MEHI QA 874

07.12.2022

To,
Chandra Nirman Pvt.Ltd.
507-509, Avinash Empressa,
Kota, Raipur – 497001 (C.G.)
Cell : +91 9752523000
Email : cnpl.rgh@hotmail.com

KIND ATTN : MR.SAURABH AGRAWAL.


SUB : QUOTATION FOR TRANSFORMER.
YOUR REF : VERBAL.

Dear Sir,
With reference to the above, we are pleased to submit our most competitive offer for the supply
of Transformer as under :
DESCRIPTION OF TRANSFORMER PRICE/EACH (Rs.) QTY.
630 KVA, 33 / 0.433 KV TRANSFORMER
(WITH OFF CIRCUIT TAP CHANGER) (ISI MARKED) 20,16,000/- 02
(AS PER IS:1180, ENERGY EFFICIENCY LEVEL 1)
500 KVA, 33 / 0.433 KV TRANSFORMER
(WITH OFF CIRCUIT TAP CHANGER) (ISI MARKED) 16,69,000/- 02
(AS PER IS:1180, ENERGY EFFICIENCY LEVEL 1)
The Price quoted above is Ex-Works, INDORE (M.P.) / VADODARA (GUJARAT) with First Filling of Oil with
Standard Fittings as per ISS / IEC.
GST : Extra @ 18.00%.

TCS : Extra as applicable at the time of dispatch.

PAYMENT : 50% advance alongwith order and balance against Proforma Invoice prior to despatch.

DELIVERY : 08 to 10 weeks from the date of receipt of Techno-commercially clear order, subject to usual
force majeure clause, which includes non availability of raw materials or any other cause
beyond our control.

GUARANTEE : The Transformer shall be guaranteed against defective material and faulty workmanship for a
period of EIGHTEEN MONTHS from the date of despatch.

VALIDITY : 15 days from the date of our offer.

We hope you will find our offer in line with your requirement and look forward to receive your valued order.

With Best Regards,

R.V.Singh
Cell # +91 9300290586
Encl : Technical Specifications.
(PART A)

GENERAL TECHNICAL SPECIFICATIONS

1. DESIGN :
Oil Immersed, Core Type Double Wound Transformer with Class “A” Insulation, Designed for continuous duty
at rated capacity with particular reference to tropical conditions confirming to ISS 2026 / IEC 60076.

2. STANDARDS :
IS 1180 : Outdoor type Oil Immersed Distribution Transformers upto and including 2500 KVA, 33 KV.
IS 2026 / IEC 60076 : Power Transformers.
IS 3639 / IEC : Specification for Fittings & Accessories for Power Transformers.
IS 335 / IEC 60296 : Transformer Oil.
IS 1271/ IEC 60085 : Insulating Material.
IS 3347 / IEC 60137 : Bushings.

3. CONSTRUCTIONS :

a) CORE : The core shall be C.R.G.O. Annealed Steel Material having Low Losses and good grain properties,
bolted together to the frame firmly to prevent vibration and noise.

b) WINDING : Winding shall be made out of paper covered Electrolytic Grade Copper Wires / Strips. Generally
H.V.Winding shall be crossover or disc type with paper covered Conductor and the L.V.Winding shall be
Cylindrical Type / Disc Type or Helical Type depending up on the Voltage and currents.

c) TANK : Transformer Tank shall be of Robust Construction and shall be fabricated with M.S.Plates. Proper
reinforcement shall be provided to insure no bulging occur during service. The Tank shall be pressure and
Vaccume Tested to the C.B.I.P.Standads. All joints of tank & fittings shall be leak proof.

d) FITTINGS & ACCESSORIES : All the fittings and accessories shall be of good quality and conforming to
relevant IS Specifications.

e) OIL : The Transformer shall be supplied with first filling of oil.

f) PAINTING : Tank inside shall be painted by heat and oil resistant paint. The exterior of the Transformer
shall be painted with Epoxy Paint as per SHADE NO. RAL 7038.

4. DRAWINGS :
Three copies of G.A.Drawings showing weights, dimensions and position of fitting and accessories shall be
submitted within 15 days from the date of order.

