TP DIVISION- TRANSMISSION COMMISSIONING DEPARTMENT

SITE TEST REPORT


CONTRACT NO: PO#3761800059 NAME OF SUB STATION: 132/11kV JUMSOUTH SUBSTATION
Main Contractor CENTAUR Name of Bay: E03 - 132KV BRSH-2 FEEDER,
Consultant: ---- Equipment: 132kV VOTAGE TRANSFORMER Page 1 of 3
Manufacturer TRENCH SCADA No: C1070 DATE 05.08.2022

INSPECTION AND TESTING OF PHASE VOLTAGE TRANSFORMER

1. CHARACTERISTICS
MAKE: TRENCH
TYPE: SUD145/S92
SERIAL NO. 18/3011308
NO. OF CORES 2  

Core 1 Core 2
Pry 132kV/√3 132kV/√3
Ratio
Sec 110V/√3 110V/√3
Class 0.5/3P 0.5/3P
Burden (VA) 100VA 30VA
Rated Voltage 145kV 145kV
R 1c-1cn 2c-2cn
VT Ter.
Y 1a-1an 2a-2an
No.
B 1b-1bn 2b-2bn
VT R XEW1-1 XEW2-1
Terminal Y XEW1-3 XEW2-4
Block B XEW1-5 XEW2-7
No. N XEW1-7,8,9 XEW2-10,11,12
Purpose M1FP & M2FP DFR,BCU & BVS

2. MECHANICAL AND ELECTRICAL CHECKS

   R Phase Y Phase B Phase


GENERAL VISUAL INSPECTION OK OK OK
NAME PLATE OK OK OK
TIGHTNESS OF CONNECTIONS AT VT SEC. TERMINALS OK OK OK
TIGHTNESS OF CONNECTIONS AT VT SEC. TERMINAL BLOCKS
OK OK OK
(LV COMPARTMENT)
EARTHING OF PRIMARY NEUTRAL TERMINAL OK OK OK
SECONDARY EARTHING CORE 1 & 2 OK OK OK
CONFIRMATION OF RATING OF FUSES IN VT TERMINAL BOX
NA NA NA
AS SPECIFIED IN DRAWING

DEWA/TP/TCD/132 kV/P31/VT. Rev.3.


TP DIVISION- TRANSMISSION COMMISSIONING DEPARTMENT
SITE TEST REPORT
CONTRACT NO: PO#3761800059 NAME OF SUB STATION: 132/11kV JUMSOUTH SUBSTATION
Main Contractor CENTAUR Name of Bay: E03 - 132KV BRSH-2 FEEDER,
Consultant: ---- Equipment: 132kV VOTAGE TRANSFORMER Page 2 of 3
Manufacturer TRENCH SCADA No: C1070 DATE 05.08.2022

INSPECTION AND TESTING OF PHASE VOLTAGE TRANSFORMER

3. INSULATION RESISTANCE MEASUREMENT.


a. Confirm Isolation of links of VT Terminal Blocks.
b. Confirm isolation Primary neutral earthing link
c. IR Values to be measured up to VT Terminal Blocks.

Ambient Temperature 30.7 ℃ Humidity: 40.6 %


DC
  Voltage R Phase Y Phase B Phase
Applied
Primary to Earth 2.5kV 23.9 GΩ 50.0 GΩ 43.0 GΩ
Primary to Sec. Core 1 2.5kV 40.5 GΩ 59.9 GΩ 63.6 GΩ
Primary to Sec. Core 2 2.5kV 46.1 GΩ 71.4 GΩ 63.2 GΩ
Sec. Core 1 to Earth 1000V 23.6 GΩ 21.1 GΩ 36.5 GΩ
Sec. Core 2 to Earth 1000V 28.5 GΩ 24.9 GΩ 30.6 GΩ
Sec. Core 1 to Core 2 1000V 60.7 GΩ 46.8 GΩ 63.5 GΩ

4. POLARITY CHECKS.
  R PHASE Y Phase B Phase
At VT Sec. At LCC At VT Sec. At LCC At VT Sec. At LCC
VT
Terminals Ter. Blocks Terminals Ter. Blocks Terminals Ter. Blocks
Pry. to Core 1 OK OK OK OK OK OK
Pry. to Core 2 OK OK OK OK OK OK

5. WINDING RESISTANCE MEASUREMENT.


Ambient Temperature - t 30.8 0C
CORE R Phase Y Phase B Phase

  R at t0C R at 750C R at t0C R at 750C R at t0C R at 750C

Primary in (kΩ) 41.30 48.44 41.26 48.39 41.29 48.43


Sec. CORE 1 in (mΩ) 61.99 72.71 63.74 74.76 57.66 67.63
Sec. CORE 2 in (mΩ) 61.06 71.62 60.27 70.69 61.77 72.45

Resistance at 750C = Rt (1+0.00393(75–t))

DEWA/TP/TCD/132 kV/P31/VT. Rev.3.


TP DIVISION- TRANSMISSION COMMISSIONING DEPARTMENT
SITE TEST REPORT
CONTRACT NO: PO#3761800059 NAME OF SUB STATION: 132/11kV JUMSOUTH SUBSTATION
Main Contractor CENTAUR Name of Bay: E03 - 132KV BRSH-2 FEEDER,
Consultant: ---- Equipment: 132kV VOTAGE TRANSFORMER Page 3 of 3
Manufacturer TRENCH SCADA No: C1070 DATE 05.08.2022

INSPECTION AND TESTING OF PHASE VOLTAGE TRANSFORMER


6. MAGNETIZING CURRENT MEASUREMENT.

R-N Y-N B-N

 Primary voltage applied in (V) 1316 1320 1317

Primary current measured in (µA) 239.4     219.7 239.9 

7. RATIO TEST.
R Phase Y Phase B Phase
CORE

Error Error Error


Pri-Volts Sec-Volts Pri-Volts Sec-Volts Pri-Volts Sec-Volts
(%) (%) (%)

Core 1 1316 1.098 0.18 1320 1.101 0.09 1317 1.099 0.18

Core 2 1316 1.098 0.18 1320 1.101 0.09 1317 1.099 0.18

TESTING INSTRUMENT DETAILS


PARTICULARS MAKE TYPE SR.NO. CAL. DUE DATE
IR TESTER MEGGER MIT520/2 1000-374/110311/2947 02-06-2023
MULTIMETER FLUKE 87V 30720363 06-07-2023
MULTIMETER FLUKE 87V 22470258 02-06-2023
MULTIMETER FLUKE 87V 30720361 02-06-2023
MICRO OHM METER MEGGER DLRO 10 101122440 21-03-2023
TEMPERATYRE/HUMIDITY
FLUKE 971 367906652 02-06-2023
METER
- - - - -

Tested By Witnessed / Verified By Witnessed / Verified By

Signature

Name PATRIS.J
Organization CENTAUR NA DEWA

DEWA/TP/TCD/132 kV/P31/VT. Rev.3.