TEST REPORT FOR HT BREAKER

ELECTROTEST DOC. No :
DATE :
PVT. LTD. TESTING DATE : 20-12-2023
FEEDER :- 2MVA TR-1 FOR HF-1
CLIENT : TSL, JAMSHEDPUR PANEL:- 6.6 KV HT SWBD
Page 1 of 2
LOCATION : NEW S/S ST MILLS FEEDER NO. :- 12

01. EQUIPMENT DETAILS :-

Make L&T Rated Volts 12kV


Name 2MVA TR-1.FOR HF-1 Rated Current 1250 A
Sl. No. M-2022-42 Making Capacity 40kA
Installation INDOOR Breaking Capacity 40kA
Mfg. Year 2022 Operating Duty O-0.3s-CO-3MIN-CO
Type VK10M40H

02. TESTING EQUIPMENT DETAILS:-


CALIBRATION
INSTRUMENT MAKE SL. NO. RANGE
DUE DATE
Digital Insulation tester Motwane A02747J21 0 – 5 KV 12-01-2025
Digital Multimeter Fluke 55030407 0-1000 V 12-01-2025
CRM 100 Scope 2300.06AI0990 0-100 A/0-2000µΩ 12-01-2025
Breaker Time Interval Meter Scope 2100.02AI0832 ----- 12-01-2025

03. INSULATION RESISTANCE MEASUREMENT : ( 2.5 ) KV DC MEGGER FOR 1 MIN.


I.R. VALUE
Reference
Before Hi Pot After Hi Pot Limits
R – R’ 505 GΩ 510 GΩ
Y – Y’ 511 GΩ 515 GΩ
B – B’ 502 GΩ 510 GΩ
R–E 418 GΩ 420 GΩ
Y–E 415 GΩ 419 GΩ ≥100 MΩ
B–E 421 GΩ 422 GΩ
R–Y 247 GΩ 248 GΩ
Y–B 298 GΩ 299 GΩ
B–R 321 GΩ 324 GΩ

04. VCB TIMING TEST :-

PHASE CLOSING TIME ( in ms) TRIP TIME ( in ms) CLOSE – OPEN TIME ( in ms)
TC1 TC2 TC1 TC2
Rph 25 21 23 23 23
Yph 25 21 23 23 23
Bph 25 21 23 24 23
05. VCB CONTACT RESISTANCE TEST :-
REFERENCE MEASURED VALUE NO. OF JOINTS LIMIT REMARKS
TEST REPORT FOR HT BREAKER
ELECTROTEST DOC. No :
DATE :
PVT. LTD. TESTING DATE : 20-12-2023
FEEDER :- 2MVA TR-1 FOR HF-1
CLIENT : TSL, JAMSHEDPUR PANEL:- 6.6 KV HT SWBD
Page 2 of 2
LOCATION : NEW S/S ST MILLS FEEDER NO. :- 12

R – R’ 23 µΩ 05
Y – Y’ 23 µΩ 05 <100 µΩ OK
B – B’ 21 µΩ 05

06. COIL RESISTANCE TEST :


COIL No. MEASURED VALUE RATED VALUE DEVIATION REMARKS
Closing Coil 37.5 Ω 37.2 Ω 0.8% OK
Tripping Coil-1 37.1 Ω 37.2 Ω 0.2% OK
Tripping Coil-2 37.4 Ω 37.2 Ω 0.5% OK
Motor Coil 5.45 MΩ NA NA OK

a) Hi – Pot Test of Close Condition :-


Reference Applied voltage ( AC ) Time in Min Measured Leakage
in KV Current (mA)
R – Y+B+E 14.0 1.0 0.3
Y – R+B+E 14.0 1.0 0.2
B – R+Y+E 14.0 1.0 0.3

b) Hi – pot Test of Open Condition :-


Reference Applied voltage ( AC ) Time in Min Measured Leakage
in KV Current (mA)
R – R’+E 8.0 1.0 0.1
Y – Y’+E 8.0 1.0 0.1
B – B’+E 8.0 1.0 0.1

Remarks:- Test results found satisfactory, BREAKER is fit for service.

TEST PERFORMED BY: TEST WITNESSED BY:


Name : Vishal & Dhanai Name : Nandan kumar
Organization: Electrotest Pvt. Ltd Organization : TSL E&P

Checked by/
ELECTROTEST TSL (E&P) TSL ETD
Approved By
Name: Abhishek Singh
Designation: Manager
Signature.
Date: