You are on page 1of 33

Electrical documentation for Transformer

2000kVA Distribution Transformer - 501LV100T01


1000kVA Converter duty Transformer - 531FN510T01

Client : Arghakhanchi Cement Pvt. Ltd, Nepal


Project : Cement Grinding Line 2 - VRM OK 27-4
Contract No. : 8001645705
FLS Doc.No. : 60169557
Version : 1.0

2.0 27-Apr-18 Internal revision Vendor PAN-IN DP-IN


1.0 28-Mar-18 First submission Vendor PAN-IN DP-IN
Ver. no. Date Description Prepared by Checked by Approved By
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47841/1 Tag No.: 501LV100T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
1 GENERAL
VOLTMAP
1 Manufacturer's Name TRANSFORMER
LTD.
2 Collaboration, if any
3 Quantity No's 1 NO.
4 Reference standard IS 2026
5 Reference list for similar supplies enclosed Yes/No --
Printed leaflets and catalogues for the equipment
6 Yes/No --
enclosed
2 TECHNICAL
1 Rated output - ONAN KVA 2000
2 Rated No load Voltage - HV KV 6.6
- LV KV 0.433
3 Rated current - HV Amps 174.95
- LV Amps 2666.74
2% of FLRC &
4 No-load current - HV Amps (100%&110%)
3% of FLRC
2% of FLRC &
- LV Amps (100%&110%)
3% of FLRC
5 No. of phases 3
6 Installation OUT DOOR
7 Type of cooling ONAN
8 IP class IP 55
9 Rated Frequency Hz 50
10 Voltage variation % +/-10%
11 Frequency variation % +/-5%
12 Combined variation % +/-10%
13 Short circuit rating of transformer
Primary KA 31.5 kA for 1 sec.
Secondary KA 50 kA for 1 sec.
14 System Earthing
Primary Resistive
Secondary Solid
15 Number of winding Two
16 HV winding
Max Current density – wdg A/mm2 3.5A/mm2
Max Current density – bushing A/mm2 ≤ 1.8A/mm2
17 LV winding
Max Current density – wdg A/mm2 3.5A/mm2
Max Current density – bushing A/mm2 ≤ 1.8A/mm2
18 Reference ambient temperature Deg C 50 deg.C
19 Temp. rise at full load (over 55 deg C ambient )
- Winding Deg C 50
- Oil Deg C 55
98Deg. C Over an
20 Hot spot temperature rise Deg C ambient Temp. of 32
Deg. C
21 NCT Details with ratio and CT type -
Three phase dead short-circuit at terminal with rated
22 voltage maintained on the other side Sec 2

Single phase short circuit at terminal with rated


23 voltage maintained on other side Sec 2

3 No load current
1 At 50% Rated Voltage Amps 0.75% of FLRC
2 At 75% Rated Voltage Amps 0.8% of FLRC
3 At 90% Rated Voltage Amps 1% of FLRC

