Professional Documents
Culture Documents
NO:V7859 SHEET 1 OF 1
END CUSTOMER
CONSULTANT
DRAWING SUB-
APPLICABLE No. OF CUSTOMER
WORK ORDER
Sr.
DESCRIPTION FOR PANEL SHEET DRG. No.
SERIES
DRAWING
No. 1 2 3 4 5
ITEM No.
No.
NOTE: SCH.-SCHEMATIC DRAWING; WRG.-WIRING DRAWING;Z-IF W.O. IS HAVING ONLY ONE SWITCHBOARD; FOR
MULTIPLE SWITCHBOARD ORDER USE LETTER A,B,C..; IN DRG. SUB-SERIES: 10 SERIES STANDS FOR - INCOMER TYPE, 20
SERIES FOR - OUTGOING TYPE, 30 SERIES FOR - BPT TYPE; 40 SERIES FOR - BUS-COUPLER TYPE
DRAWING SERIES: T-TECHNICAL SPECIFICATION; G-GENERAL ARRANGEMENT DRAWING (FRONT VIEW, SIDE VIEW,
PANEL LINEUP & INSTRUMENT LAYOUT) & FOUNDATION PLAN; M-SINGLE LINE DIAGRAM; S-SCHEMATIC DRAWING; B-
REV. SUMMARY OF REVISION DRN. CHK. DATE BILL OF MATERIAL; L-LEGEND; W-WIRING DRAWING; U-BUS-WIRING DIAGRAM; C-BREAKER DRAWING
TECHNICAL SPECIFICATIONS
F F
(A) SYSTEM PARAMETERS (D) CIRCUIT BREAKER
1 RATED VOLTAGE 11000V 1 APPLICABLE STANDARD IS 13118-1991 / IEC 62271-100
2 RATED FREQUENCY 50Hz 2 MECHANISM TRIP FREE
3 SYSTEM NEUTRAL UNEARTHED 3 BREAKING CAPACITY 25 kA
4 FAULT LEVEL 25kA 4 SHORT TIME RATING 25 kA FOR 3 SEC
VT7859-Z-00
NOTE - 5150/67/67N RELAY & kWh METER IS NOT IN CGL SCOPE OF SUPPLY
without prior consent of
TITLE
3 FOR 8 PANEL BOARD APPD. PSS 09.03.2017
SHEET 1 OF 2
2 TECHNICAL SPECIFICATION THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VT7859-Z-00 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
RED,YELLOW,BLUE,BLACK
1 CT CIRCUIT 4.0 SQMM.
FOR R,Y,B PH & NEUTRAL
E RED,YELLOW,BLUE,BLACK E
2 PT SECONDARY CIRCUIT 4.0 SQMM.
FOR R,Y,B PH & NEUTRAL
FILE NAME:
DRG. NO.
NOTES :
1. WIRING SHALL BE DONE AS PER IS 5578-1984
2. THE SCHEMATIC REPRESENTATION OF CKT IS DONE ON THE BASIS OF DE ENERGISED
All information contained in this document
is confidential and should not be used
TITLE
3 FOR 8 PANEL BOARD APPD. PSS 09.03.2017
SHEET 2 OF 2
2 WIRING SIZE & COLOR CODE DETAILS THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VT7859-Z-00 REV 0
0
60
280
CUTOUT IN BOTTOM FRAME 490
FOR POWER CABLE ENTRY 155
VG7859-Z-00
+2
-
BREAKER CHAMBER DOOR
PROVISION TO INSERT RACK IN
RACK OUT OPERATING HANDLE
+/-2mm +/-2mm +/-2mm +/-2mm +/-2mm +/-2mm +/-2mm +/-2mm
800 650 650 650 650 650 650 650
DESIGNATION : INCOMER OUTGOING-1 OUTGOING-2 OUTGOING-3 OUTGOING-4 OUTGOING-5 OUTGOING-6 OUTGOING-7
SWGR SR No. : 86091VG 86092VG 86093VG 86094VG 86095VG 86096VG 86097VG 86098VG
PANEL No. : 1 2 3 4 5 3 4 5
GENERAL ARRANGEMENT DRAWING ARP 09.03.2017 V7859
FOR 8 PANEL BOARD PSS 09.03.2017
1 4
FRONT VIEW
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VG7859-Z-00 0
0
INSTRUMENTAL LAYOUT
S34E212 S34E212
2/3 V 2/3 V
HDF
*67R *67Y
KW
KW HAN
S34E212 S34E212 S34E212
2/3 V 2/3 V 2/3 V
*67B *67N 86 * 5150 HDF
8W
86 ANN
VG7859-Z-00
8W
AM ANN
AM VM
* KWh * KWh
AS HAN
AS VS
LR TNC
LR TNC
FOUNDATION HOLES
VG7859-Z-00
DIM 'A'
*
FOUNDATION HOLES
VG7859-Z-00
DIM 'A'
F F
VS7859-Z-11
E E
FILE NAME:
DRG. NO.
