You are on page 1of 7

- Test report -

- 220Kv Transmission Line Mardan Tarbela 1-

Customer
Name: Location:
Test job
Description:
Executed on: 11/18/2018 12:41:12 PM by: Administrator
Plant
Name:
Voltage level:
Bay:
Device under test
Designation: Distance RElay Order number: 421
Manufacturer: KoCoS Messtechnik AG Description:
Type series/Model:
Serial number:
Specification:
Test system
Name: ARTES 560 (ARTES 560) Serial number: 32901000255
Last adjustment: 10/26/2017 4:18:17 PM

created on: 11/18/2018 12:42:43 PM


ITTEHAD ELECTRIC CO. created by: Administrator
Signature:
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

Installation Location
Plant: Voltage level:
Bay:
Test object data
Designation: Distance RElay Serial number:
Manufacturer: KoCoS Messtechnik AG Build date: 14.11.2017
Type series/Model: HW-Version:
Specification: FW-Version:
Rated values: 5.000 A 63.509 V 50.000 Hz

IO-Interfaces
Analog inputs
Connection Signal Settings Ratio
Line voltage L1-N 63.509 (130.000) V 220.00/√3
kV/110.00/√3 V
Line voltage L2-N 63.509 (130.000) V 220.00/√3
kV/110.00/√3 V
Line voltage L3-N 63.509 (130.000) V 220.00/√3
kV/110.00/√3 V
Line current L1 4.000 In 1200.00 A/5.00 A
Line current L2 4.000 In 1200.00 A/5.00 A
Line current L3 4.000 In 1200.00 A/5.00 A
Binary outputs
Connection Signal Settings
Distance general trip command Normally open contact (NO)
Relay trip command Normally open contact (NO)
Voltage transformer - Energy system
Vendor/Type: Ratio: 220.00/√3 kV /
110.00/√3 V
Serial number: Power/Precision class: 0.000 VA /
Build date:
Current transformer - Energy system
Vendor/Type: Ratio: 1200.00 A / 5.00 A
Serial number: Power/Precision class: 0.000 VA / 0
Build date:

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 2/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

Scheme Settings
Instrument transformer Line current
Vendor/Type:
Serial number:
Build date:
Ratio: 1200.00 A / 5.00 A
Power/Precision class: 0.000 VA / 0
Instrument transformer Line voltage
Vendor/Type:
Serial number:
Build date:
Ratio: 220.00/√3 kV / 110.00/√3 V
Power/Precision class: 0.000 VA /

Line parameters
Line impedance Re/R1L;Xe/X1L
Z1L: 2.680 Ω 78.00 ° Fr=Re/R1L: 1.350
Z0L: 8.60 Ω 70.90 ° Fx=Xe/X1L: 0.700
Z01: 8.60 Ω 70.90 ° Fr1=Re1/R11: 1.350
Earth coefficient Fx1=Xe1/X11: 0.700
k0L: 0.740 -10.29 °
k01: 0.740 -10.29 °
Source parameters
Source impedance Earth coefficient
Z1s: 5.800 Ω 75.00 ° k0s: 1.000 0.00 °
Z0s: 23.200 Ω 75.00 °
Ze: 5.80 Ω 75.00 °

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 3/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

Settings IMP monitor


Non directional tripping time: 1s
Directional tripping time: 5s
Impedance correction: 1
Directional line: 172 °
-8 °
Shortest tripping time: 0.02 s

Distance protection test series


Duration: 10:32.582
Comments before testing:

Comments after testing:

IMP monitor test points

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 4/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