1 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47841/1 Tag No.: 501LV100T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
4 At 100% Rated Voltage Amps 2% of FLRC
5 At 110 % Rated Voltage Amps 3% of FLRC
4 No load Power factor
1 At 50% Rated Voltage 0.2 (Approx.)
2 At 75% Rated Voltage 0.2 (Approx.)
3 At 90% Rated Voltage 0.2 (Approx.)
4 At 100% Rated Voltage 0.2 (Approx.)
5 At 110 % Rated Voltage 0.2 (Approx.)
5 Range of variation of transformation
1 Ratio +5% to –5% @ 2.5%
2 a) Increasing ratio with steps
'2.5%
3 b) Decreasing ratio with steps
6 TAP CHANGER OCTC
1 Make & size of tap changer PARAGON
PA/110/R2 &
2 Model and Type of tap changer
BRIDGE
3 Type of coolant ONAN
7 Voltage regulation at full load at 75 Deg. C Voltage
1 a) At unity P.F. 100% / 110% 1.612% / 1.807%
2 b) At 0.8 lagging P.F. 100% / 110% 5.929% / 6.539%
8 GUARANTEED LOSSES
No-load loss at rated voltage and frequency (with &
1 KW (HV&LV) 1.95KW(Max.)
without IS tolerances)
No-load loss at 110% voltage and frequency (with &
2 KW (HV&LV) 2.14KW(Max.)
without IS tolerances)
Copper loss at rated current at 75 Deg.C (Max) with
3 KW 26KW(Max.)
& without IS Tolerances
4 Fan Losses KW NA
Load loss @ 50 % at rated current at 75 Deg.C
5 KW (HV&LV) 13 KW (Approx)
(Max)with and without IS Tolerances
Load loss @ 100 % at rated current at 75 Deg.C
6 KW (HV&LV) 26 KW (Max.)
(Max)with and without IS Tolerances
Total losses in rated voltage, freequncy and current
7 KW (HV&LV) 27.95 KW
@ 75 DegC
8 Tolerance on losses As per spec MAXIMUM
Efficiency at normal ratio with unity and 0.8
9 P.F
lagging P.F. at 75 Deg. C with following loads :
1 a) 110% load 1.0 / 0.8 98.50 / 98.14
1 b) 100% load 1.0 / 0.8 99.62 / 98.28
2 c) 80% load 1.0 / 0.8 98.85 / 98.57
3 d) 60% load 1.0 / 0.8 99.07 / 98.84
4 e) 50% load 1.0 / 0.8 99.16 / 98.95
5 f) 40% load 1.0 / 0.8 99.24 / 99.05
6 g) 20% load 1.0 / 0.8 99.26 / 99.07
10 MVA at which Max. efficiency occurs % 27.38 % Load
1 Max Efficiency % 99.29%
11 Connections (a) High voltage Star/Delta Delta
1 (b) Low voltage Star/Delta Star
12 Vector group Dyn11
Reactance at rated current and frequency at 75
13 Percentage 7.894
Deg. C
Impedance at rated voltage, frequencyand
14 % 8% (IS Tolerence)
current at 75 Deg. C
1 Positive sequence impedance % 8% (IS Tolerence)
2 Zero sequence impedance % (HV & LV) as per tested value
3 Negative sequence impedance % 8% (IS Tolerence)
HV - 0.325 Ohms, LV -
15 Resistance at 75 Deg. C HV/LV ( Approx.) Ohm (HV & LV) 0.451m.Ohms

2 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47841/1 Tag No.: 501LV100T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
16 Zero Sequence capacitance of HV winding uF/ph NA
17 X/R ratio 6.07
18 Per unit Value P.U 8% (IS Tolerence)
18.a Insulation strength of high voltage winding
1 a) Impulse test KV peak 60
2 b) Power frequency test KV rms 20
19 Insulation strength of low voltage winding
1 a) Impulse test KV peak NA
2 b) Power frequency test KV rms 3
20 Insulation strength of HVN / LVN winding
1 a) Impulse test KV peak 60 / NA
2 b) Power frequency test KV rms 20 / NA
Overload capacity of transformer both under hot
21
and cold conditions with following overloads:
1 - 10% Sec
2 - 20% Sec
3 - 30% Sec
AS PER IS 6600
4 - 50% Sec
5 - 75% Sec
6 - 100% Sec
7 Parallel operation Among Themselves
Maximum flux density at rated voltage and
22
frequency
1 At 75% Rated Voltage Tesla 1.24
2 At 90% Rated Voltage Tesla 1.48
3 At 100% Rated Voltage Tesla 1.65
4 At 110 % Rated Voltage Tesla 1.81
5 Magnetizing current % 2% of FLRC
23 Tank
1 Material MS
2 Type MS
3 Thickness of sides 5 mm
4 Thickness of Bottom 6 mm
5 Thickness of Top 10 mm
6 Conservator type Conventional Type
Max. internal pressure withstand capacity of tank &
7 As per CBIP
OLTC tank
8 Atmoseal type and breather as backup. Provided Yes/No Yes
24 Core
1 Type - core or Shell CORE
2 Core material & grade M4 OR Better
3 Thickness of lamination mm 0.23-0.27mm approx
4 Insulation of lamination mm Carlite
5 Equivalent cross section area mm2 456.44 Sq.cm
25 Winding
1 Type of Coil
a) H V Disc
b) L V Spiral
2 Conductor material Mat Copper
3 Insulating material
a) H V - Turn Mat Kraft paper
b) L V - Turn Mat Kraft paper
c) L V - Core Mat Paper + Oil
d) H V - L V Mat Paper + Oil +
4 Insulation Material thickness
a) H V - Turn Mat 0.4
b) L V - Turn Mat 0.45
c) L V - Core Mat 1.5
d) H V - L V Mat 2

