SWITCHBOARD GENERAL REQUIREMENTS

PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-80-01

LOCATION: ALGERIA No. REQ'D: 1

PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07

SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH

SPECIFICATION No.: J8328A-E-SP-15001 CONTRACTOR:


ONE LINE DIAG. No.: J8328A-E-DW- CONTRACTOR REFERENCE:
SYSTEM NOMINAL RATING: 60 kV SWITCHBOARD RATED VOLTAGE: 72.5 kV
BUS-BAR SYSTEM RATED CURRENT: 2500 A BUS-BAR INSULATION: SF6
RATED (RMS) WITHSTAND: 31.5 kA DESIGN TEMPERATURE: 40 °C
RATED (RMS) WITHSTAND TIME: 3 Seconds NEUTRAL EARTHING: Solid
ASYMMETRIC PEAK MAKING DUTY: HOLD kA EARTH BAR X SECTION: Rated for full fault level

DEGREE OF PROTECTION: Gas Tight FORM OF SEGREGATION: Individual Panels. Fully segregated

EARTH BAR POSITION: Manufacturers standard DESIGN LIFE: 25 yrs


SHORT CIRCUIT TESTING AUTH.: See note 1 BUS-BAR SYSTEM TEST CERT No.: See note 1
SWITCHBOARD TEST CERT No.: See note 1 CB TEST CERT No.: See note 1
CONTRACTORS TEST CERT No.: See note 1
SWBD. ARRANGEMENT: Front / Rear Access MAXIMUM HEIGHT: 2.5 m
EARTHING REQ: Bus-bars & circuits VIA:
PAINT COLOUR: Refer note 5 EARTH SWITCH FAULT MAKE RATING: Asymmetric peak 'make' rating
CONTROL SUPPLIES:
OPEN / CLOSE 110 V DC SUPPLY INTERNAL / EXTERNAL
SPRING CHARGE 110 V DC SUPPLY INTERNAL / EXTERNAL
PROTECTION RELAYS 110 V DC SUPPLY INTERNAL / EXTERNAL
VT SECONDARIES 110 V AC SUPPLY INTERNAL / EXTERNAL
CABLE ENTRY:
POWER CABLE: BOTTOM / TOP CONTROL CABLE: BOTTOM / TOP
NOTES:
1. Information required with bid
2. Double Bus Bar Arrangement is required
3. All relays to be withdrawable types from the Protection and Control Panels (PCPs)
4. 2 out of 3 auto transfer scheme required for 2 incomers and bus section circuit breakers
5. Refer painting specification J8328A-L-SP-14010
6. Auxiliary enclosures to be protected to IP 31

60kV SWITCHBOARD DATA SHEET

PROJECT DOCUMENT NUMBER Sht No. REV


J8328A-E-DS-15069 2 B1
SWITCHBOARD INCOMERS
PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-80-1
LOCATION: ALGERIA No. REQ'D: 2
PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07
SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH
INCOMER TYPE: CIRCUIT BREAKER
A. BASIC REQUIREMENTS: SUPPLIER'S INFORMATION:
1 NUMBER OF POLES THREE 1. CIRCUIT BREAKER TYPE Refer note 1
2 RATED NORMAL CURRENT 1250A 2. RATED NORMAL CURRENT Refer note 1
3 INTERRUPTING MEDIUM SF6 3. TRIPPING TIME Refer note 1
4 CLOSING MECHANISM (SPRING) MOTOR DRIVEN 4. CLOSING TIME Refer note 1
5 SHORT CCT BREAKING CURRENT HOLD 5. TYPE TEST CERT No. Refer note 1
6 ASYMMETRIC PEAK CURRENT HOLD
7 AUX CONTACTS - WIRED OUT (min) 2 x N/O + 2 x N/C
(additional as required)