5. TESTING :
All Routine Tests as per ISS / IEC will be carried out prior to despatch at our works and Test Certificate in
Triplicate will be issued.
(PART B)

TECHNICAL PARTICULARS AS PER IS : 1180 (PART-1) : 2014

1. Make MEHI POWER


2. Continuous Rating 630 KVA.
3. Voltage Ratio
Primary 33 KV.
Secondary 433 VOLTS.
4. System 3 Phase, 50 Hz.
5. Winding Materials Copper.
6. Connection on Primary / Secondary Delta / Star.
7. Vector Group Dyn11.
8. Installation Outdoor.
9. Type of Cooling ONAN.
10. Temperature Rise over Ambient Temp.
In Oil by thermometer 40°C.
In Winding by resistance 45°C.
11. Type of Tap Changer Off Load Switch.
12. Controls of Tap Changer Externally Mannual.
13. Taps / Steps on H.V.Winding (+) 5% to (-) 10% in Steps of 2.5%.
14. Terminal Arrangements
a). Primary Bare Bushings / Cable Box.
b). Secondary Cable Box.
15. Maximum Losses at 50% Loading (Energy Efficiency Level 1) 1999.5 W.
16. Maximum Losses at 100% Loading (Energy Efficiency Level 1) 5697.5 W.
17. Impedance Voltage % (Subject to IS / IEC Tolerance) 4.50%
(PART B)

TECHNICAL PARTICULARS AS PER IS : 1180 (PART-1) : 2014

1. Make MEHI POWER


2. Continuous Rating 500 KVA.
3. Voltage Ratio
Primary 33 KV.
Secondary 433 VOLTS.
4. System 3 Phase, 50 Hz.
5. Winding Materials Copper.
6. Connection on Primary / Secondary Delta / Star.
7. Vector Group Dyn11.
8. Installation Outdoor.
9. Type of Cooling ONAN.
10. Temperature Rise over Ambient Temp.
In Oil by thermometer 40°C.
In Winding by resistance 45°C.
11. Type of Tap Changer Off Load Switch.
12. Controls of Tap Changer Externally Mannual.
13. Taps / Steps on H.V.Winding (+) 5% to (-) 10% in Steps of 2.5%.
14. Terminal Arrangements
a). Primary Bare Bushings / Cable Box.
b). Secondary Cable Box.
15. Maximum Losses at 50% Loading (Energy Efficiency Level 1) 1623.25 W.
16. Maximum Losses at 100% Loading (Energy Efficiency Level 1) 4622.5 W.
17. Impedance Voltage % (Subject to IS / IEC Tolerance) 4.50%
(PART C) Code – DTCU2

STANDARD FITTINGS & ACCESSORIES

PARTICULARS QTY.
1. Rating & Diagram Plate. 1 No.
2. Earthing Terminals. 2 Nos.
3. Lifting Lugs for Transformer. 2 Nos.
4. Lifting Lugs for Top Cover. 2 Nos.
5. Bottom Drain cum Filter Valve with Plug. 1 No.
6. Top Filter Valve with Plug. 1 No.
7. Conservator Tank. 1 No.
8. Prismatic Oil Level Guage. 1 No.
9. Oil Filling hole with Plug. 1 No.
10. Air Release Plug. 1 No.
11. Thermometer Pocket. 1 No.
12. Silicagel Breather. 1 No.
13. Explosion Vent (Pressure Relief Valve). 1 No.
14. Off.Ckt. Tap Changer Switch with Handle & Position Indicator. 1 No.
15. L.V. Terminal Box with Extended Copper Flats/suitable Bus Palm. 1 No.
16. Neutral brought out terminal. 1 No.
17. Detachable Radiators with Shutoff Valves. 1 Set.
18. Bi-Directional Rollers. 4 Nos.
19. Oil Temperature Indicator (6” Dial Type) with Alarm & Trip Contacts. 1 No.
20. Double Float Buchholz Relay with Alarm & Trip Contacts. 1 No.
21. Marshalling Box with complete wiring. 1 No.
22. Winding Temperature Indicator (6” Dial Type) with Alarm & Trip contacts. 1 No.

REMARKS / NOTES :
(PART D)

LIST OF ROUTINE TEST TO BE CARRIED OUT (AS PER IS : 2026)

SR.NO. DETAILS OF TEST

01. Measurement of Winding Resistance.

02. Measurement of Voltage Ratio & Check of Phase Displacement.

03. Insulation Resistance of HV & LV Winding (With 2.5 KV Analog Meter).

04. Measurement of Short Circuit Impedance & Load Loss.

05. Measurement of No-Load Loss & No Load Current .

06. Induced Over Voltage Test (DVDF Test).

07. Separate Source Power Frequency Test On HV & LV Winding.

08. Dielectric Value (BDV) of Oil Test.


(PART E)

DETAILS OF CONTACTS IN FITTINGS AND ACCESSORIES OF TRANSFORMER.

ALARM CONTACT TRIP CONTACT

SR Type Type
DISCRIPTION Quantity Quantity
NO.
1 2 1 2

1. Buchholz Relay 1 NO - 1 NO -

2. Oil Temperature Indicator 1 NO - 1 NO -

Winding Temperature
3. 1 NO - 1 NO -
Indicator