A 5 NAME DATE
SCHEMATIC DIAGRAM FOR DRN. ARP 09.03.2017 W.O.NO. V7859
4
TITLE
3 INCOMER PANEL APPD. PSS 09.03.2017
SHEET 1 OF 7
2 TITLE PAGE THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7859-Z-11 REV 0
0
KW
V1
PC
V2
PC
V3
PC
AUX SUPPLY FOR ENERGY METER ** 11
67R
12 E75
VN
KWh 67Y
E90
1 2
FEEDER CONNECTED
WDG-1:50VA/CL0.5, WDG-2:50VA/CL: 3P ET RED YP
3 PHASE, 5 LIMB DRAWOUT TYPE 1 2
YELLOW BP
SS 1 2
1 4
SURGE SUPRESSOR BLUE
2 5
ZnO TYPE,9KV,10KA
3 6
ET
NOTE:
***
CUSTOMER HAS TO CONFIRM CABLE SIZE DURING DRG. APPROVAL
***
RCB SUITABLE FOR
2Rx1Cx600Sq.mm XLPE/PHASE
INCOMER
SCHEMATIC DIAGRAM FOR ARP 09.03.2017 V7859
INCOMER PANEL PSS 09.03.2017
2 7
POWER CIRCUIT
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VS7859-Z-11 0
0
BUSBARS PL
32
90
1 2 3
ET
I/L FOR HIGHER CT RATIO SHORT & EARTH
VCB52 C10 C30 C50 ,D10 D30 D50 , A10 A30 A50 INSTEAD
2000AMP OF C13 C33 C53, D13 D33 D53, A13 A33 A53
4 5 6 EARTHING SWITCH
REFER NOTE**
* CUSTOMER TO TAKE CARE OF INCOMING SUPPLY "OFF"
VS7859-Z-11
A33 123
DIFF. PROTECTION
Vk>=500V, AT HR
A53 124
CT1 CT2 CT3
A90
Imag<=30mA @ Vk/2
67N
C13 104 C70 9 10
BURDEN/A.CL:15VA/CL5P20
PL VCB52 PL
C33 105 229 U09 15 7a 8a 16 U10 230
CORE-2 PROTECTION
C53 106
DIRECTIONAL O/C + E/F RELAY
CT1 CT2 CT3 PL VCB52 PL
C90
C71
231 U11 17 9a 10a 18 U12 232
2S2 2S2 2S2 ET 67R
9 10
2S1 2S1 2S1
PL VCB52 PL
C11 101 C11 233 U13 19 11a 12a 20 U14 234
67Y
C31 102 C31 9 10
CT RATIO: 1200-900/1+1+1 A
241 242
D12
1S2 1S2 1S2 86 SPARE CONTACT
ET 3 D15
1S1 1S1 1S1 86
TB1 AS U23 8 9 U24
TTB
D11 110 D11 1 2 D18 243 NO-3 244
R A2
D31 111 D31 A2S1
KWh
A2S2 D34 A2S1
KW
A2S2 D38 Y A1 D71 A1S1
AM
A1S2 **
5150 RELAY & kWh METER IS NOT IN CGL SCOPE OF SUPPLY
D32
6 D35 ONLY CUTOUT & WIRING TO BE PROVIDED
D51 112 D51 D58 B DIGITAL AMMETER
P1
TTB
4 5
10A
KWh KW
A3S1 A3S2 D54 A3S1 A3S2
D52
9 D55
TTB
7 8
TTB
CONTD FROM PREV. PAGE
SCHEMATIC DIAGRAM FOR ARP 09.03.2017 V7859
INCOMER PANEL PSS 09.03.2017
3 7
POWER CIRCUIT
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VS7859-Z-11 0
0
201 202
110V DC SUPPLY
TB2
TB2
FROM REMOTE
J1
J2
2 4
MCB-DC
16A
1 3
J4
J3
94
LR REMOTE CLOSE ANTIPUMPING DEVICE A1 A2
VS7859-Z-11
3 C K27A
211 212
K25
K27
LST
FUTURE I/L 3 4
94
FC1 LR TNC 16 PL ZZ VCB52 VCB52 PL FC2
86 LSS