B. PROTECTION & INTERLOCKS:


QUANTITY ANSI No. MANUFACTURER TYPE RESET REMARKS
1 DEF. TIME OVERCURRENT 3 51
2 INST. OVERCURRENT 3 50 Auto-transfer block
3 DEF. TIME EARTH FAULT 1 51N
4 INST. EARTH FAULT 50N
5 RESTRICTED E/FAULT 64 (REF)
6 DIRECTIONAL 67
7 DIFFERENTIAL 87
8 PILOT WIRE 85
9 LOCKOUT RELAY 1 86
10 TRIP SEND/RECEIVE 1 94
11 UNDERVOLTAGE 1 27 3 Phase
12 OVERVOLTAGE 1 59
13 THERMAL RELAY 49
14 UNDER/OVER FREQUENCY 1 81
15 TRIP CIRCUIT SUPERVISION 1
16 REVERSE POWER
17 CHECK SYNCH 1 25
18 TIMER
19 DISTANCE 3 21
20
C. INSTRUMENTATION, METERING & CONTROLS D. CURRENT TRANSFORMERS
REQUIRED SCALE/COLOUR REMARKS RATIO CLASS QUANTITY SERVING ITEMS
1 LOCAL AMMETER √ Protection relay display 1250/1 3 3 C1, C4, C5, C7
2 REMOTE AMMETER C8
3 VOLTMETER √ Protection relay display 1250/1 5P20 3 B1, B2, B3, B19
4 PWR FACTOR MTR √ Protection relay display 1250/1 1 3 Free issue for
5 kW METER √ Protection relay display Fiscal metering
6 FREQUENCY METER √ Protection relay display
7 kWhr METER √ Protection relay display
8 VAR METER √ Protection relay display
9 SELECTOR SWITCH 1 Off / Test / In Service Note: 4-20mA transducer to be provided by
10 PUSH BUTTONS 2 Open / Closed switchgear manufacturer
11 OPERATIONS COUNTER 1
12 CLOSED LAMP 1 WHITE CB Closed
13 OPEN LAMP 1 GREEN CB Open
14 TRIPPED LAMP 1 RED Fault E. VOLTAGE TRANSFORMERS
15 EARTH SWITCH CLOSED LAMP 1 YELLOW Switch closed 60000/110/110√3 3 3ph B11, B12, B14, B19
16 SERVICE POSITION LAMP 1 BLUE CB withdrawn C3, C4, C5, C6, C7
17 TRIP-OFF-CLOSED SWITCH 1 C8
60000/110/110√3 1 3ph Free issue for
fiscal metering

60 kV SWITCHBOARD DATA SHEET


0
PROJECT DOCUMENT NUMBER Sht No. REV
J8328A-E-DS-15069 3 B2
SWITCHBOARD BUS SECTION
PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-01
LOCATION: ALGERIA No. REQ'D: 1
PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07
SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH
BUS SECTION TYPE: CIRCUIT BREAKER
A. BASIC REQUIREMENTS: SUPPLIER'S INFORMATION:
1 NUMBER OF POLES THREE 1. CIRCUIT BREAKER TYPE Refer note 1
2 RATED NORMAL CURRENT 2500A 2. RATED NORMAL CURRENT Refer note 1
3 INTERRUPTING MEDIUM SF6 3. TRIPPING TIME Refer note 1
4 CLOSING MECHANISM (SPRING) MOTOR DRIVEN 4. CLOSING TIME Refer note 1
5 SHORT CCT BREAKING CURRENT HOLD 5. TYPE TEST CERT No. Refer note 1
6 ASYMMETRIC PEAK CURRENT HOLD
7 AUX CONTACTS - WIRED OUT 2 x N/O + 2 x N/C
(additional as required)

B. PROTECTION & INTERLOCKS:


QUANTITY ANSI No. MANUFACTURER TYPE RESET REMARKS
1 DEF. TIME OVERCURRENT 51
2 INST. OVERCURRENT 50
3 DEF. TIME EARTH FAULT 51N
4 INST. EARTH FAULT 50N
5 RESTRICTED E/FAULT 64
6 DIRECTIONAL 67
7 DIFFERENTIAL 87
8 PILOT WIRE 85
9 LOCKOUT RELAY 86
10 TRIP SEND/RECEIVE 1 94
11 UNDERVOLTAGE 2 27 1 each bus-bar (A / B)
12 OVERVOLTAGE
13 THERMAL RELAY 49
14 VROC RELAY
15 TRIP CIRCUIT SUPERVISION 1
16 REVERSE POWER
17 CHECK SYNCH Y 25
18 TIMER
19 LOAD SHEDDING