3 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47841/1 Tag No.: 501LV100T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
5 Area of cross section of conductor
HV winding mm 33.84 Sq.mm
LV winding mm 736.92 Sq.mm
6 Insulation class of winding class A
26 Termination connection
1 - High voltage (Outdoor Bushing/Cable Box) Cable Box
2 - Low voltage (Busduct/Cable Box) Cable Box
3 Neutral bushing been provided outside the Yes/No Yes
27 Marshalling Box
1 Degree of protection IP 55
Provided with removable gland plate/ conduit Removable Gland
2
Knockout Plate
28 Terminal Block
1 Make Elmex/Connect Well
2 Type Stud Type
3 20 % spare furnished Yes/No Yes
29 Wiring
1 Cable Type PVC Armoured
2 Voltage grade Volt 1100
3 Conductor size Sq.mm 1.5
30 Trip & Alarm Contacts Ratings OTI & WTI
1 Voltage grade Volt 250 VAC / 250 VDC
2 Rated/making current Amp 5 A / 0.5 A
31 Accessories
Each transformer furnished with fittings
1 and accessories as per Annexure ? Yes/No As per Drawing

32 WEIGHT
1 Total weight of transformer with oil Kg 6125
2 Core and Frame Kg 1750
3 Weight of core and winding Kg 3000
4 Weight of Oil Kg 1375
33 DIMENSION
1 Dimensions of transformer
- Length mm
- Height mm Refer Drawing
- width mm
2 Clearance height for lifting core and winding from mm
3 Transformer Roller center to center distance mm 1000
4 Minimum clearance
HV
Between Phases
a) In oil mm 10
b) In air mm 130
Between Phase - earth
a) In oil mm 20
b) In air mm 80
LV
Between Phases
a) In oil mm NA
b) In air mm 25
Between Phase - earth
a) In oil mm 5
b) In air mm 20
5 Minimum clearance between HV and LV phases
a) In oil mm ---
b) In air mm -
6 NOISE Level, less than 75 DB Yes/No DB As per NEMA Std

4 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47841/1 Tag No.: 501LV100T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
7 Top winding and yoke mm 20mm
8 Bottom winding and yoke mm 5mm
34 Total quantity of oil Litres
1 10% Spare oil Yes/No Yes
35 Shipping data
1 Weight of the heaviest package Kg 5205
2 Dimensions of the largest package (L x B x H) mm 2750 x 1850 x 2675
List of transformer fittings enclosed but not
36 Yes/No
limited please follow the specification
37 List of transformer protections provided :
1 a) Oil temperature
PERFECT Control /
- Make
PRECIMEASURE
- Type Dial Type
- Provision for Alarm & trip Yes/No Yes
contacts Yes
2 b) Winding temperature
PERFECT Control /
- Make
PRECIMEASURE
- Type Dial Type
- Provision for Alarm & trip Yes/No Yes
contacts Yes
3 Local WTI and OTI with Digital Display provided Yes/No No
4 c) Buchholz Relay
ATVUS / PRAYOG /
- Make
I&C
- Type REED Type
- Provision for Alarm & trip Yes/No Yes
contacts Yes
5 d) Oil level gauge (In main tank and Conservator)
ATVUS / SUKRUT /
- Make
I&C
Magnetic Oil Level
- Type
Guage
- Provision for Alarm & trip Yes/No Alarm Only
contacts Yes
e) Have all the alarm and trip contactsbeen wired
6 Yes/No Yes
upto terminal box
f) Pressure relief device with trip contact provided
7 Yes/No Yes
for main tank and OLTC tank
38 Details of Bushings (HV/HVN/LV/LVN)
Porcelain / Epoxy
1 Type and make CJI/JP/AP/Reputed /
BB/FF/Epothane/Repu
2 Rated voltage KV 17.5 kv / 1
Momentary power frequency dry withstand HV 38 KV rms
3 KV
voltage (HV/HVN/LV/LVN) LV 5KV r.m.s
HV 38 KV rms
4 Visible power frequency discharge voltage KV
LV 5KV r.m.s
Under oil flash over or puncture withstand power HV 38 KV rms
5 KV
frequency voltage LV 5KV r.m.s
6 Full wave withstand impulse voltage KVp 95
7 Creepage distance in air (31 mm/KV) Yes/No 31mm/ kV
HV - Drg 4.7 LV-
8 Weight of assembled bushing Kg
18KG/Unit
9 Reference standards IS 3347
39 OFF Circuit Tap Changer