1 2 K11 1 A 2 B 12 13 K19 15 18 K13 28 a b 1b 2b a b 3 4 29 K12 2 1
6A K11A NC 213 214 67N 6A
22 24 CLOSE CIRCUIT
+ -
67B
22 24
+ -
67Y
22 24
+ -
67R
22 24
J4
AUTO TRIP
NO-2
J3
PL LSS PL SP AMBER
2 1 2 3 L15 1 2
SERVICE POSITION INDICATION
LST PL AMBER TP
1 2 4 L17 1 2 TEST POSITION INDICATION
CLEAR
SCHEMATIC DIAGRAM FOR ARP 09.03.2017 V7859
INCOMER PANEL PSS 09.03.2017
4 7
DC CIRCUIT
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VS7859-Z-11 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
203
TB2 204
H2
2 4
VS7859-Z-11
MCB-AC
16A
1 3
E E
H3
FILE NAME:
H4
DRG. NO.
KW
12 13
AUX SUPPLY FOR WATTMETER
+ -
2A
PSW 80W,230V AC LMP
1 2 H25 130 H25 1 2
SKT
230V AC,40 W
FS SSW LKS
1 2 H31 1 2 H33 P N H32 2 1
C C
10A
90A E
ET
B B
CG Power and Industrial Solutions Limited
H3
H4
All information contained in this document
is confidential and should not be used
without prior consent of
A 5 NAME DATE
SCHEMATIC DIAGRAM FOR DRN. ARP 09.03.2017 W.O.NO. V7859
4
TITLE
3 INCOMER PANEL APPD. PSS 09.03.2017
SHEET 5 OF 7
2 AC CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7859-Z-11 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
VS7859-Z-11
J3
110V DC SUPPLY
J4
E E
FROM PAGE NO. 4
FILE NAME:
DRG. NO.
J4
J3
A1 A2 110VDC,150WATT
ZZ PL B
J4
J3
21 L13 1 2
BLUE
SPRING CHARGE INDICATION
C C
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
A 5 NAME DATE
SCHEMATIC DIAGRAM FOR DRN. ARP 09.03.2017 W.O.NO. V7859
4
TITLE
3 INCOMER PANEL APPD. PSS 09.03.2017
SHEET 6 OF 7
2 MOTOR CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7859-Z-11 REV 0
0
J4
J3
8-WINDOW ANNUNCIATOR
ANN
VS7859-Z-11
1
1
FAN2
EARTH FAULT TRIP
FAN1 2A
POWER MODULE
ACKNOWLEDGE
2A 2
2
COMMON1
COMMON2
DC FAIL
AC FAIL
SPARE
SPARE
RESET
MUTE
TEST
PS NS F1 RST F8 C2 F2 F3 F4 F5 F6 F7 F7 F8 I1 N I2 C1 COM2 TST MUT ACK COM1 P
L78
L74
L75
L73
L71
H81
3 3
1
67B
67R
219 220
2
HDF 4 4
217 218
3 3
67Y
67N
H3
H4
L63
230VAC 4 4
SUPPLY FROM
PAGE NO.5
1
HAN
2
L61
L62
NOTE:
WINDOW DESCRIPTION MAY CHANGE DURING AS PER ANNUNCIATOR MODEL
SCHEMATIC DIAGRAM FOR ARP 09.03.2017
V7859
INCOMER PANEL PSS 09.03.2017
7 7
ANNUNCIATOR CIRCUIT
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VS7859-Z-11 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
VS7859-Z-21
E E
FILE NAME:
DRG. NO.
C C
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
A 5 NAME DATE
SCHEMATIC DIAGRAM FOR DRN. ARP 09.03.2017 W.O.NO. V7859
4
TITLE
3 OUTGOING PANEL APPD. PSS 09.03.2017
SHEET 1 OF 7
2 TITLE PAGE THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7859-Z-21 REV 0
1 2 3 4 5 6 7 8 9 10
0
F F
VS7859-Z-21
E E
**
FILE NAME:
DRG. NO.
KWh
AUX SUPPLY FOR ENERGY METER V1
PC
KWh
12 13
+ - V2
PC
V3
110V AC SUPPLY
FY
206 E30 1 2 E31 Y1 Y2 E33 V2
PC
FB
207 E50 1 2 E51 B1 B2 E53 V3
PC
208 E70 N1 N2 E73 VN
C C
1 2 3
VCB52
I/L
B 1250A B
CG Power and Industrial Solutions Limited
4 5 6 EARTHING SWITCH
All information contained in this document
**
is confidential and should not be used
TITLE
3 OUTGOING PANEL APPD. PSS 09.03.2017
SHEET 2 OF 7
2 POWER CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7859-Z-21 REV 0
0
PL
32
90
OUTGOING RCB SUITABLE FOR
2x3Cx300 Sq.mm XLPE
*** NOTE:
*** ET
CUSTOMER HAS TO CONFIRM CABLE SIZE DURING DRG. APPROVAL
P2
VS7859-Z-21
**
C50 109
C30 108
TB1
C10 107
TB1 5150
C13 104 C70 12 11A VCB OP SPARE CONTACTS
BURDEN/A.CL:15VA/CL5P20
51 50
C33 105
CORE-2 PROTECTION
C53 106
NON-DIRECTIONAL O/C + E/F RELAY PL VCB52 PL
CT1 CT2 CT3 225 U01 5 5b 6b 6 U02 226
C90
5150
9A 10
51 50
CT STR: 25kA/1 SEC
CT1
1S3
CT2
1S3
CT3
1S3
D53 115
** A1S1
KWh
A1S2 D14 A1S1
KW
A1S2 PL VCB52 PL
D90
CORE-1 METERING
R A2
KWh KW AM
D31 111 D31 A2S1 A2S2 D34 A2S1 A2S2 D38 A1 D71 A1S1 A1S2 98X
Y
D32
U15 13 14 U16
6 D35 DIGITAL AMMETER
D51 112 D51 D58 B 239 98X 240
TTB U17 43 44 U18
4 5
10A 241 98X 242
KWh KW U19 21 22 U20
A3S1 A3S2 D54 A3S1 A3S2
D52 243 98X 244
9 D55 U21 31 32 U22
245 246
TTB
7 8 86 SPARE CONTACT
86
TTB
U23 8 9 U24
247 NO-3 248
FOR HIGHER CT RATIO SHORT & EARTH **5150 RELAY & kWh METER IS NOT IN CGL SCOPE OF SUPPLY
C10 C30 C50 ,D10 D30 D50 INSTEAD
ONLY CUTOUT & WIRING TO BE PROVIDED
OF C13 C33 C53, D13 D33 D53,
CONTD FROM PREV. PAGE
SCHEMATIC DIAGRAM FOR ARP 09.03.2017 V7859
OUTGOING PANEL PSS 09.03.2017
3 7
POWER CIRCUIT
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VS7859-Z-21 0
0
201 202
110V DC SUPPLY FROM REMOTE
TB2
TB2
J1
J2
1 3
MCB-DC ANTIPUMPING UNIT
16A LR REMOTE CLOSE 94
2 4 3 C K27A
A1 A2
J3
J4 209 210
K27
LST
3 4
K25
FUTURE I/L 94
VS7859-Z-21
86-2
FC1 LR TNC 86 16 PL ZZ VCB52 VCB52 PL FC2
LSS
1 2 K11 1 A 2 B 3 4 K19 15 18 K13 28 a b 1b 2b a b 3 4 29 K12 2 1
6A K11A 211 212 6A
CLOSE CIRCUIT
5150
22 24
+ -
T TRIP CKT HEALTHY CHECK
W PL
1 2 K7 1 2 K5 22
J4
AUTO TRIP
AMBER
PL LSS PL SP
2 1 2 3 L15 1 2
SERVICE POSITION INDICATION
J3
LST PL AMBER TP
1 2 4 L17 1 2 TEST POSITION INDICATION
CLEAR
SCHEMATIC DIAGRAM FOR ARP 09.03.2017 V7859
OUTGOING PANEL PSS 09.03.2017
4 7
DC CIRCUIT
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VS7859-Z-21 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
230VAC SUPPLY FROM REMOTE
203
TB2 204
TB2
H1
H2
1 3
VS7859-Z-21
MCB-AC
16A
E 2 4 E
H3
FILE NAME:
H4
DRG. NO.