C. INSTRUMENTATION, METERING & CONTROLS D. CURRENT TRANSFORMERS


REQUIRED SCALE/COLOUR REMARKS RATIO CLASS QUANTITY SERVING ITEMS
1 LOCAL AMMETER √ Protection relay display
2 REMOTE AMMETER
3 VOLTMETER 2 Protection relay display
4 PWR FACTOR MTR √ Protection relay display
5 kW METER √ Protection relay display
6 FREQUENCY METER √ Protection relay display
7 kWhr METER √ Protection relay display
8 VAR METER √ Protection relay display
9 SELECTOR SWITCH 1 Off / Test / In Service
10 PUSH BUTTONS 2 Open / Closed
11 OPERATIONS COUNTER 1
12 CLOSED LAMP 1 WHITE CB Closed
13 OPEN LAMP 1 GREEN CB Open
14 TRIPPED LAMP 1 RED Fault E. VOLTAGE TRANSFORMERS
15 EARTH SWITCH CLOSED LAMP 1 YELLOW Switch closed 60000/110/110√3 4 x 3ph B11, 1 set per bus
16 SERVICE POSITION LAMP 1 BLUE CB withdrawn
17 TRIP-OFF-CLOSED SWITCH 1

60kV SWITCHBOARD DATA SHEET


PROJECT DOCUMENT NUMBER Sht No. REV
J8328A-E-DS-15069 4 B2
SWITCHBOARD OUTGOING CIRCUITS - TRANSFORMER FEEDER
PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-80-01
LOCATION: ALGERIA No. REQ'D: 4
PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07
SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH
OUTGOING CIRCUIT TYPE: CIRCUIT BREAKER
A. BASIC REQUIREMENTS: SUPPLIER'S INFORMATION:
1 NUMBER OF POLES THREE 1. CIRCUIT BREAKER TYPE Refer note 1
2 RATED NORMAL CURRENT 800A 2. RATED NORMAL CURRENT Refer note 1
3 INTERRUPTING MEDIUM SF6 3. TRIPPING TIME Refer note 1
4 CLOSING MECHANISM (SPRING) MOTOR DRIVEN 4. CLOSING TIME Refer note 1
5 SHORT CCT BREAKING CURRENT HOLD 5. TYPE TEST CERT No. Refer note 1
6 ASYMMETRIC PEAK CURRENT HOLD
7 AUX CONTACTS - WIRED OUT 2 x N/O + 2 x N/C
(additional as required)

B. PROTECTION & INTERLOCKS:


QUANTITY ANSI No. MANUFACTURER TYPE RESET REMARKS
1 DEF. TIME OVERCURRENT 3 51
2 INST. OVERCURRENT 3 50
3 DEF. TIME EARTH FAULT 51N
4 INST. EARTH FAULT 64 (REF)
5 INST. UNRESTRICTED E/FAULT 50G
6 DIRECTIONAL 67
7 DIFFERENTIAL Y 87 Located in 5.5kV Switchboard
8 PILOT WIRE 85
9 LOCKOUT RELAY 1 86
10 TRIP SEND/RECEIVE 94
11 UNDERVOLTAGE 27
12 OVERVOLTAGE
13 THERMAL RELAY 49
14 VROC RELAY
15 TRIP CIRCUIT SUPERVISION 1
16 REVERSE POWER
17 CHECK SYNCH
18 TIMER
19 TEMPERATURE Y 26 Transformer winding (by others)

C. INSTRUMENTATION, METERING & CONTROLS D. CURRENT TRANSFORMERS


REQUIRED SCALE/COLOUR REMARKS RATIO CLASS QUANTITY SERVING ITEMS
1 LOCAL AMMETER √ Protection relay display 500/1 3 3 C1, C7, C4
2 REMOTE AMMETER 500/1 5P20 3 B1, B2
3 VOLMETER √ Protection relay display 500/1 X 3 B7, free issue
4 PWR FACTOR MTR √ Protection relay display from 5.5kV
5 kW METER √ Protection relay display swrd.
6 FREQUENCY METER √ Protection relay display manufacturer
7 kWhr METER √ Protection relay display
8 VAR METER √ Protection relay display Note: 4-20mA transducer to be provided by
9 SELECTOR SWITCH 1 OFF / TEST / IN SERVICE switchgear manufacturer
10 PUSH BUTTONS 2 Open / Closed
11 OPERATIONS COUNTER 1
12 CLOSED LAMP 1 WHITE CB Closed
13 OPEN LAMP 1 GREEN CB Open
14 TRIPPED LAMP 1 RED Fault E. VOLTAGE TRANSFORMERS
15 EARTH SWITCH CLOSED LAMP 1 YELLOW Switch closed
16 SERVICE POSITION LAMP 1 BLUE CB withdrawn
17 TRIP-OFF-CLOSED SWITCH 1

60kV SWITCHBOARD DATA SHEET


PROJECT DOCUMENT NUMBER Sht No. REV
J8328A-E-DS-15069 5 B1