5 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47841/1 Tag No.: 501LV100T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
1 Make PARAGON
2 Collaboration, if any -
3 Reference standard IEC 60214
4 Type bridge
5 Operating Voltage kV 11
6 Tap range Range +5% to -5%
7 Curent Rating 150
8 No of Poles 5
9 Number of steps Steps 4
10 Voltage per steps variation % 2.5%
11 Taps above nominal voltage 2
12 Taps below nominal voltage 4
13 Tapping on Winding HV
14 Control Local/Remote/Manu Manual
15 Auxiliary supply NA
40 Drawings/data
1 GA 3GA-47841/0
2 Foundation plan 4FD-47841/0
2950 X 3475 X 2950
3 Dimension ( LXWXH)
MAX.
4 BOM As per GA Drawing
5 wiring diagram 3WD-47841/0
3HC-47841/0 &
6 HV & LV Cable Box details
3LC-47841/0
41 Paint shade
1 External Surface 632 of IS 5
Oil & Heat
2 Internal Surface
Resistance Paint
3 Type of painting Epoxy
42 Accessories
1 List of accessories shall be provided along with offer As Per GA Drawing
2 Recommended spares NA
43 Spares
1 2 Year Spares Yes/No Not Applicable
2 Operational Spares Yes/No NA
44 Test
1 Test shall be performed as per specification Yes/No As per QAP

6 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47842/1 Tag No.: 531NF510T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
1 GENERAL
VOLTMAP
1 Manufacturer's Name TRANSFORMER
LTD.
2 Collaboration, if any
3 Quantity No's 1 NO.
4 Reference standard IS 2026
5 Reference list for similar supplies enclosed Yes/No --
Printed leaflets and catalogues for the equipment
6 Yes/No --
enclosed
2 TECHNICAL
1 Rated output - ONAN KVA 1000
2 Rated No load Voltage - HV KV 6.6
- LV KV 0.720-0.720
3 Rated current - HV Amps 87.47
- LV Amps 400.94-400.94
4 No-load current - HV Amps (100%&110%) 3% / 4.5% of FLRC
- LV Amps (100%&110%) 3% / 4.5% of FLRC
5 No. of phases 3
6 Installation OUT DOOR
7 Type of cooling ONAN
8 IP class IP 55
9 Rated Frequency Hz 50
10 Voltage variation % +/-10%
11 Frequency variation % +/-5%
12 Combined variation % +/-10%
13 Short circuit rating of transformer
Primary KA 31.5 kA for 1 sec.
Secondary KA 50 kA for 1 sec.
14 System Earthing
Primary Resistive
Secondary Floating
15 Number of winding Three
16 HV winding
Max Current density – wdg A/mm2 3.5A/mm2
Max Current density – bushing A/mm2 ≤ 1.8A/mm2
17 LV winding
Max Current density – wdg A/mm2 3.5A/mm2
Max Current density – bushing A/mm2 ≤ 1.8A/mm2
18 Reference ambient temperature Deg C 50 deg.C
19 Temp. rise at full load (over 55 deg C ambient )
- Winding Deg C 50
- Oil Deg C 55
98Deg. C Over an
20 Hot spot temperature rise Deg C ambient Temp. of 32
Deg. C
21 NCT Details with ratio and CT type -
Three phase dead short-circuit at terminal with rated
22 voltage maintained on the other side Sec 2

