You are on page 1of 1

Date/Issuer

-CNHHS/Q Routine Test Report 2022.3.10 / CNHHS/FQC Luke

Three phase metal enclosed switchgear Type Page/Pages Rev.


Report No. ELK-04 G
1/1
1HZC 259 801/T1008669
Device Shipping unit
Order No. 502855105 Rated voltage 170 kV

Locati on Bangladesh Rated power frequency withstand voltage 325 kV

Substation CNTIC Bangladesh Ashuganj 132kV kV


Rated lightning impulse withstand voltage 750

Bay designation E04 Rated frequency 50 Hz

Shipping unit SD10104 Rated short time withstand current


50 kA

Single line diagram 1HZC2 3 20150-02 Rated duration of short-circuit


3 sec

Layout drawing 1HZC2 3 20150-01 Rated peak withstand current kA


125

Gas compartment 3150


1HZC2 3 20150-02 Rated current busbar A

Tests carried out acc. to IEC 62271-203 (Last edition)


1. Resistance of the main circuits ( I = 200 ADC )

measured from ... to ... Desired value R Phase Y Phase B Phase

90F3-20 118  83  88  83 
90EP-140EP 81  59  60  60 
- -  -  -  - 
2. Design and visual checks X All right

3. Power frequency voltage dry test


Min. gas density = min. gas pressure at 20°C, (abs)
According Gas-compartment drawing: 1HZC2 3 20150-02
325 kV, 1min X All right

4. Partial discharge measurement


Partial discharge level at 1.2xUn < 2 pC , 1.5 min X All right

5. Gas tightness test

Test acc. to internal instruction ≤0.1% per year X All right

6. Current transformer
W iring, polarity, rati o, terminal markings acc. to single line diagram X All right

Dielectric test on secondary circuits Vk≥2kV,5 kV 1 min; Vk<2kV, 3kV 1min X All right

Shipping Unit

CNHHS/Q Prepared by Approved by For the client

Date 2022-06-22 2022-06-22

Signature