State Fault Zone Z |Z| Angle Tripping time


Loop (relative) Reference Actual Deviation
L1-E Z1 0.693 Z 1 1.616 Ω 78.00 ° 0.020 s 0.019 s -5.00 %
L1-E Z1 0.953 Z 1 2.221 Ω 78.00 ° 0.020 s 0.033 s 63.12 %
L1-E Z2 1.064 Z 1 2.481 Ω 78.00 ° 0.360 s 0.382 s 6.15 %
L1-E Z2 1.176 Z 1 2.740 Ω 78.00 ° 0.360 s 0.382 s 6.18 %
L1-E Z2 0.607 Z 3 3.260 Ω 78.00 ° 0.360 s 0.383 s 6.39 %
L1-E Z3 0.672 Z 3 3.606 Ω 78.00 ° 0.710 s 0.734 s 3.36 %
L1-E Z3 4.471 Ω 4.471 Ω 78.00 ° 0.710 s 0.732 s 3.08 %
L1-E Z3 5.249 Ω 5.249 Ω 78.00 ° 0.710 s n.t. 0.00 %
L1-E FIN 5.682 Ω 5.682 Ω 78.00 ° 1.000 s n.t. 0.00 %
L2-E Z1 0.693 Z 1 1.616 Ω 78.00 ° 0.020 s 0.019 s -6.25 %
L2-E Z1 0.953 Z 1 2.221 Ω 78.00 ° 0.020 s 0.034 s 67.50 %
L2-E Z2 1.064 Z 1 2.481 Ω 78.00 ° 0.360 s 0.388 s 7.74 %
L2-E Z2 1.176 Z 1 2.740 Ω 78.00 ° 0.360 s 0.382 s 6.15 %
L2-E Z2 0.607 Z 3 3.260 Ω 78.00 ° 0.360 s 0.382 s 6.11 %
L2-E Z3 0.672 Z 3 3.606 Ω 78.00 ° 0.710 s 0.732 s 3.15 %
L2-E Z3 4.471 Ω 4.471 Ω 78.00 ° 0.710 s 0.732 s 3.08 %
L2-E Z3 5.249 Ω 5.249 Ω 78.00 ° 0.710 s n.t. 0.00 %
L2-E FIN 5.682 Ω 5.682 Ω 78.00 ° 1.000 s n.t. 0.00 %
L3-E Z1 0.693 Z 1 1.616 Ω 78.00 ° 0.020 s 0.020 s -1.87 %
L3-E Z1 0.953 Z 1 2.221 Ω 78.00 ° 0.020 s 0.032 s 58.13 %
L3-E Z2 1.064 Z 1 2.481 Ω 78.00 ° 0.360 s 0.382 s 6.04 %
L3-E Z2 1.176 Z 1 2.740 Ω 78.00 ° 0.360 s 0.382 s 6.08 %

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 5/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

State Fault Zone Z |Z| Angle Tripping time


Loop (relative) Reference Actual Deviation
L3-E Z2 0.607 Z 3 3.260 Ω 78.00 ° 0.360 s 0.381 s 5.94 %
L3-E Z3 0.672 Z 3 3.606 Ω 78.00 ° 0.710 s 0.732 s 3.15 %
L3-E Z3 4.471 Ω 4.471 Ω 78.00 ° 0.710 s 0.733 s 3.26 %
L3-E Z3 5.249 Ω 5.249 Ω 78.00 ° 0.710 s n.t. 0.00 %
L3-E FIN 5.682 Ω 5.682 Ω 78.00 ° 1.000 s n.t. 0.00 %
L1-L2 Z1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.032 s 60.63 %
L1-L2 Z1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.032 s 61.88 %
L1-L2 Z2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.383 s 6.32 %
L1-L2 Z2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.381 s 5.94 %
L1-L2 Z2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.383 s 6.42 %
L1-L2 Z3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.731 s 1.56 %
L1-L2 Z3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.732 s 1.65 %
L1-L2 Z3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.732 s 1.61 %
L1-L2 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %
L3-L1 Z1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.033 s 63.12 %
L3-L1 Z1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.033 s 66.87 %
L3-L1 Z2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.382 s 6.04 %
L3-L1 Z2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.388 s 7.85 %
L3-L1 Z2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.382 s 6.11 %
L3-L1 Z3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.733 s 1.86 %
L3-L1 Z3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.732 s 1.67 %
L3-L1 Z3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.732 s 1.72 %
L3-L1 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %
L2-L3 Z1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.032 s 58.13 %
L2-L3 Z1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.033 s 62.50 %
L2-L3 Z2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.382 s 6.08 %
L2-L3 Z2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.382 s 6.15 %
L2-L3 Z2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.382 s 6.08 %
L2-L3 Z3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.733 s 1.74 %
L2-L3 Z3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.737 s 2.29 %
L2-L3 Z3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.733 s 1.84 %
L2-L3 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %
L1-L2-L3 Z 1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.031 s 57.50 %
L1-L2-L3 Z 1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.031 s 57.50 %
L1-L2-L3 Z 2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.367 s 1.98 %
L1-L2-L3 Z 2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.368 s 2.15 %
L1-L2-L3 Z 2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.382 s 6.04 %

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 6/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

State Fault Zone Z |Z| Angle Tripping time


Loop (relative) Reference Actual Deviation
L1-L2-L3 Z 3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.732 s 1.63 %
L1-L2-L3 Z 3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.732 s 1.65 %
L1-L2-L3 Z 3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.732 s 1.63 %
L1-L2-L3 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 7/7

You might also like