H4
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
A 5 NAME DATE
SCHEMATIC DIAGRAM FOR DRN. ARP 09.03.2017 W.O.NO. V7859
4
TITLE
3 OUTGOING PANEL APPD. PSS 09.03.2017
SHEET 5 OF 7
2 AC CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7859-Z-21 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
VS7859-Z-21
E E
J3
110V DC SUPPLY
J4 FROM PAGE NO. 3
FILE NAME:
DRG. NO.
4A T1 4A
A1 A2 110VDC,150WATT
ZZ PL B
J3
J4
21 L13 1 2
BLUE
SPRING CHARGE INDICATION
C C
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
A 5 NAME DATE
SCHEMATIC DIAGRAM FOR DRN. ARP 09.03.2017 W.O.NO. V7859
4
TITLE
3 OUTGOING PANEL APPD. PSS 09.03.2017
SHEET 6 OF 7
2 MOTOR CIRCUIT THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VS7859-Z-21 REV 0
0
J3
J4
8-WINDOW ANNUNCIATOR
ANN
VS7859-Z-21
1
1
FAN2
FAN1 2A
POWER MODULE
ACKNOWLEDGE
2A 2
2
COMMON1
COMMON2
DC FAIL
DC FAIL
AC FAIL
SPARE
SPARE
SPARE
SPARE
SPARE
RESET
MUTE
TEST
F7 NS C3 I3 P COM1 F1 F2 F3 F4 F5 F6 F7 F8 C1 I1 C2 I2 TST MUT ACK RST COM2 N
L78
L76
L74
L75
L73
L71
H81
5150
218 219 215 216 217
2
L63
H3
H4
230VAC
SUPPLY FROM
1
HAN
2
L61
L62
NOTE:
WINDOW DESCRIPTION MAY CHANGE DURING AS PER ANNUNCIATOR MODEL
SCHEMATIC DIAGRAM FOR ARP 09.03.2017 V7859
OUTGOING PANEL PSS 09.03.2017
7 7
ANNUNCIATOR CIRCUIT
CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD
NTS VS7859-Z-21 0
B'SHEET FOR W. O. : V7859 REV.0
B'SHEET NO. VB7859-Z-00
CUSTOMER : HIGHTENSION SWGR. PVT LTD
PREPARED BY : ARP
APPROVED BY : PSS
DATE : 09.03.2017
IT DESCRIPTION IC X 1 OG X 7 TOTAL
IND. LAMPS LED TYPE MAKE:AS PER CGL STANDARD
COLOUR VOLTAGE PURPOSE
A1 R RED 110 VDC VCB ON 1 1 8
A2 G GREEN 110 VDC VCB OFF 1 1 8
A3 B BLUE 110VDC SPR. CHR. INDICATION 1 1 8
A4 A AMBER 110 VDC AUTOTRIP 1 1 8
A5 W WHITE 110 VDC TRIP CKT HEALTHY 1 1 8
A6 RP RED 110 VAC R PHASE HEALTHY 1 0 1
A7 YP YELLOW 110 VAC Y PHASE HEALTHY 1 0 1
A8 BP BLUE 110 VAC B PHASE HEALTHY 1 0 1
A9 SP AMBER 110V DC SERVICE POSITION IND 1 1 8
A10 TP CLEAR 110V DC TEST POSITION IND 1 1 8
A20 T1 TIMER 1 1 8
PURPOSE: FOR SPRING CHARGING MOTOR CKT
CONTROL VOLTAGE: 110 VDC
IT DESCRIPTION IC X 1 OG X 7 TOTAL