Single phase short circuit at terminal with rated


23 voltage maintained on other side Sec 2

3 No load current
1 At 50% Rated Voltage Amps 1.0% of FLRC
2 At 75% Rated Voltage Amps 1.5% of FLRC
3 At 90% Rated Voltage Amps 1.8% of FLRC
4 At 100% Rated Voltage Amps 3% of FLRC
5 At 110 % Rated Voltage Amps 4.5% of FLRC

1 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47842/1 Tag No.: 531NF510T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
4 No load Power factor
1 At 50% Rated Voltage 0.2 (Approx.)
2 At 75% Rated Voltage 0.2 (Approx.)
3 At 90% Rated Voltage 0.2 (Approx.)
4 At 100% Rated Voltage 0.2 (Approx.)
5 At 110 % Rated Voltage 0.2 (Approx.)
5 Range of variation of transformation
1 Ratio +5% to –5% @ 2.5%
2 a) Increasing ratio with steps
'2.5%
3 b) Decreasing ratio with steps
6 TAP CHANGER OCTC
1 Make & size of tap changer PARAGON
2 Model and Type of tap changer BRIDGE
3 Type of coolant ONAN
7 Voltage regulation at full load at 75 Deg. C Voltage
1 a) At unity P.F. 100% / 110% 1.515% / 1.679%
2 b) At 0.8 lagging P.F. 100% / 110% 4.045% / 4.454%
8 GUARANTEED LOSSES
No-load loss at rated voltage and frequency (with &
1 KW (HV&LV) 1.50KW(Max.)
without IS tolerances)
No-load loss at 110% voltage and frequency (with &
2 KW (HV&LV) 2.2KW(APPROX.)
without IS tolerances)
Copper loss at rated current at 75 Deg.C (Max) with
3 KW 14.00KW(Max.)
& without IS Tolerances
4 Fan Losses KW NA
Load loss @ 50 % at rated current at 75 Deg.C
5 KW (HV&LV) NA
(Max)with and without IS Tolerances
Load loss @ 100 % at rated current at 75 Deg.C
6 KW (HV&LV) NA
(Max)with and without IS Tolerances
Total losses in rated voltage, freequncy and current
7 KW (HV&LV) 15.50KW(Max.)
@ 75 DegC
8 Tolerance on losses As per spec MAXIMUM
Efficiency at normal ratio with unity and 0.8
9 P.F
lagging P.F. at 75 Deg. C with following loads :
1 a) 110% load 1.0 / 0.8 98.35% / 97.95%
1 b) 100% load 1.0 / 0.8 98.47% / 98.10%
2 c) 80% load 1.0 / 0.8 98.71% / 98.39%
3 d) 60% load 1.0 / 0.8 98.92% / 98.66%
4 e) 50% load 1.0 / 0.8 99.01% / 98.77%
5 f) 40% load 1.0 / 0.8 99.07% / 98.84%
6 g) 20% load 1.0 / 0.8 98.98% / 98.73%
10 MVA at which Max. efficiency occurs % 32.73% LOAD
1 Max Efficiency % 99.09%
11 Connections (a) High voltage Star/Delta Delta
1 (b) Low voltage Star/Delta Delta - Star
12 Vector group Dd0yn11
Reactance at rated current and frequency at 75
13 Percentage 4.80%
Deg. C
Impedance at rated voltage, frequencyand
14 % 5.00% (IS Tol.)
current at 75 Deg. C
1 Positive sequence impedance % 5.00% (APPROX.)
+/-10% of Measured
2 Zero sequence impedance % (HV & LV)
Value
3 Negative sequence impedance % 5.00% (IS Tol.)
15 Resistance at 75 Deg. C HV/LV ( Approx.) Ohm (HV & LV) 1.40%
16 Zero Sequence capacitance of HV winding uF/ph NA
17 X/R ratio 3.42
18 Per unit Value P.U 5.00% (IS Tol.)

