SITE TEST REPORT SIEMENS

PRE-COMMISSIONING FORMATS FOR CAPACITIVE VOLTAGE TRANSFORMER

I. GENERAL DETAILS DATE OF TESTING – 08/06/2018

DETAILS

Project: 400/220 kV GSS AT JAISALMER (II) Sub-Station: 400/220 kV GSS, RRVPNL, JAISALMER (RJ.)
LOA No. : RVPN/SE(P&P)/XEN/kfw/ICB-1 D.1771 Dated:
Feeder name: BAY 201-M CVT
16-10-2015
Make: SIEMENS Type: TCVT 245

Sr. No.: LINE (CVT) Primary Voltage rating-: 220/√3 kV


R Ø:-2CV2997
YØ:- 2CV2996
BØ:- 2CV2995
Secondary Voltage rating: Secondary Voltage Burden:
Winding- I 110/√3V Winding- I 50VA
Winding- II 110/√3V Winding- II 50VA
Winding - III 110/√3V Winding - III 50VA
Voltage Class: Purpose of
Winding- CI 3P Winding- I PROTECTION
Winding- CI 3P Winding- II PROTECTION
Winding - CI 0.2 Winding - III METERING
Rating: 245 kV Year of Manufacture: 2018

II. CONTINUITY OF WINDING


(After removing Earth Link 1, 2 & 3)

i. Between terminals 1a - 1n Yes No




ii. Between terminals 2a - 2n Yes No

iii. Between terminals 3a - 3n Yes


 No

III. INSULATION RESISTANCE MEASUREMENT (APPLIED VOLTAGE 5 KV)


Make of testing kit --: AGAM (AT501)
Date of calibration --: 13/09/2017 to 12/09/2018
Ambient temperature --: 42 deg. C

MEASURED VALUE
UNIT
BETWEEN R Ø YØ BØ

Primary - secondary core 1 GΩ 37.1 29.9 51.5


Primary - secondary core 2 GΩ 53.7 66.0 72.9
Primary - secondary core 3 GΩ 58.6 68.4 68.8
Primary – earth GΩ 28.3 13.6 90.2

Format : 220 kV CAPACITIVE VOLTAGE TRANSFORMER


Page 1 of 3
SITE TEST REPORT SIEMENS

IV. INSULATION RESISTANCE MEASUREMENT (APPLIED VOLTAGE 500 VOLT)

Make of testing kit --: AGAM (AT501)


Date of calibration --: 13/09/2017 to 12/09/2018
Ambient temperature --: 42 deg. C

MEASURED VALUE
BETWEEN  UNIT R Ø YØ BØ
 
Secondary core 1 – earth GΩ 15.3 13 16.8
Secondary core 2 – earth GΩ 16.9 22 18.3
Secondary core 3 – earth GΩ 17.5 21.1 18.
Core 1 - core 2  GΩ 18.1 20.3 17.5
Core 1 - core 3  GΩ 17.2 19.5 16.7
Core 2 - core 3  GΩ 17.9 19.9 16.2

V. SECONDARY WINDING RESISTANCE(in Ohm)

Make of testing kit : RISH (138269)


Date of calibration : 16/09/2017 to 15/09/2018
Ambient temperature 44 ºC

Phase Core 1 Core 2 Core 3

R Ø 0.22 0.22 0.22

YØ 0.22 0.22 0.22

BØ 0.22 0.22 0.22

VI. VOLTAGE RATIO TEST

Phase Primary Secondary Voltage %


Actual Ratio
Voltage Between Value Error
5 Kv 1a – 1 n 2.49 220000/(√3)/110/(√3) 0.4
R
5 Kv 2a – 2 n 2.49 220000/(√3)/110/(√3) 0.4
5 Kv 3a – 3 n 2.48 220000/(√3)/110/(√3) 0.8
5 kV 1a – 1 n 2.49 220000/(√3)/110/(√3) 0.4
Y
5 kV 2a – 2 n 2.49 220000/(√3)/110/(√3) 0.4
5 kV 3a – 3 n 2.50 220000/(√3)/110/(√3) 0
5 kV 1a – 1 n 2.49 220000/(√3)/110/(√3) 0.4
B
5 kV 2a – 2 n 2.50 220000/(√3)/110/(√3) 0
5 kV 3a – 3 n 2.49 220000/(√3)/110/(√3) 0.4

VII. TAN DELTA AND CAPACITANCE MEASUREMENT

Format : 220 kV CAPACITIVE VOLTAGE TRANSFORMER


Page 2 of 3
SITE TEST REPORT SIEMENS
Make of testing kit : MEGGER (13850213)
Date of calibration : 07/04/2018 to 06/04/2019
Ambient temperature: 44°C
 
CAPACITANCE

PRE COMMISSIONING VALUES (in pF)


ACROSS STACK
R Ø YØ B Ø

2 kV 4383 4390 4425


10 kV 4393 4401 4438

TAN DELTA

PRE COMMISSIONING VALUES


ACROSS STACK
R Ø YØ B Ø
2 kV 0.664 0.626 0.571
10 kV 0.541 0.521 0.511

Signature: Signature: Signature: Signature:

OTEPL (Testing ) SIEMENS LTD. T & C , RRVPNL JAISALMER MPT & S , RRVPNL JAISALMER