A22 ES INTEGRAL EARTH SWITCH 650 W 0 1 7
INTEGRAL EARTH SWITCH 800 W 1 0 1
A25 TH THERMOSTAT 1 1 8
RANGE- 30 - 75 DEG CELSIUS
CT & PT
CT1 11 KV EPOXY CASTED CURRENT TRANSFORMER 3 0 3
CTR - 1200-900 /1+1+1A
STR - 25 KA/1SEC
BURDEN/ACC CLASS- 15VA/CL 0.5 + 15VA/5P20 + 15VA/PS
PS CLASS DETAILS: Vk=500VAC @ HR, 30mA @ Vk/2 CUSTOMER TO CONFIRM THE PS CLASS DETAILS DURING
CT SEC - ON P1 SIDE DRAWING APPROVAL
MAKE- CGL/SILKANS/SGELECTRICALS/EQUIVALENT
VT VT VOLTAGE TRANSFORMER 1 0 1
11KV/110V/110V 3PH 5L DRAWOUT TYPE
FEEDER CONNECTED TOP MOUNTED
VT SEC - 110 V AC STAR/STAR/OPEN DELTA
BURDEN& ACC.CLASS- 50VA/50VA CL0.5/3P
VOLTAGE FACTOR - 1.2 CONT/1.5 FOR 8 HRS
PDF created with pdfFactory Pro trial version www.pdffactory.com
B'SHEET FOR W. O. : V7859 REV.0
B'SHEET NO. VB7859-Z-00
CUSTOMER : HIGHTENSION SWGR. PVT LTD
PREPARED BY : ARP
APPROVED BY : PSS
DATE : 09.03.2017
IT DESCRIPTION IC X 1 OG X 7 TOTAL
BIL - 28KV/75 KVp
MAKE-CGL/EQUIVALENT
RELAYS
R1 67R DIRECTIONAL OVERCURRENT EARTH FAULT RELAY 4 0 4
67Y TYPE MIT 131/121
67B MAKE EASUN REYROLLE
67N CT SEC 1A/5A RELAY IS NOT IN CGL SCOPE OF SUPPLY
CASE SIZE 2/3V
AUX. SUPPLY 110 VDC
IT DESCRIPTION IC X 1 OG X 7 TOTAL
STAND BY SUPPLY -230 VAC
WINDOW DESCRIPTION :-
WINDOW 1: SPARE WINDOW DESCRIPTION MAY CHANGE
WINDOW 2: SPARE AS PER ANNUNCIATOR MODEL
WINDOW 3: OVER CURRENT & EARTH FAULT TRIP
WINDOW 4: SPARE
WINDOW 5: SPARE
WINDOW 6: SPARE
WINDOW 7: DC FAIL
WINDOW 8: AC FAIL
METERS
M1 AM DIGITAL AMMETER
MAKE OF THE METER - AE/RISHABH
FLUSH MTG., CASE SIZE : 96 SQMM
CT SEC: 1A,
CTR - 1200-900/1A 1 0 1
CTR - 400-200/1A 0 1 7
AUX VOLTAGE - 80-300 VAC
ACC. CLASS:0.5
M2 VM DIGITAL VOLTMETER 1 0 1
MAKE OF THE METER - AE/RISHABH
VT RATIO: 11KV/110V
VT SEC: 110V AC
AUX.SUPPL : 80-300VAC
CASE SIZE: 96 SQMM, MTG : FLUSH
ACC CLASS : 0.5
M4 KW DIG. KW METER 1 1 8
MAKE OF THE METER - AE/RISHABH
CT SEC - 1A/5A SELECTABLE
PT SEC - 110VAC / ROOT 3(PER PHASE)
SUIATBLE TO READ - W
ACCURACY- CLASS 0.5
OVERALL SIZE :96X96m (FLUSH MTG)
CONNECTIONS- 3PHASE 4 WIRE 3 ELEMENT TYPE
AUX.VOLTAGE : 80-270 VAC
A4 DIGITAL AMMETER 6 6