2 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47842/1 Tag No.: 531NF510T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
18.a Insulation strength of high voltage winding
1 a) Impulse test KV peak 60
2 b) Power frequency test KV rms 20
19 Insulation strength of low voltage winding
1 a) Impulse test KV peak NA
2 b) Power frequency test KV rms 3
20 Insulation strength of HVN / LVN winding
1 a) Impulse test KV peak 60 / NA
2 b) Power frequency test KV rms 20 / NA
Overload capacity of transformer both under hot
21
and cold conditions with following overloads:
1 - 10% Sec
2 - 20% Sec
3 - 30% Sec
AS PER IS 6600
4 - 50% Sec
5 - 75% Sec
6 - 100% Sec
7 Parallel operation Among Themselves
Maximum flux density at rated voltage and
22
frequency
1 At 75% Rated Voltage Tesla 1.23
2 At 90% Rated Voltage Tesla 1.48
3 At 100% Rated Voltage Tesla 1.65
4 At 110 % Rated Voltage Tesla 1.81
5 Magnetizing current % 2% of FLRC
23 Tank
1 Material MS
2 Type MS
3 Thickness of sides 4
4 Thickness of Bottom 5
5 Thickness of Top 8
6 Conservator type Conventional Type
Max. internal pressure withstand capacity of tank &
7 As per CBIP
OLTC tank
8 Atmoseal type and breather as backup. Provided Yes/No Yes
24 Core
1 Type - core or Shell Core Type
2 Core material & grade CRGO & M4 or
3 Thickness of lamination mm 0.23 to 0.27 (approx)
4 Insulation of lamination mm CARLITE
5 Equivalent cross section area mm2 380 sq.cm (approx)
25 Winding
1 Type of Coil
CONT. DISC /
a) H V
LAYER
b) L V SPIRAL
2 Conductor material Mat Electrolytic Coppper
3 Insulating material
a) H V - Turn Mat Kraft paper
b) L V - Turn Mat Kraft paper
c) L V - Core Mat Paper + Oil
d) H V - L V Mat Paper + Oil +
4 Insulation Material thickness
a) H V - Turn Mat 0.4
b) L V - Turn Mat 0.45
c) L V - Core Mat 5
d) H V - L V Mat 18
5 Area of cross section of conductor
HV winding mm 14.5 sq.mm

3 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47842/1 Tag No.: 531NF510T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
LV winding mm 240 sq.mm
6 Insulation class of winding class A
26 Termination connection
1 - High voltage (Outdoor Bushing/Cable Box) Cable Box
2 - Low voltage (Busduct/Cable Box) Cable Box
3 Neutral bushing been provided outside the Yes/No Yes
27 Marshalling Box
1 Degree of protection IP 55
Provided with removable gland plate/ conduit Removable Gland
2
Knockout Plate
28 Terminal Block
1 Make Elmex/Connect Well
2 Type Stud Type
3 20 % spare furnished Yes/No Yes
29 Wiring
1 Cable Type PVC Armoured
2 Voltage grade Volt 1100
3 Conductor size Sq.mm 1.5
30 Trip & Alarm Contacts Ratings OTI & WTI
1 Voltage grade Volt 250 VAC / 250 VDC
2 Rated/making current Amp 5 A / 0.5 A
31 Accessories
Each transformer furnished with fittings
1 and accessories as per Annexure ? Yes/No As per Drawing

32 WEIGHT
1 Total weight of transformer with oil Kg 4075 Kg.
2 Core and Frame Kg 1290 kg Approx
3 Weight of core and winding Kg 1775 Kg.
4 Weight of Oil Kg 850Kg.
33 DIMENSION
1 Dimensions of transformer
- Length mm
- Height mm Refer Drawing
- width mm
2 Clearance height for lifting core and winding from mm
3 Transformer Roller center to center distance mm 800
4 Minimum clearance
HV
Between Phases
a) In oil mm 10
b) In air mm 90
Between Phase - earth
a) In oil mm 20
b) In air mm 70
LV
Between Phases
a) In oil mm 10
b) In air mm 25
Between Phase - earth
a) In oil mm 10
b) In air mm 20
5 Minimum clearance between HV and LV phases
a) In oil mm 13
b) In air mm 90
6 NOISE Level, less than 75 DB Yes/No DB As per NEMA Std
7 Top winding and yoke mm 20mm
8 Bottom winding and yoke mm 20mm

