REFERENCE R ph Y ph B ph
VOLTAGE
Primary to Earth 520 GΩ 515 GΩ 498 GΩ
Primary to Sec. 1 2.5 KV DC 467 GΩ 283 GΩ 224 GΩ
Primary to Sec. 2 289 GΩ 254 GΩ 245 GΩ
Sec 1 to Earth 35.7 GΩ 37.0 GΩ 37.3 GΩ
Sec.2 to Earth 500 V DC 41.5 GΩ 48.0 GΩ 42.1 GΩ
Sec 1 to Sec 2 44.2 GΩ 51.6 GΩ 51.7 GΩ
4. Sec.Resistance test :
REFERENCES R ph Y ph B ph
1a-1n 0.1 Ω 0.1 Ω 0.1 Ω
2a-2n 0.7 Ω 0.7 Ω 0.7 Ω
Primary A-N 346.2 Ω 345.7 Ω 347.1 Ω
TEST REPORT FOR POTENTIAL TRANSFORMER
5. Polarity Test :
REFERENCES R ph Y ph B ph
1a-1n OK OK OK
2a-2n OK OK OK
6. Ratio Test :
R Phase
Applied voltage in Secondary Measured Voltage in Secondary
(In Volts) Measured
(In Volts)
Current(mA)
Volt % Core-1 (1a-1n) Core 2 (2a-2n)
25 15.87 144.4 15.70
50 31.75 240.9 31.56
75 47.63 0.31 A 47.82
100 63.51 0.42 A 63.27
110 69.86 0.46 A 69.90
R Phase
Applied voltage in Secondary Measured Voltage in Secondary
(In Volts) Measured
(In Volts)
Current(mA)
Volt % Core 2 (2a-2n) Core 1 (1a-1n)
25 15.87 141.3 15.62
50 31.75 244.5 31.81
75 47.63 0.31 A 47.76
100 63.51 0.42 A 63.82
110 69.86 0.48 A 70.2
Y Phase
TEST REPORT FOR POTENTIAL TRANSFORMER
B Phase
Applied voltage in Secondary Measured Voltage in Secondary
(In Volts) Measured
(In Volts)
Current(mA)
Volt % Core-1 (1a-1n) Core 2 (2a-2n)
25 15.87 140.0 15.71
50 31.75 247.7 31.80
75 47.63 0.33 A 47.75
100 63.51 0.49 A 63.73
110 69.86 0.57 A 70.2
B Phase
Applied voltage in Secondary Measured Voltage in Secondary
(In Volts) Measured
(In Volts)
Current(mA)
Volt % Core 2 (2a-2n) Core 1 (1a-1n)
25 15.87 138.4 15.77
50 31.75 243.6 31.86
75 47.63 0.32 47.74
100 63.51 0.49 63.81
110 69.86 0.57 70.4