MAKE OF THE METER - AE/RISHABH
FLUSH MTG., CASE SIZE : 96 SQMM
CT SEC: 1A,
CTR - 400-200/1A
AUX VOLTAGE - 80-300 VAC
ACC. CLASS:0.5
A5 DIGITAL VOLTMETER 6 6
MAKE OF THE METER - AE/RISHABH
VT RATIO: 11KV/110V
VT SEC: 110V AC
AUX.SUPPL : 80-300VAC
CASE SIZE: 96 SQMM, MTG : FLUSH
ACC CLASS : 0.5
A6 DIG. KW METER 3 3
MAKE OF THE METER - AE/RISHABH
CT SEC - 1A/5A SELECTABLE
PT SEC - 110VAC / ROOT 3(PER PHASE)
SUIATBLE TO READ - W
ACCURACY- CLASS 0.5
OVERALL SIZE :96X96m (FLUSH MTG)
CONNECTIONS- 3PHASE 4 WIRE 3 ELEMENT TYPE
AUX.VOLTAGE : 80-270 VAC
21 DISTANCE PROTECTION RELAY NORMALLY CLOSED PUSH BUTTON FI1,FI2 INDICATION CIRCUIT FUSES
F F
25 CHECK SYNCHRONIZING RELAY M MOTOR T TRIP CKT HEALTHY TEST PUSH BUTTON MTTB METERING TEST TERMINAL BLOCK FAN1,FAN2 ANNUNCIATION CIRCUIT FUSES
27 UNDER VOLTAGE RELAY CURRENT TRANSFORMER DA DC FAIL ACCEPT PUSH BUTTON RTTB RELAY TEST TERMINAL BLOCK FCA1,FCA2 COMMON ALARM CIRCUIT FUSES
32 DIRECTIONAL POWER RELAY VOLTAGE TRANSFORMER AA AC FAIL ACCEPT PUSH BUTTON FSY1,FSY2 SYNCHRONIZING CIRCUIT FUSES
37 UNDER CURRENT/POWER RELAY THERMOSTAT EPB EMERGENCY PUSH BUTTON ADF AC DC FAIL RELAY (WITH ALARM LOGIC) FAX1,FAX2 AUXILLARY RELAY CKT FUSES
46 NEGATIVE SEQUENCE VOLTAGE RELAY BUZZER/HOOTER PA/PR ACCEPT/RESET PUSH BUTTON DCF DC FAIL RELAY (WITH ALARM LOGIC) FM/LKM FUSE/LINK FOR MOTOR CIRCUIT
47 NEGATIVE SEQUENCE CURRENT RELAY LAMP PM/PT MUTE/TEST PUSH BUTTON CAR COMMON ALARM SCHEME FH/LKH FUSE/LINK FOR HEATER CIRCUIT
VL7859-Z-00
49 THERMAL RELAY SWITCH(TNC,LR,AUTO MANUAL) VSS VOLTAGE SELECTION SCHEME FS/LKS FUSE/LINK FOR SOCKET CIRCUIT
50 HIGHSET OVER CURRENT RELAY TOGGLE SWITCH Z OPENS WHEN SPRINGS ARE CHARGED FV1-4 FUSES FOR VOLT SEL SCHEME
50N HIGHSET EARTH FAULT RELAY COIL ZZ CLOSES WHEN SPRINGS ARE CHARGED SS SURGE SUPPRESSOR MCB MINIATURE CIRCUIT BREAKER
E E
51 IDMTL OVER CURRENT RELAY CC CURRENT COIL OF METER LS CLOSES WHEN VCB IS MECH.FREE TO CLOSE LA LIGHTNING ARRESTOR
51N IDMTL EARTH FAULT RELAY PC PRESSURE COIL OF METER TNC BREAKER CONTROL SWITCH LLI LINE LINE INDICATOR TS CONTACTOR SENSING TEST POSITION
FILE NAME:
DRG. NO.