4 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47842/1 Tag No.: 531NF510T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
34 Total quantity of oil Litres
1 10% Spare oil Yes/No Yes
35 Shipping data
1 Weight of the heaviest package Kg 3465 Approx.
2 Dimensions of the largest package (L x B x H) mm 2500 X 2000 X 2475
List of transformer fittings enclosed but not
36 Yes/No
limited please follow the specification
37 List of transformer protections provided :
1 a) Oil temperature
PERFECT Control /
- Make
PRECIMEASURE
- Type Dial Type
- Provision for Alarm & trip Yes/No Yes
contacts Yes
2 b) Winding temperature
PERFECT Control /
- Make
PRECIMEASURE
- Type Dial Type
- Provision for Alarm & trip Yes/No Yes
contacts Yes
3 Local WTI and OTI with Digital Display provided Yes/No No
4 c) Buchholz Relay
ATVUS / PRAYOG /
- Make
I&C
- Type -
- Provision for Alarm & trip Yes/No Yes
contacts Yes
5 d) Oil level gauge (In main tank and Conservator)
ATVUS / SUKRUT /
- Make
I&C
Magnetic Oil Level
- Type
Guage
- Provision for Alarm & trip Yes/No Alarm Only
contacts Yes
e) Have all the alarm and trip contactsbeen wired
6 Yes/No Yes
upto terminal box
f) Pressure relief device with trip contact provided
7 Yes/No Yes
for main tank and OLTC tank
38 Details of Bushings (HV/HVN/LV/LVN)
Porcelain / Epoxy
1 Type and make CJI/JP/AP/Reputed /
BB/FF/Epothane/Repu
2 Rated voltage KV 17.5 kv / 1
Momentary power frequency dry withstand HV 38 KV rms
3 KV
voltage (HV/HVN/LV/LVN) LV 5KV r.m.s
HV 38 KV rms
4 Visible power frequency discharge voltage KV
LV 5KV r.m.s
Under oil flash over or puncture withstand power HV 38 KV rms
5 KV
frequency voltage LV 5KV r.m.s
6 Full wave withstand impulse voltage KVp 95
7 Creepage distance in air (31 mm/KV) Yes/No 31mm/ kV
HV - Drg 4.7 LV-
8 Weight of assembled bushing Kg
18KG/Unit
9 Reference standards IS 3347
39 OFF Circuit Tap Changer
1 Make PARAGON
2 Collaboration, if any -

5 of 6
Technical Datasheet for Distribution (Detail Engineering)

Customer: FLSMIDTH Privat Limited, Chennai

JN 47842/1 Tag No.: 531NF510T01

Project : Arghakhanchi Cements Private Limited, NEPAL-EXPORT Project.


Equipment: Distribution Transformer Transformer Rating
SNo. Parameters Unit Vendor to fill
3 Reference standard IEC 60214
4 Type bridge
5 Operating Voltage kV 11
6 Tap range Range +5% to -5%
7 Curent Rating 100
8 No of Poles 5
9 Number of steps Steps 4
10 Voltage per steps variation % 2.5%
11 Taps above nominal voltage 2
12 Taps below nominal voltage 2
13 Tapping on Winding HV
14 Control Local/Remote/Manu Manual
15 Auxiliary supply NA
40 Drawings/data
1 GA 3GA-47842/0
2 Foundation plan 4FD-47842/0
2675 X 2600 X 2450
3 Dimension ( LXWXH)
(+5%)
4 BOM As per GA Drawing
5 wiring diagram 3WD-47842/0
3HC-47842/0 &
6 HV & LV Cable Box details
3LC-47842/0
41 Paint shade
1 External Surface 632 of IS 5
Oil & Heat
2 Internal Surface
Resistance Paint
3 Type of painting Epoxy
42 Accessories
1 List of accessories shall be provided along with offer As Per GA Drawing
2 Recommended spares NA
43 Spares
1 2 Year Spares Yes/No Not applicable
2 Operational Spares Yes/No NA
44 Test
1 Test shall be performed as per specification Yes/No As per QAP

6 of 6