You are on page 1of 3

1.

Capacitive voltage transformer(CVT) Date:


1.1 Equipment detail

Equipment : Capacitive Voltage Transformer


circuit position : Bhaktapur 66 kV Line
manufacturer : Mehru Electrical and Mechanical
Engineers (P) Ltd.
Serial no
R phase : OCVT-8649/1/1/18
Y phase : OCVT-8649/1/2/18
B phase : OCVT-8649/1/3/18
Highest system voltage : 72.5KV
Voltage Ratio : 66/√3/0.110/√3KV
Number of core : 2

Rated burden of each core : 100VA

1.2 General check

S.N. Test Items Inspection Results Remarks


1 Name plate OK
2 Surface Painting OK
3 Steel Structure Installation OK
4 Bushing Installation OK
5 Equipment and Structure Earthing OK
6 Weather Sealing OK
7 Oil leakage OK
8 Oil Level OK

1.3 Insulation Resistance Test

Weather Condition Clear


Ambient Temperature 25oC
Testing Equipment KYORITSU High Voltage Insulation Tester
Applied Voltage 5000V
Phase Connection IR Value Result Connection IR Value Result
(5000V) GΩ (500V) MΩ
R P– E 25 GΩ P– C1 2 GΩ
P– C2 7 GΩ
C1– C2 8 GΩ
C1– E 6 GΩ
C2– E 3 GΩ
Y P– E 26 GΩ P– C1 2 GΩ
P– C2 3 GΩ
C1– C2 5 GΩ
C1– E 3 GΩ
C2– E 3 GΩ
B P– E 20 GΩ P– C1 5 GΩ
P– C2 7 GΩ
C1– C2 4 GΩ
C1– E 6 GΩ
C2– E 3 GΩ
Note: P is Primary Terminal, C is Secondary Terminal, E is Earth Terminal
1.4 Voltage ratio test
Testing Equipment: MEGGER TTR-100 Single Phase Transformer Ratio Test Set
Phase Ratio Core
R C1 C2
66/√3/110/√3 602.12 599.80
Remarks
Phase Ratio Core
Y C1 C2
66/√3/110/√3 603.50 601.80
Remarks
Phase Ratio Core
C1 C2
B 66/√3/110/√3 599.98 601.12
Remarks

Note: C1 is for Metering & C2 is for Protection

Witnessed By
Tested By
_______________________________
______________________________
Nepal Electricity Authority