51S SENSITIVE EARTH FAULT RELAY (52a)VCB OPERATED NO CONTACT LR LOCAL REMOTE SWITCH ANN ANNUNCIATOR CS CONTACTOR SENSING SERVICE POSITION
51G STAND-BY EARTH FAULT RELAY (52b)VCB OPERATED NC CONTACT SS SYNCHRONIZING SELECT SWITCH HCA HOOTER FOR COMMON ALARM CLS CONTACTOR SENSING SERVICE /TEST POSITION
59 OVER VOLTAGE RELAY 3PIN SOCKET AS/VS AMMETER/VOLTMETER SELECTOR SWITCH HAN HOOTER FOR ANNUNCIATOR 98X AUX CONTACTOR FOR VCBCONTACT MULT.
59N VOLTAGE BALANCE RELAY (NDR) TSS TRIP SEL SWITCH(USED IN SYNCHRO.CKT) HAF HOOTER FOR AC FAIL ALARM 98U AUX CONTACTOR FOR 27 RELAY CONT MULT
61 CURRENT BALANCE RELAY (NDR) TAG TAG DESCRIPTION BSS CB SEL SWITCH(USED IN SYNCHRO. CKT) HDF HOOTER FOR DC FAIL ALARM 98M AUX CONTACTOR FOR 86 RELAY CONT MULT
80 DC SUPPLY SUPERVISION RELAY PL PLUG & SOCKET SSW TOGGLE SWITCH FOR SOCKET T1,T2... TIMER
81U UNDER FREQUENCY RELAY RCB REAR CABLE BOX DS DOOR SWITCH R1,R2... RESISTOR CTX CURRENT TRANSDUCER
81O OVER FREQUENCY RELAY SCB SIDE CABLE BOX AMS AUTO MANUAL SELECTOR SWITCH VTX VOLTAGE TRANSDUCER
85 PILOT WIRE RECEIVER RELAY FR,FY,FB PT SECONDARY(Y SIDE) FUSES KWX KW TRANSDUCER
86 MASTER TRIP(LOCK OUT) RELAY CT CURRENT TRANSFORMER AM ANALOG/DIGITAL AMMETER F1,F2 PT SECONDARY(V SIDE) FUSES KVARX KVAR TRANSDUCER
94 ANTI PUMPING RELAY VT VOLTAGE TRANSFORMER VM ANALOG/DIGITAL VOLTMETER FC1,FC2 CLOSING CIRCUIT FUSES TEMX TEMPERATURE TRANSDUCER
C C
95 TRIP CKT. SUPERVISION RELAY CBCT CORE BALANCED CURRENT.TRANSFORMER HZ FREQUENCY METER FT1,FT2 TRIPPING CIRCUIT FUSES
98 CONTACTOR ICT INTERPOSING CURRENT TRANSFORMER KW WATT METER
NOTES
KVAR REACTIVE VOLT AMP METER
R BREAKER ON INDICATION(RED) KVA VOLT AMP METER
1. THESE ARE THE FREQUENTLY USED ABBREVIATIONS AS PER CGL STANDARD DRAWINGS
TERMINAL BLOCK FOR CT WIRE
G
2. REFERENCES IEV-440 , IS-5578, IEC-60050
TERMINAL BLOCK FOR WITHIN PANEL WIRE BREAKER OFF INDICATION(GREEN) PF POWER FACTOR METER
TERMINAL BLOCK FOR WITHIN BOARD WIRE A AUTO TRIP INDICATION(AMBER) KWH WATTHOUR METER
TERMINAL BLOCK FOR REMOTE FEEDBACK W TRIP CKT HEALTHY INDICATION(WHITE) TVM TRIVECTOR METER
HRC FUSE B SPRING CHARGED INDICATION (BLUE) MDC MAXIMUM DEMAND CONTROLLER
LINK SP SERVICE POSITION INDICATION (AMBER) LM LOAD MANAGER
B B
CG Power and Industrial Solutions Limited
PLUG AND SOCKET TP TEST POSITION INDICATION (CLEAR) MFM MULTIFUNCTION METER
NORMALLY OPEN CONTACT DF DC FAIL INDICATION(CLEAR) RH RUN HOUR METER
AF AC FAIL INDICATION(CLEAR)
All information contained in this document
TITLE
3 APPD. PSS 09.03.2017
SHEET 1 OF 1
2
THIRD ANGLE PROJECTION
1 CUSTOMER: HIGH TENSION SWITCHGEARS PVT LTD ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. VL7859-Z-00 REV 0