- --- --- --- ---
Volt Transducer --- --- --- --- ---
Analog Voltmeter + VSS RISHAB or equiv. RISHAB or equiv. RISHAB or equiv.
--- ---
(Qty : 1) (Qty : 1) (Qty : 1)
Analog Ammeter + ASS RISHAB or equiv. RISHAB or equiv. RISHAB or equiv. RISHAB or equiv. RISHAB or equiv.
(Qty : 1) (Qty : 1) (Qty : 1) (Qty : 1) (Qty : 1)
Run Hour Meter --- --- --- --- ---
Voltage Test Block (YONG SUNG) YES (Qty:2) --- --- YES (Qty:2) YES (Qty:2)
Current Test Box (YONG SUNG) YES (Qty:2) YES (Qty:2) YES (Qty:2) YES (Qty:2) YES (Qty:2)
Alarm Annunciation Window --- --- --- --- ---
Indicating Lamps YES (Qty:3) YES (Qty:3) YES (Qty:3) YES (Qty:3) YES (Qty:3)
(Close, Open, Trip) (Close, Open, Trip) (Close, Open, Trip) (Close, Open, Trip) (Close, Open, Trip)
Aux. Relay (RXM type) As necessary As necessary As necessary As necessary As necessary
MCB As necessary As necessary As necessary As necessary As necessary

Mimic Diagram Standard Adhesive Type Standard Adhesive Type Standard Adhesive Type Standard Adhesive Type Standard Adhesive Type

Protection Relay 1 EASERGY P3U30 EASERGY P3U30 EASERGY P3U30 EASERGY P3U30
Protection Relay Cortex : P3U30-5BAA2BBA Cortex : P3U30-5BAA2BBA Cortex : P3U30-5BAA2BBA Cortex : P3U30-5BAA2BBA
---
Protection ANSI Codes 50/51, 50N/51N, 27/59 50/51, 50N/51N 50/51, 50N/51N 50/51, 50N/51N, 27/59 ---
Communication Protocol Modbus RTU Modbus RTU Modbus RTU Modbus RTU ---
Check synch module --- --- --- --- ---

Protection Relay 2 --- --- --- --- ---


Protection ANSI Codes --- --- --- --- ---
Communication Protocol --- --- --- --- ---
Check synch module --- --- --- --- ---

Protection Relay 3 --- --- --- --- ---


Protection ANSI Codes --- --- --- --- ---
Communication Protocol --- --- --- --- ---
Check synch module --- --- --- --- ---

Packing Seaworthy Seaworthy Seaworthy Seaworthy Seaworthy